| Plan Review Stops For Permit 20120483 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-03-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-26 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-26 |
Time |
13:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-02-16 |
|
|
Cont ID |
|
| Sent By |
mcphers |
Date |
2021-02-16 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-02-16 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2021-02-16 14:55:50 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A SURVEY SHOWING THE FOLLOWING | | | INFORMATION 107.2.5 SITE PLAN. THE CONSTRUCTION | | | DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT | | | SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE | | | THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED | | | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS | | | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN | | | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE | | | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE | | | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED | | | WATER RETAINING SWALES) | | | | | | 2) JOB VALUE = HAS BEEN REVISED ON THE ADDED PLAN | | | REVIEW FORM. OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-12-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-12-28 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-28 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2020-12-28 14:31:44 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE BUILDING DESIGNER OF RECORD. | | | 2) PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA | | | PRODUCT APPROVAL FOR THE MASONITE DOORS. | | | 3) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE | | | CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT | | | APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND SEALED | | | ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR | | | ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A | | | HIGHER WIND PRESSURE - SEE GENERAL LIMITATION NOTES ON | | | THE PRODUCT APPROVAL. | | | 4) PLEASE PROVIDE A SURVEY SHOWING THE FOLLOWING | | | INFORMATION 107.2.5 SITE PLAN. THE CONSTRUCTION | | | DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT | | | SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE | | | THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED | | | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS | | | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN | | | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE | | | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE | | | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED | | | WATER RETAINING SWALES) | | | 5) CEILING INSULATION R30 USED IN A 2X6 JOIST WILL NOT | | | ALLOW THE REQUIRED 1 INCH GAP FOR VENTILATION FBC | | | R806.3 VENT AND INSULATION CLEARANCE. | | | WHERE EAVE OR CORNICE VENTS ARE INSTALLED, INSULATION | | | SHALL NOT BLOCK THE FREE FLOW OF AIR. NOT LESS THAN A | | | 1-INCH (25 MM) SPACE SHALL BE PROVIDED BETWEEN THE | | | INSULATION AND THE ROOF SHEATHING AND AT THE LOCATION | | | OF THE VENT. | | | 6) JOB VALUE = FROM THE ICC BUILDING VALUATION DATA - | | | 208 SQ. FT. X $ 122.00 PER SQ. FT. = $ 25,376.00 + 75 | | | SQ. FT. X $ 48.00 PER SQ. FT. = $ 3600.00 = TOTAL JOB | | | VALUE $ 28,967.00 - PLEASE REVISE THE BUILDING PERMIT | | | APPLICATION JOB VALUE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2020-12-28 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2020-12-28 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2020-12-28 |
Time |
11:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-04-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-04-28 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-04-21 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-04-08 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-04-08 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-03-08 |
Time |
11:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-03-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-03-03 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-01-27 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-01-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-01-20 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2020-12-14 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2021-06-03 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-06-03 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-05-05 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2021-06-03 12:20:43 | RECEIPT MU-2021-027062 - $1945.04 - PAID | | 2021-05-05 12:20:44 | 05/05/21 IMPACT FEE QUESTIONNAIRE UPLAODED IN | | | PROJECTDOX. EMAILED PBC IMPACT OFFICE FOR REVIEW. CC |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-12-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-12-28 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-28 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2020-12-28 14:34:53 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2021-02-02 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-02-02 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-02 |
Time |
09:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-12-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-18 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-18 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2020-12-18 13:49:36 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20120483 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS NEW | | | ADDITION. FBC EC 101.5.1.1.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2020-12-15 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-12-15 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-12-15 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2020-12-15 15:03:27 | 12/15/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2021-02-16 |
|
|
Cont ID |
|
| Sent By |
mcphers |
Date |
2021-02-16 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-02-16 |
Time |
14:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-12-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-12-28 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-28 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2020-12-28 14:33:11 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-04-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-04-28 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-04-28 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-03-26 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-26 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-26 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2021-03-26 13:06:10 | AS NOTED ON THE LAST REVIEW - - - | | | | | | SHEET A-2 IS A COPY OF A DIGITAL SIGNATURE. THE | | | ENGINEERING BOARD DID NOT RENEW THE POLICY TO ALLOW A | | | COPY SO WE CAN NO LONGER ACCEPT THEM. PLEASE SUBMIT AN | | | ORIGINAL DIGITAL SIGNATURE AND SEAL. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-02-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-02 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-02 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2021-02-02 10:30:11 | SHEET A-2 IS A COPY OF A DIGITAL SIGNATURE. THE | | | ENGINEERING BOARD DID NOT RENEW THE POLICY TO ALLOW A | | | COPY SO WE CAN NO LONGER ACCEPT THEM. PLEASE SUBMIT AN | | | ORIGINAL DIGITAL SIGNATURE AND SEAL. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-12-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-18 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-18 |
Time |
13:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-04-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2021-04-07 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2021-03-01 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-03-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2021-03-01 |
Time |
|
Sent To |
I |
|
| Notes |
| 2021-03-01 12:50:18 | ADDRESS PREVIOUS ZONING COMMENTS | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-01-19 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-01-19 |
Time |
|
Rev Time |
|
| Received By |
rthermid |
Date |
2021-01-19 |
Time |
|
Sent To |
I |
|
| Notes |
| 2021-01-19 10:54:46 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 1/19/2021 | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PLEASE PROVIDE A SURVEY OF THE PROPERTY SHOWING THE | | | LOCATION OF THE PROPOSED WORK. ALSO SHOW THE SETBACK OF | | | THE PROPOSED WORK TO ALL PROPERTY LINES. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | | LIKE TO RESUBMIT ELECTRONICALY, EMAIL | | | [email protected] AND REQUEST TO HAVE YOUR | | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN | | | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | | ARE FINISHED UPLOADING. | | | | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | TTY: 800.955.8771 | | | E: [email protected] | | | W: WPB.ORG | | | |
|
|