| 2021-02-22 16:16:23 | 2NDREVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120481 |
| | 2/22/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST. |
| | NOTES HAVE BEEN ADDED IN CAP LETTERS. PLEASE COMPLY. |
| | |
| | 1) SHEET G-1.1: THE MARKED-UP SITE PLAN SHALL BE |
| | DIGITALLY SIGNED AND SEALED BY THE ARCHITECT OF RECORD |
| | IN ACCORDANCE WITH SECTION 107.2.1 WPB AMENDMENTS, AND |
| | FL. STATUTE 481.221 AND SECTION 61G1-16.005 FAC. 2ND |
| | REQUEST FOR MARKED UP SHEET G-1.1 BY CLAREN |
| | ARCHITECTURE TO BE DIGITALLY SIGNED AND SEALED. |
| | |
| | 2) G-1.1: THERE IS NO RECENT RECORD OF A BACKFLOW |
| | PREVENTER PERMIT AT THE 1321 ALPHA ST. PLEASE NOTE THAT |
| | A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. A |
| | SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW. A RED |
| | LINE NOTE WILL BE ADDED TO THE APPROVED SIGNED AND |
| | SEALED PLAN. |
| | |
| | 3) G-1.1: SHOW THE LOCATION OF THE WATER METER AND |
| | REQUIRED SHUTOFF VALVES AT THE METER AND AT THE |
| | TRAILER- SECTION 606.1 FBC P. SHUTOFF VALVES NOT SHOWN. |
| | A RED LINE NOTE WILL BE ADDED TO THE APPROVED PLAN. |
| | |
| | 4) G-1.1: PROVIDE SANITARY DRAINAGE AND WATER RISER |
| | DRAWINGS- SECTION 107.3.5.1.3 WPB AMENDMENTS. A RED |
| | LINE NOTE FOR CLEANOUTS WILL BE ADDED TO THE APPROVED |
| | PLAN. |
| | |
| | NEW COMMENT |
| | 1) THE COMMENT RESPONSE NARRATIVE STATES THE 1 IN. PVC |
| | WATER SERVICE LINE WILL BE RUN ABOVEGROUND. PLEASE |
| | INDICATE HOW THE SERVICE LINE WILL BE SECURED AND |
| | PROTECTED FROM DAMAGE- SECTION 305.7 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| 2021-02-22 16:13:47 | 2NDREVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120481 |
| | 2/22/2021CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST. |
| | NOTES HAVE BEEN ADDED IN CAP LETTERS. PLEASE COMPLY. |
| | 1) SHEET G-1.1: THE MARKED-UP SITE PLAN SHALL BE |
| | DIGITALLY SIGNED AND SEALED BY THE ARCHITECT OF RECORD |
| | IN ACCORDANCE WITH SECTION 107.2.1 WPB AMENDMENTS, AND |
| | FL. STATUTE 481.221 AND SECTION 61G1-16.005 FAC. 2ND |
| | REQUEST FOR MARKED UP SHEET G-1.1 BY CLAREN |
| | ARCHITECTURE TO BE DIGITALLY SIGNED AND SEALED. |
| | 2) G-1.1: THERE IS NO RECENT RECORD OF A BACKFLOW |
| | PREVENTER PERMIT AT THE 1321 ALPHA ST. PLEASE NOTE THAT |
| | A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. A |
| | SEPARTATE PERMIT IS REQUIRED FOR THE BACKFLOW. A RED |
| | LINE NOTE WILL BE ADDED TO THE APPROVED PLAN. |
| | 3) G-1.1: SHOW THE LOCATION OF THE WATER METER AND |
| | REQUIRED SHUTOFF VALVES AT THE METER AND AT THE |
| | TRAILER- SECTION 606.1 FBC P. SHUTOFF VALVES NOT SHOWN. |
| | A RED LINE NOTE WILL BE ADDED TO APPROVED PLAN. |
| | 4) G-1.1: PROVIDE SANITARY DRAINAGE AND WATER RISER |
| | DRAWINGS- SECTION 107.3.5.1.3 WPB AMENDMENTS. A RED |
| | LINE NOTE FOR CLEANOUTS WILL BE ADDED TO APPROVED |
| | DRAWING. |
| | NEW COMMENT |
| | 1) THE COMMENT RESPONSE NARRATIVE STATES THE 1 IN. PVC |
| | WATER SERVICE LINE WILL BE RUN ABOVEGROUND. PLEASE |
| | INDICATE HOW THE SERVICE LINE WILL BE SECURED AND |
| | PROTECTED FROM DAMAGE- SECTION 305.7 FBC P. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |