Plan Review Details - Permit 20120481
Plan Review Stops For Permit 20120481
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-02 Cont ID  
Sent By rmcphers Date 2021-03-02 Time 13:43 Rev Time 0.00
Received By rmcphers Date 2021-03-02 Time 13:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-12-22 Cont ID  
Sent By rmcphers Date 2020-12-22 Time 09:21 Rev Time 0.00
Received By rmcphers Date 2020-12-22 Time 09:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2021-05-12 Cont ID  
Sent By equinone Date 2021-05-12 Time 08:48 Rev Time 0.00
Received By equinone Date 2021-05-12 Time 08:48 Sent To  
Notes
2021-05-12 08:49:58NO ELECTRICAL REQUIRED. ELECTRICAL TEMPORARY WAS
 APPROVED UNDER PERMIT 21010537.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-02-18 Cont ID  
Sent By equinone Date 2021-02-18 Time 14:17 Rev Time 0.00
Received By equinone Date 2021-02-18 Time 14:17 Sent To  
Notes
2021-02-18 14:18:18CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
  
 ELECTRICAL REVIEW STATUS: FAILED, SAME COMMENTS AS
 FIRST REVIEW:
  
 1) PLEASE SPECIFY AVAILABLE SHORT CIRCUIT CURRENT FROM
 POWER COMPANY AND PROVIDE SHORT CIRCUIT CALCULATIONS UP
 TO SERVICE DISCONNECT
 2) PLEASE SPECIFY AIC RATINGS FOR SERVICE EQUIPMENT AND
 PANELS
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-18 Cont ID  
Sent By equinone Date 2020-12-18 Time 16:08 Rev Time 0.00
Received By equinone Date 2020-12-18 Time 16:08 Sent To  
Notes
2020-12-18 16:08:33CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
  
 ELECTRICAL REVIEW STATUS: FAILED, SEE COMMENTS BELOW.
  
 1) PLEASE SPECIFY AVAILABLE SHORT CIRCUIT CURRENT FROM
 POWER COMPANY AND PROVIDE SHORT CIRCUIT CALCULATIONS UP
 TO SERVICE DISCONNECT
 2) PLEASE SPECIFY AIC RATINGS FOR SERVICE EQUIPMENT AND
 PANELS
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-02-19 Cont ID  
Sent By pleduc Date 2021-02-19 Time   Rev Time 0.00
Received By pleduc Date 2021-02-19 Time 16:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-12-11 Cont ID  
Sent By pleduc Date 2020-12-11 Time   Rev Time 0.00
Received By pleduc Date 2020-12-11 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-05-18 Time   Rev Time 0.00
Received By aoliver Date 2021-05-11 Time 14:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-11 Cont ID  
Sent By lmarchan Date 2021-05-11 Time 11:07 Rev Time 0.00
Received By lmarchan Date 2021-02-10 Time 11:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-21 Cont ID  
Sent By ajones Date 2021-01-21 Time 16:18 Rev Time 0.00
Received By ajones Date 2020-12-09 Time 12:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-05-18 Cont ID  
Sent By ccole Date 2021-05-18 Time 13:53 Rev Time 0.00
Received By ccole Date 2021-05-18 Time 08:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-02-22 Cont ID  
Sent By ccole Date 2021-02-22 Time 16:13 Rev Time 0.00
Received By ccole Date 2021-02-22 Time 15:29 Sent To  
Notes
2021-02-22 16:16:232NDREVIEW FBC-2017 PLUMBING
 PERMIT- 20120481
 2/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST.
 NOTES HAVE BEEN ADDED IN CAP LETTERS. PLEASE COMPLY.
  
 1) SHEET G-1.1: THE MARKED-UP SITE PLAN SHALL BE
 DIGITALLY SIGNED AND SEALED BY THE ARCHITECT OF RECORD
 IN ACCORDANCE WITH SECTION 107.2.1 WPB AMENDMENTS, AND
 FL. STATUTE 481.221 AND SECTION 61G1-16.005 FAC. 2ND
 REQUEST FOR MARKED UP SHEET G-1.1 BY CLAREN
 ARCHITECTURE TO BE DIGITALLY SIGNED AND SEALED.
  
 2) G-1.1: THERE IS NO RECENT RECORD OF A BACKFLOW
 PREVENTER PERMIT AT THE 1321 ALPHA ST. PLEASE NOTE THAT
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. A
 SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW. A RED
 LINE NOTE WILL BE ADDED TO THE APPROVED SIGNED AND
 SEALED PLAN.
  
 3) G-1.1: SHOW THE LOCATION OF THE WATER METER AND
 REQUIRED SHUTOFF VALVES AT THE METER AND AT THE
 TRAILER- SECTION 606.1 FBC P. SHUTOFF VALVES NOT SHOWN.
 A RED LINE NOTE WILL BE ADDED TO THE APPROVED PLAN.
  
 4) G-1.1: PROVIDE SANITARY DRAINAGE AND WATER RISER
 DRAWINGS- SECTION 107.3.5.1.3 WPB AMENDMENTS. A RED
 LINE NOTE FOR CLEANOUTS WILL BE ADDED TO THE APPROVED
 PLAN.
  
 NEW COMMENT
 1) THE COMMENT RESPONSE NARRATIVE STATES THE 1 IN. PVC
 WATER SERVICE LINE WILL BE RUN ABOVEGROUND. PLEASE
 INDICATE HOW THE SERVICE LINE WILL BE SECURED AND
 PROTECTED FROM DAMAGE- SECTION 305.7 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2021-02-22 16:13:472NDREVIEW FBC-2017 PLUMBING
 PERMIT- 20120481
 2/22/2021CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST.
 NOTES HAVE BEEN ADDED IN CAP LETTERS. PLEASE COMPLY.
 1) SHEET G-1.1: THE MARKED-UP SITE PLAN SHALL BE
 DIGITALLY SIGNED AND SEALED BY THE ARCHITECT OF RECORD
 IN ACCORDANCE WITH SECTION 107.2.1 WPB AMENDMENTS, AND
 FL. STATUTE 481.221 AND SECTION 61G1-16.005 FAC. 2ND
 REQUEST FOR MARKED UP SHEET G-1.1 BY CLAREN
 ARCHITECTURE TO BE DIGITALLY SIGNED AND SEALED.
 2) G-1.1: THERE IS NO RECENT RECORD OF A BACKFLOW
 PREVENTER PERMIT AT THE 1321 ALPHA ST. PLEASE NOTE THAT
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. A
 SEPARTATE PERMIT IS REQUIRED FOR THE BACKFLOW. A RED
 LINE NOTE WILL BE ADDED TO THE APPROVED PLAN.
 3) G-1.1: SHOW THE LOCATION OF THE WATER METER AND
 REQUIRED SHUTOFF VALVES AT THE METER AND AT THE
 TRAILER- SECTION 606.1 FBC P. SHUTOFF VALVES NOT SHOWN.
 A RED LINE NOTE WILL BE ADDED TO APPROVED PLAN.
 4) G-1.1: PROVIDE SANITARY DRAINAGE AND WATER RISER
 DRAWINGS- SECTION 107.3.5.1.3 WPB AMENDMENTS. A RED
 LINE NOTE FOR CLEANOUTS WILL BE ADDED TO APPROVED
 DRAWING.
 NEW COMMENT
 1) THE COMMENT RESPONSE NARRATIVE STATES THE 1 IN. PVC
 WATER SERVICE LINE WILL BE RUN ABOVEGROUND. PLEASE
 INDICATE HOW THE SERVICE LINE WILL BE SECURED AND
 PROTECTED FROM DAMAGE- SECTION 305.7 FBC P.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-23 Cont ID  
Sent By ccole Date 2020-12-23 Time 12:05 Rev Time 0.00
Received By ccole Date 2020-12-23 Time 10:58 Sent To  
Notes
2020-12-23 12:05:511ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20120481
 12/23/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET G-1.1: THE MARKED-UP SITE PLAN SHALL BE
 DIGITALLY SIGNED AND SEALED BY THE ARCHITECT OF RECORD
 IN ACCORDANCE WITH SECTION 107.2.1 WPB AMENDMENTS, AND
 FL. STATUTE 481.221 AND SECTION 61G1-16.005 FAC.
  
 2) G-1.1: THERE IS NO RECENT RECORD OF A BACKFLOW
 PREVENTER PERMIT AT THE 1321 ALPHA ST. PLEASE NOTE THAT
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 3) G-1.1: SHOW THE LOCATION OF THE WATER METER AND
 REQUIRED SHUTOFF VALVES AT THE METER AND AT THE
 TRAILER- SECTION 606.1 FBC P.
  
 4) G-1.1: PROVIDE SANITARY DRAINAGE AND WATER RISER
 DRAWINGS- SECTION 107.3.5.1.3 WPB AMENDMENTS.
  
 5) THE $2800.00 PERMIT VALUE APPEARS LOW FOR THE ENTIRE
 SCOPE OF THE PROJECT. PLEASE PROVIDE COPIES OF SIGNED
 CONTRACTS AND/OR ESTIMATES AND INVOICES FOR THE
 BUILDING, PLUMBING AND ELECTRICAL SITE WORK, TRAILER
 AND HOLDING TANK INSTALLATIONS, TRAILER LEASING AND
 HOLDING TANK MAINTENANCE AGREEMENTS. PLEASE INCLUDE A
 PUMP-OUT SCHEDULE FOR THE TANK.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-02-22 Cont ID  
Sent By shill Date 2021-02-22 Time 12:55 Rev Time 0.00
Received By shill Date 2021-02-22 Time 12:55 Sent To  
Notes
2021-02-22 12:55:40DOCS W/MASTER, INSPECTIONS ONLY
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-18 Cont ID  
Sent By ccole Date 2021-05-18 Time 13:53 Rev Time 0.00
Received By ccole Date 2021-05-18 Time 08:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-03-02 Cont ID  
Sent By rmcphers Date 2021-03-02 Time 13:43 Rev Time 0.00
Received By rmcphers Date 2021-03-02 Time 13:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-12-22 Cont ID  
Sent By rmcphers Date 2020-12-22 Time 09:21 Rev Time 0.00
Received By rmcphers Date 2020-12-22 Time 09:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-05-11 Cont ID  
Sent By ajones Date 2021-05-11 Time 11:01 Rev Time 0.00
Received By ajones Date 2021-05-11 Time 11:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-01-21 Cont ID  
Sent By avann Date 2021-01-21 Time 16:18 Rev Time 0.00
Received By ajones Date 2021-01-21 Time 16:18 Sent To  
Notes
***NONE***