| 2020-12-10 10:01:05 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 |
| | [email protected] |
| | |
| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC R 301 PROVIDE CERTIFIED ENGINEER LETTER |
| | VERIFYING EXISTING ROOF STRUCTURE CAN WITHSTAND THE |
| | ADDITIONAL LOADS IMPOSED ON IT BY CEMENT TILE |
| | INSTALLATION. |
| | 2.FBC R 9053.2 REVISE ROOF DIAGRAM TO PROVIDE ROOF |
| | SLOPE. |
| | 3. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE COUNTY NOA |
| | 19-0814.02 COVERS MULTIPLE ATTACHMENT SYSTEMS; |
| | MECHANICAL, ADHESIVE AND MORTAR SET. ALL APPLICABLE |
| | DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON |
| | THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS |
| | NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. (IF ADHESIVE PROVIDE |
| | COMPLETE SET OF PRODUCT APPROVALS/NOA?S. |
| | 4. SUBMITTED PRODUCT APPROVAL FL5374-R4 HAS BEEN |
| | REVISED TO FL5374-R5. PLEASE PROVIDE A COMPLETE SET. |
| | INCLUDE COVER SHEET(S). ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3. |
| | 5. SUBMITTED MIAMI-DADE COUNTY NOA 19-0311.04 COVERS |
| | MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH E(8). ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. (IF |
| | APPLICABLE. PLEASE PROVIDE ENGINEER'S SIGNED AND SEALED |
| | FASTENER SPACING DETAIL WITH CALCULATIONS FOR |
| | PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL |
| | LIMITATIONS #7). |
| | |