| 2021-01-06 11:03:24 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20120439 |
| | 1/6/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A1.01: BASED ON THE CONSTRUCTION PLANS, PLEASE |
| | MODIFY NOTE #8 TO INCLUDE DEMOLITION OF THE TOILET |
| | COMPARTMENTS, GRAB BARS, ACCESSORIES ETC.- SECTION |
| | 107.2.1 WPB. |
| | |
| | 2) SHEETS A1.11 & A1.12, A4.21: PROVIDE ACCESSIBLE AND |
| | STANDARD COMPARTMENT DIMENSIONS AND DETAILS- SECTIONS- |
| | 604.8.1- 604.8.3 FBC ACC, AND SECTION 405.3.1 FBC P. |
| | |
| | A) ADVISORY 604.8.1.6 LAVATORY AND 604.8.1.7 FBC ACC- |
| | WATER CLOSET. FLORIDA LAW, SECTION 553.504(5), F.S., |
| | STIPULATES THAT "...REQUIRED BATHING ROOMS AND TOILET |
| | ROOMS IN NEW CONSTRUCTION SHALL BE DESIGNED AND |
| | CONSTRUCTED..." WITH AN ACCESSIBLE LAVATORY IN THE |
| | WHEELCHAIR ACCESSIBLE COMPARTMENT AND THE WATER CLOSET |
| | LOCATED IN A CORNER DIAGONAL TO THE DOOR. THE ADA |
| | STANDARDS FOR ACCESSIBLE DESIGN AND THEREFORE THIS CODE |
| | REQUIRE WHEELCHAIR ACCESSIBLE COMPARTMENTS IN NEW |
| | CONSTRUCTION AND IN ALTERATIONS OF EXISTING BUILDINGS |
| | TO HAVE SELF CLOSING DOORS. WHILE THE FLORIDA LAVATORY |
| | REQUIREMENT AND WATER CLOSET PLACEMENT APPLY ONLY TO |
| | NEW CONSTRUCTION, THEY ARE DESIRABLE FOR ALL WHEELCHAIR |
| | ACCESSIBLE COMPARTMENTS AND SHOULD BE CONSIDERED WHERE |
| | FEASIBLE. |
| | |
| | 3) REQUIRED DETAILS- FBC-17 ACCESSIBILITY. |
| | |
| | A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS |
| | IN THE ACCESSIBLE COMPARTMENTS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIMENSIONS FOR THE ACCESSIBLE |
| | LAVATORIES- SECTION 606.2. |
| | C) CENTERLINE OF THE ACCESSIBLE WATER CLOSETS FROM THE |
| | SIDE WALLS- SECTION 604.2. |
| | D) HEIGHTS OF THE ACCESSIBLE WATER CLOSET SEATS FROM |
| | THE FINISHED FLOORS- SECTION 604.4. |
| | E) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 |
| | F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE WATER CLOSETS- SECTION 604.5 & |
| | 609.4 |
| | G) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | H) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE ACCESSIBLE WATER CLOSETS- |
| | SECTION 604.7. |
| | I) KNEE AND TOE CLEARANCES FOR THE ACCESSIBLE |
| | LAVATORIES- SECTION 606.2. |
| | |
| | 4) SHEETS A1.01, P0.1, P2.1: INSTALLATION OF THE NEW |
| | CAFE SINK DRAIN MAY REQUIRE THE CONCRETE FLOOR SLAB TO |
| | BE X-RAYED TO IN ORDER TO LOCATE REINFORCING STEEL OR |
| | POST STRESSED FLOOR TENDONS. PLEASE PLACE A NOTE ON THE |
| | PLANS TO VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1 |
| | WPB. |
| | |
| | 5) P0.1 & P2.1: THE ANNUAL SPACE AROUND THE NEW DRAIN |
| | PIPE PENETRATION THROUGH THE CONCRETE SLAB MUST BE |
| | SEALED. PROVIDE A UL TESTED AND APPROVED FIRESTOPPING |
| | ASSEMBLY DETAIL ON THE PLAN- SECTION 714.4.1.2 FBC B. |
| | PLEASE PROVIDE SANITARY DRAIN PIPE MATERIAL |
| | SPECIFICATIONS- SECTION 303.2 FBC P. BASED ON |
| | MECHANICAL PLAN NOTES IT APPEARS THE DRAIN PIPING MAY |
| | BE RUNNING THROUGH PLENUM RATED SPACES WHERE PVC IOS |
| | PROHIBITED. |
| | |
| | 6) P0.1 & P2.1: DETAILS ON SHEET P0.1 INDICATE NEW |
| | WATER SUPPLY AND WATER HEATER FOR THE HANDICAP |
| | LAVATORY, HOWEVER THE DETAIL ON P2.1 INDICATES NEW |
| | WATER LINE AND HEATER AT THE CAFE SINK (NOTE 2). PLEASE |
| | CLARIFY- SECTION 107.2.1 WPB. |
| | |
| | 7) P0.1 & P2.1: REFER TO TABLE C404.5.1 FBC EC AND |
| | VERIFY COMPLIANCE FOR PIPING VOLUME AND MAXIMUM PIPING |
| | LENGTH FOR HOT WATER PIPING SUPPLYING THE PUBLIC |
| | LAVATORY FAUCETS FROM THE HEATED WATER SOURCE. PLEASE |
| | NOTE FOR EXAMPLE, THE MAXIMUM LENGTH FOR A 1/2 IN. PIPE |
| | IS 2 FT AND MAX VOLUME PER SECTION C404.5.2 IS 2 |
| | OUNCES. IT IS ALSO IMPORTMANT TO NOTE THAT |
| | RECIRCULATING HOT WATER SOURCES SYSTEMS ARE CONSIDERED |
| | SOURCES OF HEATED WATER. |
| | |
| | 8) P0.1 & P2.1: PROVIDE A WATER HAMMER ARRESTOR AND |
| | BACKFLOW PREVENTER FOR THE WATER SUPPLY LINE TO THE ICE |
| | MAKER- SECTIONS 604.9 & 608.3 FBC P. |
| | |
| | 9) P2.1: PROVIDE THE CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSION FOR THE ACCESSIBLE CAFE SINK- SECTION 606.2 |
| | FBC P. |
| | |
| | 10) P0.1 & P2.1: IT APPEARS A PUMP WILL BE REQUIRED FOR |
| | THE NEW CONDENSATE PIPING. PLEASE SHOW THE LOCATION AND |
| | PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN- SECTION |
| | 314.2.1 FBC P. INDICATE THE TYPE OF CONDENSATE PIPING |
| | TO BE INSTALLED- 314.2.2. PLEASE NOTE CONDENSATE DRAINS |
| | SHALL BE TRAPPED AS REQUIRED BY THE EQUIPMENT OR |
| | APPLIANCE MANUFACTURER- 314.2.4. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |