Plan Review Details - Permit 20120426
Plan Review Stops For Permit 20120426
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-01-12 Cont ID  
Sent By cpuell Date 2021-01-12 Time 16:33 Rev Time 0.00
Received By cpuell Date 2021-01-12 Time 16:33 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-12-17 Cont ID  
Sent By cpuell Date 2020-12-17 Time 10:28 Rev Time 0.00
Received By cpuell Date 2020-12-15 Time 09:39 Sent To  
Notes
2020-12-15 09:39:31PLEASE REACH OUT TO [email protected] TO ESTABLISH SUITE
 NUMBER

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-12-11 Cont ID  
Sent By shill Date 2020-12-11 Time 17:01 Rev Time 0.00
Received By shill Date 2020-12-11 Time 17:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-02-05 Cont ID  
Sent By jgomez Date 2021-02-05 Time 16:33 Rev Time 0.00
Received By jgomez Date 2021-02-05 Time 16:33 Sent To  
Notes
2021-02-05 16:34:04BUILDING REVIEW APPROVED WITH PROVISO:
 1- SOLAR SHADES TO COMPLY WITH THE TESTS REQUIRED BY
 SECTION 806.4 FBC-BUILDING FOR COMBUSTIBLE DECORATIVE
 MATERIALS EXCEPTION #3 OF SECTION 806.3 FBC-BUILDING
 2- INTERIOR FLOOR-WALL RUBBER BASE BASE TO COMPLY WITH
 TEST REQUIRED BY SECTION 806.8 FBC-BUILDING.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-01-27 Cont ID  
Sent By jgomez Date 2021-01-27 Time 17:30 Rev Time 0.00
Received By jgomez Date 2021-01-27 Time 11:07 Sent To  
Notes
2021-01-27 17:27:58BUILDING REVIEW APPROVED WITH PROVISO:
 1- SOLAR SHADES TO COMPLY WITH THE TESTS REQUIRED BY
 SECTION 806.4 FBC-BUILDING FOR COMBUSTIBLE DECORATIVE
 MATERIALS EXCEPTION #3 OF SECTION 806.3 FBC-BUILDING
 2- INTERIOR FLOOR-WALL RUBBER BASE BASE TO COMPLY WITH
 TEST REQUIRED BY SECTION 806.8 FBC-BUILDING.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-11 Cont ID  
Sent By leahy Date 2021-02-11 Time 13:12 Rev Time 0.00
Received By jleahy Date 2021-02-11 Time 07:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-26 Cont ID  
Sent By jleahy Date 2021-01-26 Time 10:17 Rev Time 0.00
Received By jleahy Date 2021-01-26 Time 09:47 Sent To  
Notes
2021-01-26 10:26:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E9.01
  
 PANEL SCHEDULES NEED TO ADD SUITE NUMER TO THE PANEL
 SCHEDULE FOR BRK BRANCH CIRCUIT NUMBERS 408.4
  
 PAGE E4.02
  
 RISER SHOULD INCLUDE WIRE SIZES ON FEEDERS TO AND FROM
 TRANSFORMER. 215.5

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-01-26 Cont ID  
Sent By jleahy Date 2021-01-26 Time 10:36 Rev Time 0.00
Received By jleahy Date 2021-01-26 Time 10:35 Sent To  
Notes
2021-01-26 10:37:32SEPARATE PERMITS REQUIRED FOR VOICE/DATE, ACCESS
 CONTROL, AND FIRE ALARM.
  
 SEPARATE PLANS REQUIRED FOR ACCESS CONTROL, AND FIRE
 ALARM
  
 JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-01-08 Cont ID  
Sent By pleduc Date 2021-01-08 Time   Rev Time 0.00
Received By pleduc Date 2021-01-06 Time 16:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-17 Cont ID  
Sent By lmarchan Date 2021-02-17 Time 17:06 Rev Time 0.00
Received By lmarchan Date 2021-02-03 Time 18:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-27 Cont ID  
Sent By jgomez Date 2021-01-27 Time 17:30 Rev Time 0.00
Received By jgomez Date 2021-01-08 Time 16:32 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-11 Cont ID  
Sent By shill Date 2021-01-11 Time 16:27 Rev Time 0.00
Received By shill Date 2020-12-31 Time 09:13 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-12-31 Cont ID  
Sent By lmarchan Date 2020-12-31 Time 13:47 Rev Time 0.00
Received By lmarchan Date 2020-12-31 Time 13:47 Sent To  
Notes
2020-12-31 13:48:12IMPACT REVIEW DONE UNDER 18090469

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-02-11 Cont ID  
Sent By medwards Date 2021-02-11 Time 08:50 Rev Time 0.00
Received By medwards Date 2021-02-11 Time 07:47 Sent To  
Notes
2021-02-11 08:52:27APPROVED WITH PRIVISO:
  
 PROVIDE FIRE DAMPER AT RATED WALL PENETRATION OF MAIN
 DUCTWORK TO TENANT SPACE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-21 Cont ID  
Sent By medwards Date 2021-01-21 Time 10:12 Rev Time 0.00
Received By medwards Date 2021-01-21 Time 08:39 Sent To  
Notes
2021-01-21 10:12:441ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20120426
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M601- TERMINAL UNIT SCHEDULE; VAV-10 THE
 NUMBERS DON?T SEEM TO MATCH UP. MAX. AIRFLOW RATE IS
 100 CFM BUT THE MIN. AIR FLOW RATE IS 210 CFM. SHEET
 M2.01 INDICATES THE CFM?S BEING SUPPLIED BY VAV-10 IS
 100. PLEASE CORRECT THE TABLE ON SHEET M601. FBC
 107.2.1
  
 2) SHEET M601- PLEASE PROVIDE OUTDOOR AIR CALCULATIONS
 BASED ON TABLE 403.3.1.1 INSTEAD OF THE NUMBER OF
 PEOPLE STATED. THE CALCULATIONS MUST MEET THE MINIMUMS
 FROM THE TABLE. FBC M TABLE 403.3.1.1
 (EXAMPLE) CONFERENCE ROOM- 262.5 SQ.FT.\1000 = .2625 X
 50 X 5 = 65.625; 262.5 X .06 = 15.75; 65.625 + 15.75 =
 81 CFM?S REQUIRED. THE VENTILATION AIR SCHEDULE SHOWS
 60 CFM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By ccole Date 2021-02-17 Time 10:17 Rev Time 0.00
Received By lcrespo Date 2021-02-17 Time 10:10 Sent To  
Notes
2021-02-17 10:17:3202/17/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-22 Cont ID  
Sent By ccole Date 2021-01-22 Time 10:54 Rev Time 0.00
Received By ccole Date 2021-01-22 Time 09:49 Sent To  
Notes
2021-01-22 10:55:101ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20120426
 1/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A3.01 & P4.01: SHOW THE WATER SUPPLY AND
 SANITARY DRAIN AND VENT PIPING FOR THE DISHWASHER AND
 ICE MACHINE IN THE ISOMETRIC DRAWINGS- SECTIONS 409.2,
 604.3, 604.4, 604.4, 802.1 FBC P. PLEASE INCLUDE THE
 LOCATIONS FOR THE REQUIRED WATER HAMMER ARRESTORS AND
 BACKFLOW PREVENTERS- SECTIONS 604.9 AND 608.3. PLEASE
 NOTE THAT CONDENSATION FROM COOLING COILS SHALL NOT
 DRAIN IN THE SANITARY SYSTEM- SEC. 90-126 WPB CODE OF
 ORDINANCES.
  
 2) SHEETS A.3.01 & A.4.03: PLEASE SHOW THE CLEAR FLOOR
 SPACE PARALLEL APPROACH DIAGRAM AND DIMENSIONS FOR THE
 NEW LOUNGE SINK, DISHWASHER AND ICE MACHINE- SECTIONS
 305.1 & 804.6, & 804.6.3 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By rgathrig Date 2021-02-17 Time 16:53 Rev Time 0.00
Received By rgathrig Date 2021-02-17 Time 16:53 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2021-01-14 Cont ID  
Sent By rgathrig Date 2021-01-14 Time 15:55 Rev Time 0.00
Received By rgathrig Date 2021-01-14 Time 15:55 Sent To  
Notes
2021-01-14 15:55:56PRIVATE PROVIDER REVIEW APPROVED WITH PROVISO
 THIS REVIEW IS FOR THE NOTICE TO BUILDING OFFICIAL,
 INSURANCE LIMITS, PLAN REVIEWERS, AND INSPECTORS ONLY.
 AFFIDAVITS WERE NOT REVIEWED FOR COMPLIANCE WITH THE
 PROJECT PAGES. HOWEVER, IT IS NOTED THAT THE PRIVATE
 PROVIDER WILL NEED TO CORRECT THE FORMAT OF THE
 AFFIDAVITS SUBMITTED TO HAVE HIS SIGNATURE AND
 ATTESTATION FOR ALL THE PAGES IN THE DESIGN DOCUMENTS
 REVIEWED FOR FLORIDA BUILDING CODE COMPLIANCE.
 PLAN REVIEW AFFIDAVITS WILL NEED TO BE REVIEWED AFTER
 THE PLAN REVIEW AUDITS ARE COMPLETE. THIS SUBMITTAL CAN
 MOVE ON TO THE FLORIDA BUILDING CODE REVIEW
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 5618056679
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-11 Cont ID  
Sent By medwards Date 2021-02-11 Time 09:00 Rev Time 0.00
Received By medwards Date 2021-02-11 Time 08:56 Sent To  
Notes
2021-02-05 16:39:51SIGNATURE ON ARCHITECTURAL SHEETS OK. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-27 Cont ID  
Sent By jgomez Date 2021-01-27 Time 17:35 Rev Time 0.00
Received By jgomez Date 2021-01-27 Time 17:35 Sent To  
Notes
***NONE***