| Plan Review Stops For Permit 20120390 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-04-12 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-04-12 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-04-12 |
Time |
15:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-03-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-03-01 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-03-01 |
Time |
06:15 |
Sent To |
|
|
| Notes |
| 2021-03-01 08:06:37 | PLAN REVIEW / BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER ? PX3169 / 1&2 FAMILY - SFP306 | | | INSPECTOR ? BN4338 | | | BUILDING OFFICIAL ? BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2014 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. TWO LIVING UNITS SEPERATED BY A FLOOR ASSEMBLY. | | | PROVIDE 1 HOUR RATED ASSEMBLY PER FBC R302.3. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-12-29 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-12-29 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-12-29 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2020-12-29 09:42:37 | PLAN REVIEW / BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2014 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE AN ENERGY SUBMITTAL. | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 2. IDENTIFY TYPE AND R-VALUE OF CEILING AND WALL | | | INSULATION ON PLANS. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 3. PROVIDE PRODUCT APPROVALS OF PROPOSED WINDOWS AND | | | DOORS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. | | | | | | DEFERAL OPTION: | | | | | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON | | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | | OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-03-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-03-01 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-03-01 |
Time |
06:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2020-12-29 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-12-29 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-12-29 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2020-12-29 09:34:03 | PROVISO: HIGH EFFICANCY LAMPS PER R404.1. CT | | 2020-12-29 09:14:12 | | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-03-12 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-03-12 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-03-12 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-12-30 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-12-30 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-12-30 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2020-12-30 15:50:10 | HISTORIC PROPERTY. HR WINDOWS NOT PERMITTED. ELEVATIONS | | | DO NOT MATCH EXISTING DETAILING OR OPENING SIZES THAT | | | ARE REQUIRED TO BE MAINTAINED. | | | | | | QUESTIONS, CONTACT: FRIEDERIKE MITTNER, CITY HISTORIC | | | PRESERVATION PLANNER | | | (561) 822-1457 OR [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2021-04-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-28 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-23 |
Time |
14:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-04-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-14 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-13 |
Time |
11:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-04-12 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-04-12 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-04-01 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-03-12 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-03-12 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-02-19 |
Time |
06:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-01-06 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-12-23 |
Time |
09:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2021-04-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-28 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-28 |
Time |
14:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2021-04-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-14 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-14 |
Time |
15:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2021-04-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-02 |
Time |
06:00 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-02 |
Time |
06:00 |
Sent To |
|
|
| Notes |
| 2021-04-02 06:00:20 | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS AND | | | MECHANICAL SYSTEM MUST BE DESIGNED BY A FLORIDA | | | LICENSED ENGINEER OR THE MECHANICAL CONTRACTOR THAT IS | | | THE PERMIT HOLDER AND IS INSTALLING THE SYSTEM. | | | FS 407.003 (H) | | | | | | 2) PLEASE PROVIDE THE MECHANICAL VENTILATION FOR EACH | | | APARTMENT AND THE CALCULATIONS AS TO HOW MUCH OUTDOOR | | | AIR WILL NEED TO BE INTRODUCED INTO EACH APARTMENT. FBC | | | M 403 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2021-02-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-24 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-23 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2021-02-24 08:31:28 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-20120390 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) MECHANICAL EQUIPMENT SIZING CALCULATIONS WERE NOT | | | SUBMITTED WITH THIS 2ND CYCLE PACKAGE, PLEASE PROVIDE. | | | FBC M 312.1 | | | | | | 2) PLEASE TELL WHAT THE USE OF THIS BUILDING IS. FBC | | | 107.2.1 | | | | | | 3) PLEASE EXPLAIN IF THIS BUILDING WILL BE NATURAL | | | VENTILATION OR MECHANICAL AND PROVIDE CALCULATIONS FOR | | | WHICH METHOD IS USED. FBC M 402; 403 | | | | | | 4) PLEASE SHOW A DETAIL OF THE DRYER DUCT AND SHOW HOW | | | YOU WILL BE PROTECTING THE PENETRATION OF THE RATED | | | FLOOR/CEILING ASSEMBLY. FBC M 607 | | | | | | 5) PLEASE PROVIDE A DETAIL OF THE BATH EXHAUST FAN | | | PENETRATION OF THE RATED FLOOR/CEILING ASSEMBLY AND HOW | | | YOU WILL PROTECT THIS PENETRATION. FBC M 607 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-12-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-29 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-29 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2020-12-29 12:30:27 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20120390 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE EXISTING OCCUPANCY CLASSIFICATION AND | | | THE OCCUPANCY CLASSIFICATION IT IS PROPOSED TO BE. FBC | | | | | | 2) PLEASE SHOW ALL VERTICAL AND HORIZONTAL RATED | | | ASSEMBLIES. FBC | | | | | | 3) PLEASE SHOW HOW YOU WILL PROTECT THE FLOOR/CEILING | | | RATED ASSEMBLY AT BATHROOM EXHAUST FAN AND AT THE DRYER | | | DUCT PENETRATIONS. FBC M 607 | | | | | | 4) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC M 312.1 | | | | | | 5) PLEASE SHOW AUXILIARY AND SECONDARY DRAIN SYSTEMS | | | FOR THE DUCTLESS MINI-SPLIT SYSTEMS. BFC M 307.2.3 | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-02-23 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-02-23 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-02-23 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2021-02-23 11:52:32 | 02/23/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-12-29 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-12-29 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-12-29 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2020-12-29 15:38:04 | 12/29/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. ON SHEET SP01, PLEASE PROVIDE CODE YEAR AND | | | PLUMBING REFERENCED USED PER THE WPB AMENDMENTS TO THE | | | FBC SEC. 101.4 REFERENCED CODES. | | | | | | 2. A SET OF PLANS HAS BEEN SUBMITTED THAT ARE NOT CLEAR | | | AND BURRY. PLEASE SUBMIT OR PROVIDE A CLEAR SET OF | | | PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1.4 | | | QUALITY OF BUILDING PLANS. | | | | | | 3. SIGNED AND SEALED DRAWINGS NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | | SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE | | | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN | | | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR | | | SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW | | | REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND | | | ASKING FOR THE FORM. | | | | | | 4. ON SHEET P01; | | | | | | A. THE WATER RISER ISOMETRIC DIAGRAM SHOWS UNITS | | | UPSTAIRS AND DOWNSTAIRS TIED TOGETHER. THESE ARE CALLED | | | OUT AS SEPARATE UNITS AND NEED TO BE ONE VALVE ON THE | | | FIRST FLOOR AND ANOTHER ON THE SECOND FLOOR. EACH | | | DWELLING UNIT SHALL BE PROVIDED WITH AN ACCESSIBLE MAIN | | | SHUTOFF VALVE NEAR THE WATER SERVICE ENTRANCE PER THE | | | 2017 FBC SEC. R 2903.9.1 SERVICE VALVE. | | | | | | B. PLEASE SHOW THE WATER HAMMERS ON THE DISHWASHER, | | | REFRIGERATOR, AND WASHING MACHINE ON THE ISOMETRIC | | | DRAWING PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | C. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR | | | SHUTTING OFF WITHOUT MOVING UNITS, 2017 FBC SEC. R | | | 2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE | | | SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS | | | PANEL OR SIMILAR REMOVABLE OBSTRUCTION. | | | | | | D. HOT WATER PIPES IN THE FIRST FLOOR NOT IN CONDITION | | | SPACE NEED SHALL BE INSULATED WITH A MINIMUM R-3 PER | | | THE 2017 FBC SEC. RE 403.5.3. | | | | | | E. IF REQUIRED, PLEASE PROVIDE DETAIL FOR THE WATER | | | HEATER AND HOW IT WILL DRAIN OUTSIDE WITH THE METHOD | | | USED TO PREVENT THE RODENT FROM ENTERING THROUGH THAT | | | DRAIN PER THE 2017 FBC R 2801.6.2 AND 2017 FBC R | | | 2606.1. | | | | | | F. PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR THE | | | TANKLESS WATER HEATER AND LOCATION TO ACCESS IT PER THE | | | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | G. PLEASE REMOVE ANY DETAILS THAT DO NOT PERTAIN TO | | | THIS STRUCTURE, I. E. (FLOOR DRAIN) PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | 5. ON SHEET P-2 FOR THE SANITARY ISOMETRIC; | | | | | | A. PLEASE SEPARATE EACH FLOOR TO ITS SEPARATE SYSTEM TO | | | EACH DWELLING AS THERE ARE CALLED OUT TWO DIFFERENT | | | UNITS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | B. THE KITCHEN SINK MUST BE DOWNSTREAM OF THE WET VENT | | | BATHROOM GROUP. THE KITCHEN SINK CANNOT DISCHARGE INTO | | | THE WET VET OF A BATHROOM GROUP. IT MUST BE DOWNSTREAM | | | PER THE 2017 FBC SECTION R3108.1 HORIZONTAL WET VENT | | | PERMITTED. | | | | | | C. THE SHOWER DOWNSTAIRS HAS A DRY VENT AND REQUIRES A | | | WET VENT PER THE 2017 FBC SEC. P3108.2.1. | | | | | | D. THE UPSTAIRS SHOWER HAS TO BE RE-VENTED SIX INCHES | | | ABOVE THE FLOOD RIM LEVEL PER THE 2017 FBC SEC. R | | | P3111.2.2. | | | | | | E. PLEASE SHOW THE DOWN-STAIRS WASHING MACHINE ON A | | | SANITARY FITTING ABOVE THE NINETY-DEGREE ELBOW PER THE | | | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. | | | | | | F. PLEASE SHOW ALL LAVS AND SINK ON A SANITARY TEE | | | ABOVE GROWN PER THE WPB AMENDMENTS TO THE FBC SEC. | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | G. THERE IS A CROSS TEE FITTING ON THE TWO UPSTAIRS | | | BATHROOMS THAT CONNECT TO A KITCHEN SINK AND ANOTHER | | | SANITARY DRAIN THAT SEEMS TO BE CONFUSING. PLEASE | | | CHANGE TO SHOW CLARITY PER THE WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2021-04-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-28 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-28 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2021-04-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-14 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-14 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2021-04-14 15:47:29 | THE ENGINEER SIGNATURE AND STAMP APPEAR TO BE A COPY. | | | PLEASE EITHER UPLOAD AN ORIGINAL DIGITALLY SIGNED AND | | | SEALED DRAWINGS OR YOU CAN BRING THE ORIGINAL SIGNED | | | AND SEALED PAPER DRAWINGS TO THE OFFICE. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-04-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-02 |
Time |
05:54 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-02 |
Time |
05:53 |
Sent To |
|
|
| Notes |
| 2021-04-02 05:59:36 | SHEET A01 IS APPROVED AS IT HAS THE SIGNED AND SEALED | | | PAPER DRAWING. IT WILL BE ROUTED TO STORAGE. | | | | | | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS AND | | | MECHANICAL SYSTEM MUST BE DESIGNED BY A FLORIDA | | | LICENSED ENGINEER OR THE MECHANICAL CONTRACTOR THAT IS | | | THE PERMIT HOLDER AND IS INSTALLING THE SYSTEM. | | | FS 407.003 (H) | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-02-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-22 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-22 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2021-02-22 16:21:50 | ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO | | | STORAGE.ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-12-29 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-12-29 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-12-29 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2020-12-29 09:34:52 | PLAN REVIEW / SIGNATURES | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | | SIGNATURE. | | | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | | WET SEAL AND SIGNATURE TO: | | | | | | BUILDING DIVISION, FIRST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST | | | WEST PALM BEACH, FL 33401 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-03-12 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2021-03-12 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2021-03-12 |
Time |
15:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2021-01-06 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2021-01-06 |
Time |
10:30 |
Sent To |
Z |
|
| Notes |
| 2021-01-06 10:30:26 | SEE HISTORIC COMMENTS REGARDING WINDOWS AND WINDOW | | | OPENINGS | | | | | | IS THE MATERIAL OF THE EXTERIOR BEING MODIFIED? WILL | | | THE WHITE TRIM BE REMOVED? PLEASE CLARIFY ON ELEVATIONS | | | AND CONFIRM WITH HISTORIC PRESERVATION PLANNER WHETHER | | | MATERIAL CAN BE MODIFIED | | | | | | WILL THE ROOF FEATURES BE REMOVED? PLEASE CLARIFY ON | | | ELEVATIONS AND CONFIRM WITH HISTORIC PRESERVATION | | | PLANNER WHETHER THESE CAN BE MODIFIED | | | | | | FROM STREET VIEW IMAGES, THE FRONT WALL IS FALLING | | | APART - WHAT IS THE PLAN FOR THIS WALL? PLEASE INDICATE | | | ON SITE PLAN | | | | | | THE CHAIN LINK FENCE IS NOT PERMITTED. THERE IS NO | | | RECORD OF PERMIT FOR THIS CHAIN LINK FENCE. IT IS OFF | | | PROPERTY IN SOME PORTIONS AND IT EXCEEDS THE PERMITTED | | | HEIGHT WITHIN THE FRONT SETBACK. FENCE WITHIN THE FRONT | | | SETBACK CAN BE CHAIN LINK ONLY IF SCREENED BY A | | | LANDSCAPE HEDGE AND CAN ONLY BE FOUR FEET IN HEIGHT. IF | | | BEING REMOVED, PLEASE INDICATE ON SITE PLAN. IF BEING | | | REPLACED, PLEASE SUBMIT FENCE PERMIT TO BE REVIEWED | | | SEPARATELY MEETING REQUIREMENTS OF SECTION 94-109. | | | | | | |
|
|