Plan Review Details - Permit 20120390
Plan Review Stops For Permit 20120390
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-12 Cont ID  
Sent By cthroop Date 2021-04-12 Time 15:47 Rev Time 0.00
Received By cthroop Date 2021-04-12 Time 15:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-01 Cont ID  
Sent By cthroop Date 2021-03-01 Time 08:04 Rev Time 0.00
Received By cthroop Date 2021-03-01 Time 06:15 Sent To  
Notes
2021-03-01 08:06:37PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? PX3169 / 1&2 FAMILY - SFP306
 INSPECTOR ? BN4338
 BUILDING OFFICIAL ? BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. TWO LIVING UNITS SEPERATED BY A FLOOR ASSEMBLY.
 PROVIDE 1 HOUR RATED ASSEMBLY PER FBC R302.3.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-29 Cont ID  
Sent By cthroop Date 2020-12-29 Time 09:34 Rev Time 0.00
Received By cthroop Date 2020-12-29 Time 07:10 Sent To  
Notes
2020-12-29 09:42:37PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 2. IDENTIFY TYPE AND R-VALUE OF CEILING AND WALL
 INSULATION ON PLANS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE PRODUCT APPROVALS OF PROPOSED WINDOWS AND
 DOORS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 DEFERAL OPTION:
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By cthroop Date 2021-03-01 Time 08:04 Rev Time 0.00
Received By cthroop Date 2021-03-01 Time 06:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-12-29 Cont ID  
Sent By cthroop Date 2020-12-29 Time 09:12 Rev Time 0.00
Received By cthroop Date 2020-12-29 Time 07:10 Sent To  
Notes
2020-12-29 09:34:03PROVISO: HIGH EFFICANCY LAMPS PER R404.1. CT
2020-12-29 09:14:12 
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-03-12 Cont ID  
Sent By fmittner Date 2021-03-12 Time 14:58 Rev Time 0.00
Received By fmittner Date 2021-03-12 Time 14:58 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2020-12-30 Cont ID  
Sent By fmittner Date 2020-12-30 Time 15:48 Rev Time 0.00
Received By fmittner Date 2020-12-30 Time 15:48 Sent To  
Notes
2020-12-30 15:50:10HISTORIC PROPERTY. HR WINDOWS NOT PERMITTED. ELEVATIONS
 DO NOT MATCH EXISTING DETAILING OR OPENING SIZES THAT
 ARE REQUIRED TO BE MAINTAINED.
  
 QUESTIONS, CONTACT: FRIEDERIKE MITTNER, CITY HISTORIC
 PRESERVATION PLANNER
 (561) 822-1457 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-04-28 Cont ID  
Sent By medwards Date 2021-04-28 Time 14:30 Rev Time 0.00
Received By medwards Date 2021-04-23 Time 14:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-04-14 Cont ID  
Sent By medwards Date 2021-04-14 Time 15:47 Rev Time 0.00
Received By medwards Date 2021-04-13 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-12 Cont ID  
Sent By cthroop Date 2021-04-12 Time 15:48 Rev Time 0.00
Received By cthroop Date 2021-04-01 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-12 Cont ID  
Sent By lmarchan Date 2021-03-12 Time 16:40 Rev Time 0.00
Received By lmarchan Date 2021-02-19 Time 06:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-06 Cont ID  
Sent By lmarchan Date 2021-01-06 Time 11:12 Rev Time 0.00
Received By lmarchan Date 2020-12-23 Time 09:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-04-28 Cont ID  
Sent By medwards Date 2021-04-28 Time 14:28 Rev Time 0.00
Received By medwards Date 2021-04-28 Time 14:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-04-14 Cont ID  
Sent By medwards Date 2021-04-14 Time 15:43 Rev Time 0.00
Received By medwards Date 2021-04-14 Time 15:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-04-02 Cont ID  
Sent By medwards Date 2021-04-02 Time 06:00 Rev Time 0.00
Received By medwards Date 2021-04-02 Time 06:00 Sent To  
Notes
2021-04-02 06:00:201) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS AND
 MECHANICAL SYSTEM MUST BE DESIGNED BY A FLORIDA
 LICENSED ENGINEER OR THE MECHANICAL CONTRACTOR THAT IS
 THE PERMIT HOLDER AND IS INSTALLING THE SYSTEM.
 FS 407.003 (H)
  
 2) PLEASE PROVIDE THE MECHANICAL VENTILATION FOR EACH
 APARTMENT AND THE CALCULATIONS AS TO HOW MUCH OUTDOOR
 AIR WILL NEED TO BE INTRODUCED INTO EACH APARTMENT. FBC
 M 403
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-02-24 Cont ID  
Sent By medwards Date 2021-02-24 Time 08:31 Rev Time 0.00
Received By medwards Date 2021-02-23 Time 14:19 Sent To  
Notes
2021-02-24 08:31:282ND REVIEW FBC-2020 MECHANICAL
 PERMIT-20120390
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MECHANICAL EQUIPMENT SIZING CALCULATIONS WERE NOT
 SUBMITTED WITH THIS 2ND CYCLE PACKAGE, PLEASE PROVIDE.
 FBC M 312.1
  
 2) PLEASE TELL WHAT THE USE OF THIS BUILDING IS. FBC
 107.2.1
  
 3) PLEASE EXPLAIN IF THIS BUILDING WILL BE NATURAL
 VENTILATION OR MECHANICAL AND PROVIDE CALCULATIONS FOR
 WHICH METHOD IS USED. FBC M 402; 403
  
 4) PLEASE SHOW A DETAIL OF THE DRYER DUCT AND SHOW HOW
 YOU WILL BE PROTECTING THE PENETRATION OF THE RATED
 FLOOR/CEILING ASSEMBLY. FBC M 607
  
 5) PLEASE PROVIDE A DETAIL OF THE BATH EXHAUST FAN
 PENETRATION OF THE RATED FLOOR/CEILING ASSEMBLY AND HOW
 YOU WILL PROTECT THIS PENETRATION. FBC M 607
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-29 Cont ID  
Sent By medwards Date 2020-12-29 Time 12:30 Rev Time 0.00
Received By medwards Date 2020-12-29 Time 10:24 Sent To  
Notes
2020-12-29 12:30:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20120390
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE EXISTING OCCUPANCY CLASSIFICATION AND
 THE OCCUPANCY CLASSIFICATION IT IS PROPOSED TO BE. FBC
  
 2) PLEASE SHOW ALL VERTICAL AND HORIZONTAL RATED
 ASSEMBLIES. FBC
  
 3) PLEASE SHOW HOW YOU WILL PROTECT THE FLOOR/CEILING
 RATED ASSEMBLY AT BATHROOM EXHAUST FAN AND AT THE DRYER
 DUCT PENETRATIONS. FBC M 607
  
 4) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC M 312.1
  
 5) PLEASE SHOW AUXILIARY AND SECONDARY DRAIN SYSTEMS
 FOR THE DUCTLESS MINI-SPLIT SYSTEMS. BFC M 307.2.3
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-02-23 Cont ID  
Sent By lcrespo Date 2021-02-23 Time 11:52 Rev Time 0.00
Received By lcrespo Date 2021-02-23 Time 11:52 Sent To  
Notes
2021-02-23 11:52:3202/23/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-29 Cont ID  
Sent By lcrespo Date 2020-12-29 Time 15:37 Rev Time 0.00
Received By lcrespo Date 2020-12-29 Time 13:29 Sent To  
Notes
2020-12-29 15:38:0412/29/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET SP01, PLEASE PROVIDE CODE YEAR AND
 PLUMBING REFERENCED USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 101.4 REFERENCED CODES.
  
 2. A SET OF PLANS HAS BEEN SUBMITTED THAT ARE NOT CLEAR
 AND BURRY. PLEASE SUBMIT OR PROVIDE A CLEAR SET OF
 PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1.4
 QUALITY OF BUILDING PLANS.
  
 3. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 4. ON SHEET P01;
  
 A. THE WATER RISER ISOMETRIC DIAGRAM SHOWS UNITS
 UPSTAIRS AND DOWNSTAIRS TIED TOGETHER. THESE ARE CALLED
 OUT AS SEPARATE UNITS AND NEED TO BE ONE VALVE ON THE
 FIRST FLOOR AND ANOTHER ON THE SECOND FLOOR. EACH
 DWELLING UNIT SHALL BE PROVIDED WITH AN ACCESSIBLE MAIN
 SHUTOFF VALVE NEAR THE WATER SERVICE ENTRANCE PER THE
 2017 FBC SEC. R 2903.9.1 SERVICE VALVE.
  
 B. PLEASE SHOW THE WATER HAMMERS ON THE DISHWASHER,
 REFRIGERATOR, AND WASHING MACHINE ON THE ISOMETRIC
 DRAWING PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR
 SHUTTING OFF WITHOUT MOVING UNITS, 2017 FBC SEC. R
 2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE
 SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS
 PANEL OR SIMILAR REMOVABLE OBSTRUCTION.
  
 D. HOT WATER PIPES IN THE FIRST FLOOR NOT IN CONDITION
 SPACE NEED SHALL BE INSULATED WITH A MINIMUM R-3 PER
 THE 2017 FBC SEC. RE 403.5.3.
  
 E. IF REQUIRED, PLEASE PROVIDE DETAIL FOR THE WATER
 HEATER AND HOW IT WILL DRAIN OUTSIDE WITH THE METHOD
 USED TO PREVENT THE RODENT FROM ENTERING THROUGH THAT
 DRAIN PER THE 2017 FBC R 2801.6.2 AND 2017 FBC R
 2606.1.
  
 F. PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER AND LOCATION TO ACCESS IT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 G. PLEASE REMOVE ANY DETAILS THAT DO NOT PERTAIN TO
 THIS STRUCTURE, I. E. (FLOOR DRAIN) PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. ON SHEET P-2 FOR THE SANITARY ISOMETRIC;
  
 A. PLEASE SEPARATE EACH FLOOR TO ITS SEPARATE SYSTEM TO
 EACH DWELLING AS THERE ARE CALLED OUT TWO DIFFERENT
 UNITS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE KITCHEN SINK MUST BE DOWNSTREAM OF THE WET VENT
 BATHROOM GROUP. THE KITCHEN SINK CANNOT DISCHARGE INTO
 THE WET VET OF A BATHROOM GROUP. IT MUST BE DOWNSTREAM
 PER THE 2017 FBC SECTION R3108.1 HORIZONTAL WET VENT
 PERMITTED.
  
 C. THE SHOWER DOWNSTAIRS HAS A DRY VENT AND REQUIRES A
 WET VENT PER THE 2017 FBC SEC. P3108.2.1.
  
 D. THE UPSTAIRS SHOWER HAS TO BE RE-VENTED SIX INCHES
 ABOVE THE FLOOD RIM LEVEL PER THE 2017 FBC SEC. R
 P3111.2.2.
  
 E. PLEASE SHOW THE DOWN-STAIRS WASHING MACHINE ON A
 SANITARY FITTING ABOVE THE NINETY-DEGREE ELBOW PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. PLEASE SHOW ALL LAVS AND SINK ON A SANITARY TEE
 ABOVE GROWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. THERE IS A CROSS TEE FITTING ON THE TWO UPSTAIRS
 BATHROOMS THAT CONNECT TO A KITCHEN SINK AND ANOTHER
 SANITARY DRAIN THAT SEEMS TO BE CONFUSING. PLEASE
 CHANGE TO SHOW CLARITY PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-04-29 Cont ID  
Sent By medwards Date 2021-04-28 Time 14:29 Rev Time 0.00
Received By medwards Date 2021-04-28 Time 14:29 Sent To  
Notes
2021-04-28 14:30:21 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-04-14 Cont ID  
Sent By medwards Date 2021-04-14 Time 15:45 Rev Time 0.00
Received By medwards Date 2021-04-14 Time 15:45 Sent To  
Notes
2021-04-14 15:47:29THE ENGINEER SIGNATURE AND STAMP APPEAR TO BE A COPY.
 PLEASE EITHER UPLOAD AN ORIGINAL DIGITALLY SIGNED AND
 SEALED DRAWINGS OR YOU CAN BRING THE ORIGINAL SIGNED
 AND SEALED PAPER DRAWINGS TO THE OFFICE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-04-02 Cont ID  
Sent By medwards Date 2021-04-02 Time 05:54 Rev Time 0.00
Received By medwards Date 2021-04-02 Time 05:53 Sent To  
Notes
2021-04-02 05:59:36SHEET A01 IS APPROVED AS IT HAS THE SIGNED AND SEALED
 PAPER DRAWING. IT WILL BE ROUTED TO STORAGE.
  
 THE MECHANICAL EQUIPMENT SIZING CALCULATIONS AND
 MECHANICAL SYSTEM MUST BE DESIGNED BY A FLORIDA
 LICENSED ENGINEER OR THE MECHANICAL CONTRACTOR THAT IS
 THE PERMIT HOLDER AND IS INSTALLING THE SYSTEM.
 FS 407.003 (H)
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-22 Cont ID  
Sent By medwards Date 2021-02-22 Time 16:19 Rev Time 0.00
Received By medwards Date 2021-02-22 Time 16:19 Sent To  
Notes
2021-02-22 16:21:50ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-29 Cont ID  
Sent By cthroop Date 2020-12-29 Time 09:34 Rev Time 0.00
Received By cthroop Date 2020-12-29 Time 07:11 Sent To  
Notes
2020-12-29 09:34:52PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-03-12 Cont ID  
Sent By elevesqu Date 2021-03-12 Time 15:01 Rev Time 0.00
Received By elevesqu Date 2021-03-12 Time 15:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By elevesqu Date 2021-01-06 Time 10:30 Rev Time 0.00
Received By elevesqu Date 2021-01-06 Time 10:30 Sent To Z
Notes
2021-01-06 10:30:26SEE HISTORIC COMMENTS REGARDING WINDOWS AND WINDOW
 OPENINGS
  
 IS THE MATERIAL OF THE EXTERIOR BEING MODIFIED? WILL
 THE WHITE TRIM BE REMOVED? PLEASE CLARIFY ON ELEVATIONS
 AND CONFIRM WITH HISTORIC PRESERVATION PLANNER WHETHER
 MATERIAL CAN BE MODIFIED
  
 WILL THE ROOF FEATURES BE REMOVED? PLEASE CLARIFY ON
 ELEVATIONS AND CONFIRM WITH HISTORIC PRESERVATION
 PLANNER WHETHER THESE CAN BE MODIFIED
  
 FROM STREET VIEW IMAGES, THE FRONT WALL IS FALLING
 APART - WHAT IS THE PLAN FOR THIS WALL? PLEASE INDICATE
 ON SITE PLAN
  
 THE CHAIN LINK FENCE IS NOT PERMITTED. THERE IS NO
 RECORD OF PERMIT FOR THIS CHAIN LINK FENCE. IT IS OFF
 PROPERTY IN SOME PORTIONS AND IT EXCEEDS THE PERMITTED
 HEIGHT WITHIN THE FRONT SETBACK. FENCE WITHIN THE FRONT
 SETBACK CAN BE CHAIN LINK ONLY IF SCREENED BY A
 LANDSCAPE HEDGE AND CAN ONLY BE FOUR FEET IN HEIGHT. IF
 BEING REMOVED, PLEASE INDICATE ON SITE PLAN. IF BEING
 REPLACED, PLEASE SUBMIT FENCE PERMIT TO BE REVIEWED
 SEPARATELY MEETING REQUIREMENTS OF SECTION 94-109.
  
  