Plan Review Details - Permit 20120283
Plan Review Stops For Permit 20120283
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-04-08 Cont ID  
Sent By rmcphers Date 2021-04-08 Time 09:11 Rev Time 0.00
Received By rmcphers Date 2021-04-08 Time 09:05 Sent To  
Notes
2021-04-08 09:11:15VACUUM SYSTEM
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 3RD REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 SEE FIRE PLANS REVIEW ASKING FOR A CHANGE OF OCCUPANCY
 1) SHOW BUILDING CONSTRUCTION TYPE PER FBC CHAPTER 6
 2) SHOW OCCUPANCY CLASSIFICATION PER FBC CHAPTER 3 - IF
 CHANGING THE OCCUPANCY PLEASE SHOW THE PREVIOUS
 OCCUPANCY CLASSIFICATION.
 3) IS BUILDING SPRINKLERED OR NON SPRINKLERED.
 4) SHOW EXISTING FIRE RATED WALL LOCATIONS AND THE
 HOURLY FIRE RATING.
 5) SHOW BUILDING SQUARE FOOTAGE.
 6) SHOW UNIT SQUARE FOOTAGE.
 7) PLEASE PROVIDE A LIFE SAFETY PLAN WHICH SHALL
 INCLUDE ALL OF THE ABOVE ITEMS AND THE MEANS OF EGRESS
 SYSTEM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-14 Cont ID  
Sent By rmcphers Date 2021-01-14 Time 13:51 Rev Time 0.00
Received By rmcphers Date 2021-01-14 Time 13:51 Sent To  
Notes
2021-01-14 13:59:37VACUUM SYSTEM
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE MORE DETAILS - MOUNTED ON ROOF? -
 PASSING THRU WALL AND MOUNTED ON THE CEILING JOIST? -
 ARE THE WALLS FIRE RATED? - HOW IS IT MOUNTED? - HEIGHT
 FROM FLOOR?
 2) SHOW BUILDING CONSTRUCTION TYPE PER FBC CHAPTER 6
 3) SHOW OCCUPANCY CLASSIFICATION PER FBC CHAPTER 3 - IF
 CHANGING THE OCCUPANCY PLEASE SHOW THE PREVIOUS
 OCCUPANCY CLASSIFICATION.
 4) IS BUILDING SPRINKLERED OR NON SPRINKLERED.
 5) SHOW EXISTING FIRE RATED WALL LOCATIONS AND THE
 HOURLY FIRE RATING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-17 Cont ID  
Sent By rmcphers Date 2020-12-17 Time 14:31 Rev Time 0.00
Received By rmcphers Date 2020-12-17 Time 14:24 Sent To  
Notes
2020-12-17 14:31:07VACUUM SYSTEM
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE MORE DETAILS - MOUNTED ON ROOF? -
 PASSING THRU WALL AND MOUNTED ON THE CEILING JOIST? -
 ARE THE WALLS FIRE RATED? - HOW IS IT MOUNTED? - HEIGHT
 FROM FLOOR?

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-01-14 Cont ID  
Sent By equinone Date 2021-01-14 Time 16:39 Rev Time 0.00
Received By equinone Date 2021-01-14 Time 16:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-16 Cont ID  
Sent By equinone Date 2020-12-16 Time 09:57 Rev Time 0.00
Received By equinone Date 2020-12-16 Time 09:49 Sent To  
Notes
2020-12-16 10:05:14CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
  
 ELECTRICAL REVIEW STATUS: FAILED, SEE COMMENTS BELOW.
  
 1) PLEASE SPECIFY SIZE OF OVERCURRENT PROTECTION AND
 CONDUCTOR SIZE FOR THE 20 HP DUST COLLECTOR AND SHAKER
 MOTOR.
 2) THE DIGITAL SIGNATURE CERTIFICATE FOR MR. BEN ELLIS
 IS ABOUT TO EXPIRE IN 12/20/2020.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2021-04-01 Cont ID  
Sent By pleduc Date 2021-04-01 Time   Rev Time 0.00
Received By pleduc Date 2021-04-01 Time 12:34 Sent To  
Notes
2021-04-01 12:55:13PREVIOUS FIRE COMMENTS WERE NOT SPECIFICALLY ADDRESSED
 AND HAVE BEEN RESUBMITTED BELOW.
  
 IT APPEARS THAT THIS OCCUPANCY IS REQUIRED TO HAVE FIRE
 SPRINKLERS PER THE FLORIDA FIRE PREVENTION CODE.
  
 PLEASE ADDRESS THE FOLLOWING PREVIOUS COMMENTS:
  
 1) FOR CLARIFICATION PURPOSES, IS THIS A NEW
 INSTALLATION OR REPLACING AN EXISTING ONE?
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK.
  
  
 1A) A PREVIOUS FIRE INSPECTION RECORD OF THIS ADDRESS
 WAS CONDUCTED IN 2012 WITH NO ACTIVE BTR OF FILE FOR
 THE CITY.
 THE CURRENT BTR ON RECORD INDICAES A MINIWAREHOUSE AND
 SELF STORAGE.
  
 THIS PERMIT APPEARS TO SUPPORT A WOODWORKING BUSINESS
 WHICH WOULD BE A CHANGE OF OCCUPANCY.
  
 PLEASE REVIEW AND PROVIDE DETAILS AND A CHANGE OF
 OCCUPANCY PERMIT.
  
  
 1B) PER THE CHANGE OF OCCUPANCY AND NFPA 1
  
 13.3.2.28 WOODWORKING OPERATIONS. AN APPROVED AUTOMATIC
 FIRE SPRINKLER SYSTEM SHALL BE INSTALLED IN BUILDINGS
 CONTAINING
 WOODWORKING OPERATIONS EXCEEDING 2500 FT2 (232 M2) THAT
 USE
 EQUIPMENT, MACHINERY, OR APPLIANCES; THAT GENERATE
 FINELY DIVIDED
 COMBUSTIBLE WASTE; OR THAT USE FINELY DIVIDED
 COMBUSTIBLE
 MATERIALS
  
 PLEASE PROVIDE DETAILS AND COMPLY WITH CODE IF
 APPLICABLE SQUARE FOOTAGE.
  
  
  
 2) SHEET M 2 - THERE IS AN INDICATION OF A DUCT RUNNING
 THROUGH A UNIT SEPARATION WALL.
  
 IS THIS WALL A REQUIRED FIRE WALL WHERE A FIRE DAMPER
 IS REQUIRED?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) PERMITS FOR THIS ADDRESS INDICATE A 2ND FLOOR. THE
 SUBMITTED PLANS DO NOT INDICATE A 2ND FLOOR.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 4) THERE ARE NO INDICATIONS THAT THE ELECTIAL
 SYSTEM/EQUIPMENT COMPLY WITH NFPA 664 OR NFPA 70
  
  
 7.3 ELECTRICAL SYSTEMS.
 7.3.1 ALL ELECTRICAL SYSTEMS AND SYSTEM COMPONENTS
 SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 70, NATIONAL
 ELECTRICAL CODE.
 7.3.2* PORTIONS OF THE FACILITY WHERE DUST
 ACCUMULATIONS OCCUR
 OR WHERE SUSPENSIONS OF WOOD DUST IN AIR COULD OCCUR
 SHALL BE
 EQUIPPED WITH ELECTRICAL SYSTEMS AND EQUIPMENT PER
 ARTICLE
 502 OR 503 OF NFPA 70, NATIONAL ELECTRICAL CODE.
  
 7.6* LIGHTING. LIGHTING SYSTEM FIXTURES SHALL BE
 DESIGNED, INSTALLED,
 AND MAINTAINED SUCH THAT THEY DO NOT POSE A POTENTIAL
 IGNITION HAZARD DUE TO THE HEAT EVOLVED FROM NORMAL
 OPERATION
 OR AS A RESULT OF CATASTROPHIC FAILURE OR DAMAGE.
  
 PLEASE REVIEW, PROVIDE DETAILS OF COMPLIANCE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-01-13 Cont ID  
Sent By pleduc Date 2021-01-13 Time   Rev Time 0.00
Received By pleduc Date 2021-01-13 Time 09:35 Sent To  
Notes
2021-01-13 10:16:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) FOR CLARIFICATION PURPOSES, IS THIS A NEW
 INSTALLATION OR REPLACING AN EXISTING ONE?
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK.
  
  
 1A) A PREVIOUS FIRE INSPECTION RECORD OF THIS ADDRESS
 WAS CONDUCTED IN 2012 WITH NO ACTIVE BTR OF FILE FOR
 THE CITY.
 THE CURRENT BTR ON RECORD INDICAES A MINIWAREHOUSE AND
 SELF STORAGE.
  
 THIS PERMIT APPEARS TO SUPPORT A WOODWORKING BUSINESS
 WHICH WOULD BE A CHANGE OF OCCUPANCY.
  
 PLEASE REVIEW AND PROVIDE DETAILS AND A CHANGE OF
 OCCUPANCY PERMIT.
  
  
 1B) PER THE CHANGE OF OCCUPANCY AND NFPA 1
  
 13.3.2.28 WOODWORKING OPERATIONS. AN APPROVED AUTOMATIC
 FIRE SPRINKLER SYSTEM SHALL BE INSTALLED IN BUILDINGS
 CONTAINING
 WOODWORKING OPERATIONS EXCEEDING 2500 FT2 (232 M2) THAT
 USE
 EQUIPMENT, MACHINERY, OR APPLIANCES; THAT GENERATE
 FINELY DIVIDED
 COMBUSTIBLE WASTE; OR THAT USE FINELY DIVIDED
 COMBUSTIBLE
 MATERIALS
  
 PLEASE PROVIDE DETAILS AND COMPLY WITH CODE IF
 APPLICABLE SQUARE FOOTAGE.
  
  
  
 2) SHEET M 2 - THERE IS AN INDICATION OF A DUCT RUNNING
 THROUGH A UNIT SEPARATION WALL.
  
 IS THIS WALL A REQUIRED FIRE WALL WHERE A FIRE DAMPER
 IS REQUIRED?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) PERMITS FOR THIS ADDRESS INDICATE A 2ND FLOOR. THE
 SUBMITTED PLANS DO NOT INDICATE A 2ND FLOOR.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 4) THERE ARE NO INDICATIONS THAT THE ELECTIAL
 SYSTEM/EQUIPMENT COMPLY WITH NFPA 664 OR NFPA 70
  
  
 7.3 ELECTRICAL SYSTEMS.
 7.3.1 ALL ELECTRICAL SYSTEMS AND SYSTEM COMPONENTS
 SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 70, NATIONAL
 ELECTRICAL CODE.
 7.3.2* PORTIONS OF THE FACILITY WHERE DUST
 ACCUMULATIONS OCCUR
 OR WHERE SUSPENSIONS OF WOOD DUST IN AIR COULD OCCUR
 SHALL BE
 EQUIPPED WITH ELECTRICAL SYSTEMS AND EQUIPMENT PER
 ARTICLE
 502 OR 503 OF NFPA 70, NATIONAL ELECTRICAL CODE.
  
 7.6* LIGHTING. LIGHTING SYSTEM FIXTURES SHALL BE
 DESIGNED, INSTALLED,
 AND MAINTAINED SUCH THAT THEY DO NOT POSE A POTENTIAL
 IGNITION HAZARD DUE TO THE HEAT EVOLVED FROM NORMAL
 OPERATION
 OR AS A RESULT OF CATASTROPHIC FAILURE OR DAMAGE.
  
 PLEASE REVIEW, PROVIDE DETAILS OF COMPLIANCE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 10:45 Rev Time 0.00
Received By medwards Date 2021-03-31 Time 13:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-14 Cont ID  
Sent By equinone Date 2021-01-14 Time 16:40 Rev Time 0.00
Received By equinone Date 2021-01-07 Time 11:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-17 Cont ID  
Sent By rmcphers Date 2020-12-17 Time 14:32 Rev Time 0.00
Received By rmcphers Date 2020-12-07 Time 13:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 10:43 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 10:29 Sent To  
Notes
2021-04-08 10:44:19PLEASE SEE BUILDING REVIEWERS COMMENTS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-01-11 Cont ID  
Sent By hmoser Date 2021-01-11 Time 14:07 Rev Time 0.00
Received By hmoser Date 2021-01-11 Time 10:16 Sent To  
Notes
2021-01-11 14:07:09PLAN DENIED
 1) FIRE SPRINKLER REQUIRED FOR DUST COLLECTOR 2000 NFPA
 664 CHAPTER 9.
 2) PLEASE PROVIDE WALL TYPE IN BUILDING CHAPTER 6
 SECTION 6.2.2
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-16 Cont ID  
Sent By hmoser Date 2020-12-16 Time 13:44 Rev Time 0.00
Received By hmoser Date 2020-12-16 Time 13:26 Sent To  
Notes
2020-12-16 14:32:27PLAN DENIED
 NO ADDRESS OR PERMIT NUMBER ON PERMIT APPLICATION.
 ADDRESS ON PLAN REVIEW BOARD AND PLAN DO NOT MATCH.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-14 Cont ID  
Sent By rmcphers Date 2021-01-14 Time 14:07 Rev Time 0.00
Received By rmcphers Date 2021-01-14 Time 14:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-17 Cont ID  
Sent By rmcphers Date 2020-12-17 Time 14:32 Rev Time 0.00
Received By rmcphers Date 2020-12-17 Time 14:32 Sent To  
Notes
2020-12-16 10:07:19SIGNATURE CERTIFICATE WILL EXPIRE ON DECEMBER 20TH,
 2020