Plan Review Details - Permit 20120240
Plan Review Stops For Permit 20120240
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-15 Cont ID  
Sent By jleahy Date 2020-12-15 Time 15:38 Rev Time 0.00
Received By jleahy Date 2020-12-15 Time 15:38 Sent To  
Notes
2020-12-15 15:47:34 
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PROVIDE RISER DIAGRAM SHOWING SIZE OF MAIN AND SIZE
 OF CONDUCTORS 215.5 NEC
  
 PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR PANEL.
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC 107.2.1
  
 2) PROVIDE PANEL SCHEDULE SHOWING SIZE OF CIRCUIT AND
 BREAKER SIZE.
  
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
  
 3) PROVIDE LOAD CALCULATION PER ARTICLE 220 NEC
  
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-05 Cont ID  
Sent By jleahy Date 2021-02-05 Time 09:10 Rev Time 0.00
Received By lmarchan Date 2020-12-04 Time 12:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-15 Cont ID  
Sent By jleahy Date 2020-12-15 Time 15:47 Rev Time 0.00
Received By jleahy Date 2020-12-15 Time 15:47 Sent To  
Notes
2020-12-15 15:49:07PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  
 IN THIS CASE OWNER BUILDER PRINT NAME , SIGN NAME, DATE
 PLAN

Review Stop Z ZONING
Rev No 1 Status F Date 2021-02-05 Cont ID  
Sent By llouie Date 2021-02-05 Time   Rev Time 0.00
Received By llouie Date 2021-02-05 Time   Sent To  
Notes
2021-02-05 09:04:34** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PLEASE PROVIDE AN UPDATED SIGNED AND SEALED SURVEY
 OF THE PROPERTY. IT IS NOT CLEAR WHICH BUILDING ON THE
 PROPERTY THE IMPROVEMENT IS INTENDED FOR.
  
 2.) A KITCHEN FACILITY HAS BEEN DETECTED IN THE PLANS.
 PLEASE NOTE THAT PURSUANT TO SECTION 94-71 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS), AN
 ACCESSORY DWELLING UNIT (WITHIN THE PRINCIPAL STRUCTURE
 OR SEPARATE ACCESSORY STRUCTURE) IS NOT PERMITTED ON
 THE PROPERTY.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF14
  
 * PAPA LOT DIMENSION MEASUREMENTS: APPROX. 50 FT. WIDE
 X 110 FT.
  
2021-01-14 11:57:38NOR USRE IF THEIS IS A LEGAL UNIT GOING TO PUT AN
 ADDITIONAL SERVICE ON THIS BUILDING JLEAHY
  
 PLEASE EMAIL ME WHEN DONE SO I CAN SEND OUT COMMENTS
 [email protected] THANKS JAKE