Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2021-06-25 Cont ID  
Sent By jgomez Date 2021-06-25 Time 18:02 Rev Time 0.00
Received By jgomez Date 2021-06-25 Time 17:40 Sent To  
Notes
2021-06-25 18:07:28VEHICLE BARRIER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2021-06-11 Cont ID  
Sent By jgomez Date 2021-06-11 Time 13:05 Rev Time 0.00
Received By jgomez Date 2021-06-11 Time 11:04 Sent To  
Notes
2021-06-11 13:06:26GUARDRAIL SUBMITTAL, 7H BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 PROPOSED VEHICLE BARRIER:
 1-TYPICALLY, VEHICLE BARRIERS ARE DESIGNED TO COMPLY
 WITH THE GUARDRAIL REQUIREMENTS ALSO. PROPOSED VEHICLE
 BARRIER DOESN'T COMPLY WITH THE GUARDRAIL REQUIREMENTS.
 THERE IS A NOTE FROM THE ENGINEER OF RECORD ON SHEET
 BC01 STATING "CHAINLINK FENCE ATTACHED TO BARRIER
 CABLES BY OTHERS". NEED TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING CHAINLINK FENCE INSTALLATION.
 SPECIFY FASTENING METHOD AND OPENINGS SIZE TO SHOW
 COMPLIANCE WITH GUARDRAIL REQUIREMENTS OF SEC. 1015
 FBC-BUILDING AND SEC. 1607.8.1 FBC-BUILDING.
  
  
 NOTE: SENT TO ZONING REVIEW FOR PROPOSED RAILING
 SYSTEM-APPROVAL WITH CHAIN LINK FENCE.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2021-05-28 Cont ID  
Sent By jgomez Date 2021-05-28 Time 16:51 Rev Time 0.00
Received By jgomez Date 2021-05-28 Time 16:21 Sent To  
Notes
2021-05-28 16:51:47GUARDRAIL SUBMITTAL, 6TH BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- REVIEW CAN NOT BE PERFORMED. UNABLE TO READ
 INFORMATION ON DRAWINGS AND CALCULATIONS. UPLOADED
 DRAWINGS AND CALCULATIONS ARE NOT LEGIBLE. PLEASE
 UPLOAD LEGIBLE DRAWINGS AND CALCULATIONS.
 SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE:
 WALKER CONSULTANTS REVIEW STAMP INDICATE THAT THERE ARE
 SOME CORRECTIONS NOTED AND SUBMITTAL IS NOT REQUIRED.
 I WAS NOT ABLE TO SEE WHAT ARE THE REQUIRED CORRECTIONS
 EITHER. NEED TO SHOW THE REQUIRED CORRECTIONS.
  
 2-- PLEASE MAKE SURE RESUBMITTED DRAWINGS AND
 CALCULATIONS ARE REVIEWED/APPROVED IN WRITING BY THE
 ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS OFFICE.
 SEC. 107.3.4 CITY AMENDMENTS.
  
 3- DRAWINGS AND CALCULATIONS SUBMITTED:
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.
 EITHER UPLOAD TO PROJECTDOX DRAWINGS AND CALCULATIONS
 WITH DIGITAL SIGNATURE OR DROP OFF ORIGINAL SIGNED AND
 SEALED PAPER ORIGINALS WITH A WET SIGNATURE TO CITY
 HALL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2021-01-25 Cont ID  
Sent By jgomez Date 2021-01-25 Time 16:04 Rev Time 0.00
Received By jgomez Date 2021-01-25 Time 16:04 Sent To  
Notes
2021-01-25 16:05:09GOOD AFTERNOON MATTHEW,
  
 FIRST OF ALL I WANT TO APOLOGIZE FOR NOT GETTING BACK
 TO YOU EARLIER. I WAS DISCUSSING THIS ISSUE WITH ROBERT
 BROWN AND I WAS DOING SOME RESEARCH TO VERIFY WHICH
 BUILDING CODE WAS THIS BUILDING BUILT UNDER. THE REASON
 FOR THIS IS THAT THERE ARE SOME DIFFERENCES BETWEEN THE
 1979 AND THE 1982 STANDARD BUILDING CODES AND I WANTED
 TO BE SURE WHICH BUILDING CODE TO APPLY IN THIS
 DISCUSSION. BOTH BUILDING CODE EDITIONS ADDRESS THE
 ISSUE WITH THE IMPACT GUARDRAILS BUT THE MAIN
 DIFFERENCE IS THE DESIGN STANDARDS. THE 1979 CODE
 REQUIRES IMPACT GUARDRAILS CAPABLE OF WITHSTANDING AN
 IMPACT OF NOT LESS THAN ONE HUNDRED AND FIFTY (150)
 POUNDS PER LINEAL FOOT, WHILE THE 1982 CODE REQUIRES
 IMPACT GUARDRAILS CAPABLE OF WITHSTANDING AN IMPACT OF
 NOT LESS THAN TWO THOUSAND FIVE HUNDRED (2,500)
 FOOT-POUNDS.
  
 BASED ON MY RESEARCH 777 S. FLAGLER DR. BUILDING WAS
 BUILT UNDER THE 1982 EDITION. SEE ATTACHED ?CERTIFICATE
 OF CODE CONFORMANCE BY ARCHITECT OR ENGINEER
 AFFIDAVIT?.
 THEREFORE, THE IMPACT GUARDRAILS NEED TO COMPLY WITH
 THE 2,500 FOOT-POUND IMPACT.
  
 ROBERT BROWN AND I RESPECTFULLY DISAGREE WITH YOUR
 INTERPRETATION. SECTION 412.7(D) OF THE 1982 SBC
 REQUIRES TWO THINGS. PEDESTRIAN GUARDRAILS AND IMPACT
 GUARDRAILS. FIRST SENTENCE CALLS FOR PEDESTRIAN
 GUARDRAILS WHEN THE DROP EXCEEDS 3 FEET . AND, THE
 SECOND SENTENCE CALLS FOR IMPACT GUARDRAILS AT THE
 PARKING AREAS. NOTE THAT THE IMPACT GUARDRAILS ARE ONLY
 REQUIRED AT THE PARKING AREAS NO AT THE PEDESTRIAN OR
 VEHICULAR ACCESS.
 TO BETTER ILLUSTRATE THIS POINT, PLEASE TAKE A LOOK AT
 THE PHOTO YOU SENT ME EARLIER SHOWING A CAR PARKED
 BEHIND THE GUARDRAIL. THIS PHOTO CLEARLY SHOWS THE
 GUARDRAIL THAT NEEDS TO BE DESIGNED AS AN IMPACT
 GUARDRAIL AT THE PARKING AREA. THEREFORE, ALL THE
 GUARDRAILS THAT ARE IN FRONT OF THE PARKED CARS NEED TO
 BE DESIGNED AS IMPACT GUARDRAILS.
  
 THANK YOU
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
 *****NOTE:
 ALL THE COMMENTS FROM FIRST REVIEW STILL APPLY.
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- GUARDRAIL DRAWINGS WERE UPLOADED TO PROJECTDOX AS A
 SINGLE PDF. ALL DRAWINGS NEED TO BE UPLOADED
 INDIVIDUALLY IN THE DRAWINGS FOLDER AS REQUIRED BY THE
 CITY GUIDE FOR DIGITAL PLAN REVIEW. ALSO, DRAWINGS NEED
 TO FOLLOW THE FILE NAMING GUIDELINES. SEE THE CITY
 QUICK START GUIDE: DIGITAL PLAN REVIEW.
 SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS ABOUT
 THIS.
  
 2- SHEET F-1:
 A)REVISE THE APPLICABLE CODES. "THE ALUMINUM DESIGN
 MANUAL 2015" CAN NOT BE USED FOR THIS PROJECT. THE
 ALUMINUM DESIGN MANUAL IS NOT FOR GUARDRAILS. ALSO,
 THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING GARAGE
 NOT IN A RESIDENTIAL BUILDING. THIS IS A VEHICLE
 BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE WITH
 SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3
 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE UNDER WHICH THE MASTER PERMIT WAS
 ISSUED IS THE FLORIDA BUILDING CODE SIXTH EDITION
 (2017) NOT FBC 2020. CHAPTER 553 F.S. REVISE AS
 REQUIRED.
  
 3- SHEET F-2:
 A) REVISE THE DESIGN LOADS AND ALUMINUM NOTES. SEE ITEM
 #2 ABOVE. NEED TO COMPLY WITH SEC. 4.5.3 OF ASCE 7-10
 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH EDITION (2017).
  
 4-REVISE SHEETS F-3 THRU F-7 TO COMPLY WITH SEC. 4.5.3
 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH
 EDITION (2017).
  
 5- ENGINEER TO REVISE CALCULATIONS SUBMITTED:
 A) THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING
 GARAGE NOT IN A RESIDENTIAL BUILDING (R-2). THIS IS A
 VEHICLE BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE
 WITH SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC.
 1607.8.3 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE IS THE FLORIDA BUILDING CODE SIXTH
 EDITION (2017) NOT FBC 2020.
 CHAPTER 553 F.S.
  
 6- REVISED DRAWINGS AND CALCULATIONS TO BE
 REVIEWED/APPROVED IN WRITING BY THE ENGINEER OF RECORD
 PRIOR TO SUBMITTAL T THIS OFFICE. SEC. 107.3.4 CITY
 AMENDMENTS.
  
 7- DRAWINGS AND CALCULATIONS SUBMITTED:
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL. THE PLANS UPLOADED HAVE AN IMAGE OF A
 SIGNATURE AND SEAL BUT ARE NOT DIGITALLY SIGNED.
  
 ALSO, THE CALCULATIONS SUBMITTED DON'T HAVE THE
 ENGINEER'S SEA/SIGNATURE AND COMPLETE INFORMATION.
  
 EITHER UPLOAD TO PROJECTDOX DRAWINGS AND CALCULATIONS
 WITH DIGITAL SIGNATURE OR DROP OFF ORIGINAL SIGNED AND
 SEALED PAPER ORIGINALS WITH A WET SIGNATURE TO CITY
 HALL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-01-19 Cont ID  
Sent By jgomez Date 2021-01-15 Time 17:00 Rev Time 0.00
Received By jgomez Date 2021-01-15 Time 16:44 Sent To  
Notes
2021-01-15 18:02:4301/15/21 DISCUSSED WITH ROBERT BROWN (BUILDING
 OFFICIAL) THE LETTER EMAILED TO ME ON 01/13/2021 BY
 MATTHEW L. CONLEY P.E. THE STRUCTURAL ENGINEER OF
 RECORD FROM WALKER CONSULTANTS FOR THIS PROJECT.
  
 THE BUILDING WAS BUILT IN 1985. IS OK TO DO THE
 GUARDRAIL REPAIRS BASED ON THE CODE IN EFFECT AT THAT
 TIME INSTEAD OF TODAY'S REQUIREMENTS FOR NEW
 CONSTRUCTION.
 THE CODE IN EFFECT WAS THE SBC 1982 EDITION.
  
 BACK THEN THE CODE USED THE TERM GUARDRAIL FOR
 GUARDRAILS IN PARKING STRUCTURES NO "VEHICLE BARRIER".
 BASED ON SEC. 1204.2(C) OF SBC 1982 THE "GUARDRAILS OR
 INTERIOR AND EXTERIOR WALLS ACTING AS GUARDRAILS, IN
 PARKING STRUCTURES SHALL BE DESIGNED TO ABSORB AN
 ENERGY OF TWO THOUSAND FIVE HUNDRED (2,500) FOOT-POUNDS
 APPLIED AT EIGHTEEN (18) INCHES ABOVE THE FLOOR AT ANY
 POINT HORIZONTALLY ALONG THE SPAN OF THE GUARDRAIL. ALL
 ELEMENTS OF THE GUARDRAIL SYSTEM, INCLUDING SUPPORTS
 AND CONNECTIONS, SHALL BE DESIGNED TO ABSORB THIS
 ENERGY BY THE FORMULA PA/24 = 2500FT-LBS.
 WHERE :
 P=THE EQUIVALENT STATIC LOAD IN POUNDS AT THE POINT OF
 IMPACT.
 A= DEFLECTION OR MOVEMENT OF THE GUARDRAIL AT THE POINT
 OF IMPACT IN INCHES.
  
 NOTE: CURRENT CODE SEC. 1607.8.3 FBC REQUIRES A DESIGN
 TO RESIST A CONCENTRATED LOAD OF 6,000 POUNDS.
  
  
 GUARDRAIL SUBMITTAL, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- GUARDRAIL DRAWINGS WERE UPLOADED TO PROJECTDOX AS A
 SINGLE PDF. ALL DRAWINGS NEED TO BE UPLOADED
 INDIVIDUALLY IN THE DRAWINGS FOLDER AS REQUIRED BY THE
 CITY GUIDE FOR DIGITAL PLAN REVIEW. ALSO, DRAWINGS NEED
 TO FOLLOW THE FILE NAMING GUIDELINES. SEE THE CITY
 QUICK START GUIDE: DIGITAL PLAN REVIEW.
 SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS ABOUT
 THIS.
  
 2- SHEET F-1:
 A)REVISE THE APPLICABLE CODES. "THE ALUMINUM DESIGN
 MANUAL 2015" CAN NOT BE USED FOR THIS PROJECT. THE
 ALUMINUM DESIGN MANUAL IS NOT FOR GUARDRAILS. ALSO,
 THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING GARAGE
 NOT IN A RESIDENTIAL BUILDING. THIS IS A VEHICLE
 BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE WITH
 SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3
 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE UNDER WHICH MASTER PERMIT WAS APPROVED
 IS THE FLORIDA BUILDING CODE SIXTH EDITION (2017) NOT
 FBC 2020.
 CHAPTER 553 F.S. REVISE AS REQUIRED.
  
 3- SHEET F-2:
 A) REVISE THE DESIGN LOADS AND ALUMINUM NOTES. SEE ITEM
 #2 ABOVE. NEED TO COMPLY WITH SEC. 4.5.3 OF ASCE 7-10
 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH EDITION (2017).
  
 4-REVISE SHEETS F-3 THRU F-7 TO COMPLY WITH SEC. 4.5.3
 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH
 EDITION (2017).
  
 5- ENGINEER TO REVISE CALCULATIONS SUBMITTED:
 A) THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING
 GARAGE NOT IN A RESIDENTIAL BUILDING (R-2). THIS IS A
 VEHICLE BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE
 WITH SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC.
 1607.8.3 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE IS THE FLORIDA BUILDING CODE SIXTH
 EDITION (2017) NOT FBC 2020.
 CHAPTER 553 F.S.
  
 6- REVISED DRAWINGS AND CALCULATIONS TO BE
 REVIEWED/APPROVED IN WRITING BY THE ENGINEER OF RECORD
 PRIOR TO SUBMITTAL T THIS OFFICE. SEC. 107.3.4 CITY
 AMENDMENTS.
  
 7- DRAWINGS AND CALCULATIONS SUBMITTED:
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL. THE PLANS UPLOADED HAVE AN IMAGE OF A
 SIGNATURE AND SEAL BUT ARE NOT DIGITALLY SIGNED.
  
 ALSO, THE CALCULATIONS SUBMITTED DON'T HAVE THE
 ENGINEER'S SEA/SIGNATURE AND COMPLETE INFORMATION.
  
 EITHER UPLOAD TO PROJECTDOX DRAWINGS AND CALCULATIONS
 WITH DIGITAL SIGNATURE OR DROP OFF ORIGINAL SIGNED AND
 SEALED PAPER ORIGINALS WITH A WET SIGNATURE TO CITY
 HALL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-01-11 Cont ID  
Sent By jgomez Date 2021-01-11 Time 16:38 Rev Time 0.00
Received By jgomez Date 2021-01-11 Time 16:36 Sent To  
Notes
2021-01-11 16:37:54GUARDRAIL SUBMITTAL, THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 *****NOTE:
 ALL THE COMMENTS FROM FIRST REVIEW STILL APPLY.
 REQUESTED INFORMATION WAS NOT PROVIDED.
  
 ONLY THE ENGINEER GUARDRAIL CALCULATIONS WERE
 RESUBMITTED. THEY DON'T SEEM TO BE REVISED. SAME
 CALCULATIONS WERE RESUBMITTED. THE ONLY INFORMATION
 THAT WAS CHANGED WAS THE "CHECKED BY AND THE DATES.
 ALSO, IT IS NOT CLEAR WHY THE
 DATES WERE CHANGED AND NOW THEY SHOW AN EARLIER DATE
 THAN THE ONE PREVIOUSLY SUBMITTED.
 ENGINEER PROVIDING THE CALCULATIONS TO CLARIFY.
  
  
  
  
 ENGINEERS/ARCHITECTS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- GUARDRAIL DRAWINGS WERE UPLOADED TO PROJECTDOX AS A
 SINGLE PDF. ALL DRAWINGS NEED TO BE UPLOADED
 INDIVIDUALLY IN THE DRAWINGS FOLDER AS REQUIRED BY THE
 CITY GUIDE FOR DIGITAL PLAN REVIEW. ALSO, DRAWINGS NEED
 TO FOLLOW THE FILE NAMING GUIDELINES. SEE THE CITY
 QUICK START GUIDE: DIGITAL PLAN REVIEW.
 SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS ABOUT
 THIS.
  
 2- SHEET F-1:
 A)REVISE THE APPLICABLE CODES. "THE ALUMINUM DESIGN
 MANUAL 2015" CAN NOT BE USED FOR THIS PROJECT. THE
 ALUMINUM DESIGN MANUAL IS NOT FOR GUARDRAILS. ALSO,
 THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING GARAGE
 NOT IN A RESIDENTIAL BUILDING. THIS IS A VEHICLE
 BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE WITH
 SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3
 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE UNDER WHICH THE MASTER PERMIT WAS
 ISSUED IS THE FLORIDA BUILDING CODE SIXTH EDITION
 (2017) NOT FBC 2020. CHAPTER 553 F.S. REVISE AS
 REQUIRED.
  
 3- SHEET F-2:
 A) REVISE THE DESIGN LOADS AND ALUMINUM NOTES. SEE ITEM
 #2 ABOVE. NEED TO COMPLY WITH SEC. 4.5.3 OF ASCE 7-10
 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH EDITION (2017).
  
 4-REVISE SHEETS F-3 THRU F-7 TO COMPLY WITH SEC. 4.5.3
 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH
 EDITION (2017).
  
 5- ENGINEER TO REVISE CALCULATIONS SUBMITTED:
 A) THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING
 GARAGE NOT IN A RESIDENTIAL BUILDING (R-2). THIS IS A
 VEHICLE BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE
 WITH SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC.
 1607.8.3 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE IS THE FLORIDA BUILDING CODE SIXTH
 EDITION (2017) NOT FBC 2020.
 CHAPTER 553 F.S.
  
 6- REVISED DRAWINGS AND CALCULATIONS TO BE
 REVIEWED/APPROVED IN WRITING BY THE ENGINEER OF RECORD
 PRIOR TO SUBMITTAL T THIS OFFICE. SEC. 107.3.4 CITY
 AMENDMENTS.
  
 7- DRAWINGS AND CALCULATIONS SUBMITTED:
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL. THE PLANS UPLOADED HAVE AN IMAGE OF A
 SIGNATURE AND SEAL BUT ARE NOT DIGITALLY SIGNED.
  
 ALSO, THE CALCULATIONS SUBMITTED DON'T HAVE THE
 ENGINEER'S SEA/SIGNATURE AND COMPLETE INFORMATION.
  
 EITHER UPLOAD TO PROJECTDOX DRAWINGS AND CALCULATIONS
 WITH DIGITAL SIGNATURE OR DROP OFF ORIGINAL SIGNED AND
 SEALED PAPER ORIGINALS WITH A WET SIGNATURE TO CITY
 HALL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-07 Cont ID  
Sent By jgomez Date 2021-01-07 Time 17:49 Rev Time 0.00
Received By jgomez Date 2021-01-07 Time 17:33 Sent To  
Notes
2021-01-07 17:59:36****NOTE:
 THERE IS NO NEW INFORMATION SUBMITTED FOR REVIEW. SAME
 COMMENTS FROM PREVIOUS REVIEW APPLY. SEE BELOW:
  
  
  
 GUARDRAIL SUBMITTAL, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- GUARDRAIL DRAWINGS WERE UPLOADED TO PROJECTDOX AS A
 SINGLE PDF. ALL DRAWINGS NEED TO BE UPLOADED
 INDIVIDUALLY IN THE DRAWINGS FOLDER AS REQUIRED BY THE
 CITY GUIDE FOR DIGITAL PLAN REVIEW. ALSO, DRAWINGS NEED
 TO FOLLOW THE FILE NAMING GUIDELINES. SEE THE CITY
 QUICK START GUIDE: DIGITAL PLAN REVIEW.
 SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS ABOUT
 THIS.
  
 2- SHEET F-1:
 A)REVISE THE APPLICABLE CODES. "THE ALUMINUM DESIGN
 MANUAL 2015" CAN NOT BE USED FOR THIS PROJECT. THE
 ALUMINUM DESIGN MANUAL IS NOT FOR GUARDRAILS. ALSO,
 THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING GARAGE
 NOT IN A RESIDENTIAL BUILDING. THIS IS A VEHICLE
 BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE WITH
 SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3
 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE UNDER WHICH MASTER PERMIT WAS APPROVED
 IS THE FLORIDA BUILDING CODE SIXTH EDITION (2017) NOT
 FBC 2020.
 CHAPTER 553 F.S. REVISE AS REQUIRED.
  
 3- SHEET F-2:
 A) REVISE THE DESIGN LOADS AND ALUMINUM NOTES. SEE ITEM
 #2 ABOVE. NEED TO COMPLY WITH SEC. 4.5.3 OF ASCE 7-10
 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH EDITION (2017).
  
 4-REVISE SHEETS F-3 THRU F-7 TO COMPLY WITH SEC. 4.5.3
 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH
 EDITION (2017).
  
 5- ENGINEER TO REVISE CALCULATIONS SUBMITTED:
 A) THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING
 GARAGE NOT IN A RESIDENTIAL BUILDING (R-2). THIS IS A
 VEHICLE BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE
 WITH SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC.
 1607.8.3 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE IS THE FLORIDA BUILDING CODE SIXTH
 EDITION (2017) NOT FBC 2020.
 CHAPTER 553 F.S.
  
 6- REVISED DRAWINGS AND CALCULATIONS TO BE
 REVIEWED/APPROVED IN WRITING BY THE ENGINEER OF RECORD
 PRIOR TO SUBMITTAL T THIS OFFICE. SEC. 107.3.4 CITY
 AMENDMENTS.
  
 7- DRAWINGS AND CALCULATIONS SUBMITTED:
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL. THE PLANS UPLOADED HAVE AN IMAGE OF A
 SIGNATURE AND SEAL BUT ARE NOT DIGITALLY SIGNED.
  
 ALSO, THE CALCULATIONS SUBMITTED DON'T HAVE THE
 ENGINEER'S SEA/SIGNATURE AND COMPLETE INFORMATION.
  
 EITHER UPLOAD TO PROJECTDOX DRAWINGS AND CALCULATIONS
 WITH DIGITAL SIGNATURE OR DROP OFF ORIGINAL SIGNED AND
 SEALED PAPER ORIGINALS WITH A WET SIGNATURE TO CITY
 HALL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-18 Cont ID  
Sent By jgomez Date 2020-12-18 Time 12:50 Rev Time 0.00
Received By jgomez Date 2020-12-18 Time 11:12 Sent To  
Notes
2020-12-18 13:49:55GUARDRAIL SUBMITTAL BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- GUARDRAIL DRAWINGS WERE UPLOADED TO PROJECTDOX AS A
 SINGLE PDF. ALL DRAWINGS NEED TO BE UPLOADED
 INDIVIDUALLY IN THE DRAWINGS FOLDER AS REQUIRED BY THE
 CITY GUIDE FOR DIGITAL PLAN REVIEW. ALSO, DRAWINGS NEED
 TO FOLLOW THE FILE NAMING GUIDELINES. SEE THE CITY
 QUICK START GUIDE: DIGITAL PLAN REVIEW.
 SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS ABOUT
 THIS.
  
 2- SHEET F-1:
 A)REVISE THE APPLICABLE CODES. "THE ALUMINUM DESIGN
 MANUAL 2015" CAN NOT BE USED FOR THIS PROJECT. THE
 ALUMINUM DESIGN MANUAL IS NOT FOR GUARDRAILS. ALSO,
 THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING GARAGE
 NOT IN A RESIDENTIAL BUILDING. THIS IS A VEHICLE
 BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE WITH
 SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3
 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE IS THE FLORIDA BUILDING CODE SIXTH
 EDITION (2017) NOT FBC 2020.
 CHAPTER 553 F.S.
  
 3- SHEET F-2:
 A) REVISE THE DESIGN LOADS AND ALUMINUM NOTES. SEE ITEM
 #2 ABOVE. NEED TO COMPLY WITH SEC. 4.5.3 OF ASCE 7-10
 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH EDITION (2017).
  
 4-REVISE SHEETS F-3 THRU F-7 TO COMPLY WITH SEC. 4.5.3
 OF ASCE 7-10 AS REQUIRED BY SEC. 1607.8.3 FBC 6TH
 EDITION (2017).
  
 5- ENGINEER TO REVISE CALCULATIONS SUBMITTED:
 A) THIS GUARDRAIL IS TO BE INSTALLED IN A PARKING
 GARAGE NOT IN A RESIDENTIAL BUILDING (R-2). THIS IS A
 VEHICLE BARRIER. ENGINEER NEEDS TO DESIGN IN ACCORDANCE
 WITH SEC. 4.5.3 OF ASCE 7-10 AS REQUIRED BY SEC.
 1607.8.3 FBC 6TH EDITION (2017).
  
 B) CURRENT CODE UNDER WHICH MASTER PERMIT WAS APPROVED
 IS THE FLORIDA BUILDING CODE SIXTH EDITION (2017) NOT
 FBC 2020.
 CHAPTER 553 F.S. REVISE AS REQUIRED.
  
 6- REVISED DRAWINGS AND CALCULATIONS TO BE
 REVIEWED/APPROVED IN WRITING BY THE ENGINEER OF RECORD
 PRIOR TO SUBMITTAL T THIS OFFICE. SEC. 107.3.4 CITY
 AMENDMENTS.
  
 7- DRAWINGS AND CALCULATIONS SUBMITTED:
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL. THE PLANS UPLOADED HAVE AN IMAGE OF A
 SIGNATURE AND SEAL BUT ARE NOT DIGITALLY SIGNED.
  
 ALSO, THE CALCULATIONS SUBMITTED DON'T HAVE THE
 ENGINEER'S SEA/SIGNATURE AND COMPLETE INFORMATION.
  
 EITHER UPLOAD TO PROJECTDOX DRAWINGS AND CALCULATIONS
 WITH DIGITAL SIGNATURE OR DROP OFF ORIGINAL SIGNED AND
 SEALED PAPER ORIGINALS WITH A WET SIGNATURE TO CITY
 HALL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2021-06-25 Cont ID  
Sent By jgomez Date 2021-06-25 Time 18:06 Rev Time 0.00
Received By jgomez Date 2021-06-24 Time 14:25 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2021-06-18 Time   Rev Time 0.00
Received By jgomez Date 2021-06-08 Time 17:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-05-28 Cont ID  
Sent By jgomez Date 2021-05-28 Time 16:51 Rev Time 0.00
Received By jgomez Date 2021-05-18 Time 06:41 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-01-15 Cont ID  
Sent By jgomez Date 2021-01-15 Time 18:02 Rev Time 0.00
Received By jgomez Date 2021-01-15 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-11 Cont ID  
Sent By jgomez Date 2021-01-11 Time 17:22 Rev Time 0.00
Received By jgomez Date 2021-01-08 Time 15:04 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-07 Cont ID  
Sent By jgomez Date 2021-01-07 Time 18:00 Rev Time 0.00
Received By jgomez Date 2021-01-04 Time 10:25 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-18 Cont ID  
Sent By jgomez Date 2020-12-18 Time 14:08 Rev Time 0.00
Received By jgomez Date 2020-12-04 Time 17:01 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-06-25 Cont ID  
Sent By jgomez Date 2021-06-25 Time 18:02 Rev Time 0.00
Received By jgomez Date 2021-06-25 Time 18:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-06-11 Cont ID  
Sent By jgomez Date 2021-06-11 Time 11:07 Rev Time 0.00
Received By jgomez Date 2021-06-11 Time 11:07 Sent To  
Notes
2021-06-11 11:09:43VEHICLE BARRIER DRAWINGS & CALCULATIONS WITH ENGINEER'S
 DIGITAL SIGNATURE FILED IN THE SIGNATURE FOLDER. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-05-28 Cont ID  
Sent By jgomez Date 2021-05-28 Time 16:33 Rev Time 0.00
Received By jgomez Date 2021-05-28 Time 16:21 Sent To  
Notes
2021-05-28 16:33:37SIGNATURE REVIEW COMMENTS:
  
 1- DRAWINGS AND CALCULATIONS SUBMITTED:
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.
 EITHER UPLOAD TO PROJECTDOX DRAWINGS AND CALCULATIONS
 WITH DIGITAL SIGNATURE OR DROP OFF ORIGINAL SIGNED AND
 SEALED PAPER ORIGINALS WITH A WET SIGNATURE TO CITY
 HALL.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-01-11 Cont ID  
Sent By jgomez Date 2021-01-11 Time 17:21 Rev Time 0.00
Received By jgomez Date 2021-01-11 Time 17:21 Sent To  
Notes
2021-01-11 17:21:49DRAWINGS AND CALCULATIONS SUBMITTED:
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL. THE PLANS UPLOADED HAVE AN IMAGE OF A
 SIGNATURE AND SEAL BUT ARE NOT DIGITALLY SIGNED.
  
 ALSO, THE CALCULATIONS SUBMITTED DON'T HAVE THE
 ENGINEER'S SEAL/SIGNATURE AND COMPLETE INFORMATION.
  
 EITHER UPLOAD TO PROJECTDOX DRAWINGS AND CALCULATIONS
 WITH DIGITAL SIGNATURE OR DROP OFF ORIGINAL SIGNED AND
 SEALED PAPER ORIGINALS WITH A WET SIGNATURE TO CITY
 HALL.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-01-07 Cont ID  
Sent By jgomez Date 2021-01-07 Time 17:59 Rev Time 0.00
Received By jgomez Date 2021-01-07 Time 17:59 Sent To  
Notes
2021-01-07 18:00:15DRAWINGS AND CALCULATIONS SUBMITTED:
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL. THE PLANS UPLOADED HAVE AN IMAGE OF A
 SIGNATURE AND SEAL BUT ARE NOT DIGITALLY SIGNED.
  
 ALSO, THE CALCULATIONS SUBMITTED DON'T HAVE THE
 ENGINEER'S SEA/SIGNATURE AND COMPLETE INFORMATION.
  
 EITHER UPLOAD TO PROJECTDOX DRAWINGS AND CALCULATIONS
 WITH DIGITAL SIGNATURE OR DROP OFF ORIGINAL SIGNED AND
 SEALED PAPER ORIGINALS WITH A WET SIGNATURE TO CITY
 HALL.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-18 Cont ID  
Sent By jgomez Date 2020-12-18 Time 14:08 Rev Time 0.00
Received By jgomez Date 2020-12-18 Time 14:08 Sent To  
Notes
2020-12-18 14:08:34DRAWINGS AND CALCULATIONS SUBMITTED:
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL. THE PLANS UPLOADED HAVE AN IMAGE OF A
 SIGNATURE AND SEAL BUT ARE NOT DIGITALLY SIGNED.
  
 ALSO, THE CALCULATIONS SUBMITTED DON'T HAVE THE
 ENGINEER'S SEA/SIGNATURE AND COMPLETE INFORMATION.
  
 EITHER UPLOAD TO PROJECTDOX DRAWINGS AND CALCULATIONS
 WITH DIGITAL SIGNATURE OR DROP OFF ORIGINAL SIGNED AND
 SEALED PAPER ORIGINALS WITH A WET SIGNATURE TO CITY
 HALL.

Review Stop Z ZONING
Rev No 1 Status P Date 2021-06-17 Cont ID  
Sent By aaponte Date 2021-06-17 Time 16:37 Rev Time 0.00
Received By aaponte Date 2021-06-17 Time 16:37 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved