Plan Review Stops For Permit 20120214
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-01-20 Cont ID  
Sent By ccole Date 2021-01-20 Time 10:06 Rev Time 0.00
Received By ccole Date 2021-01-19 Time 07:20 Sent To  
Notes
2021-01-19 10:07:22 
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-12-18 Cont ID  
Sent By ccole Date 2020-12-18 Time 11:55 Rev Time 0.00
Received By ccole Date 2020-12-18 Time 10:51 Sent To  
Notes
2020-12-18 11:55:412ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 20120214
 12/18/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 COMMENTS FROM THE 1ST REVIEW ARE MARKED AS PASSED OR
 FAILED. PLEASE SEE NOTES ADDED TO FAILED COMMENTS. THE
 REQUESTED RESPONSE NARRATIVE WAS NOT PROVIDED.
  
 1) FAILED. SHEET P101A: PLEASE PROVIDE A COMPLETE GAS
 RISER DRAWING SHOWING THE NEW AND EXISTING PIPING AND
 NEW AND EXISTING GAS LOADS REQUIRED BY SECTION
 107.3.5.3 WPB, AND SECTIONS 401.3 & 401.4 FBC FG.
 PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE RISER-
 FBC-17 FG. SHEET P304: THE NEW PLAN SHEET SHOWS PARTIAL
 RISERS FOR THE WATER HEATERS IN THE ADULT AND AND THE
 CHILD/ADOLESCENT. COMPLETE GAS RISER NOT PROVIDED.
  
 A) FAILED. DELIVERY PRESSURE AT THE METER- SECTIONS
 402.1, 402.6. NOT PROVIDED. GAS SYSTEM PRESSURE NOT
 SHOWN ON P303.
  
 B) FAILED. TYPES AND SIZES OF GAS PIPING- SECTIONS
 402.3 & 403.1. TYPES OF PIPING NOT SHOWN ON P304.
  
 C) FAILED. TOTAL DEVELOPED LENGTH OF THE PIPING FROM
 THE METER TO THE MOST REMOTE GAS OUTLET- SECTION
 402.4.1`. PARTIAL RISER LENGTHS SHOWN ON P304.
  
 D) PASSED. BRANCH AND CUT PIPING LENGTHS-SECTION
 402.4.2.
  
 E) FAILED. INDIVIDUAL GAS LOADS AT OUTLETS AND TOTAL
 LOAD OF THE SYSTEM- SECTION 402.2. INDIVIDUAL LOADS
 SHOWN, TOTAL LOAD NOT SHOWN ON P304.
  
 F) FAILED. LOCATIONS OF REGULATORS AND OUTLET
 PRESSURES- SECTIONS 410.1 & 410.2. THERE IS A NOTE ON
 THE PLAN SPECIFYING A PRV'S FOR THE GAS PIPING TO THE
 WATER HEATERS. IS THIS VALVE TO BE INSTALLED IN
 ADDITION TO GAS REGULATORS WHICH ARE TYPICALLY USED TO
 REDUCE PRESSURE? REGULATOR LOCATIONS, INPUT AND OUTPUT
 PRESSURES NOT SHOWN ON P304.
  
 G) FAILED. PIPE SIZING TABLES- SECTION 402.4. NOT
 PROVIDED.
  
 2) PASSED. P101A: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE WATER HEATER AND METHOD OF PROVIDING THE AIR-
 SECTION 304.1 & 624.1 FBC FG.
  
 3) PASSED. P101A: PROVIDE VENTING SPECIFICATIONS AND
 DIAGRAMS FOR THE GAS-FIRED WATER HEATERS- SECTIONS
 501.1 & 624.1 FBC FG. SHOW THE TYPE AND SIZE OF VENTS,
 VENT RUNS AND TERMINATION LOCATIONS.
  
 4) PASSED. PI0IA: PROVIDE VENTING DIAGRAMS FOR THE
 PRVS. SHOW THE TYPE AND SIZE OF VENTS, VENT RUNS AND
 TERMINATION LOCATIONS- SECTIONS 410.3 & 410.3.1 FBC FG.
  
 5) PASSED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 WATER HEATERS- SECTION 624.1 FBC FG.
  
 6) FAILED. PLEASE ADJUST THE $2000.00 VALUE FOR
 INSTALLATION OF THE WATER HEATERS TO INCLUDE THE COST
 OF THE WATER HEATERS AND ALL OTHER APPURTENANCES SUCH
 AS THE VENTING- SECTIONS 109.3 WPB. PERMIT VALUE IS
 BASED ON LABOR, MATERIALS, EQUIPMENT, APPLIANCES,
 DESIGN FEES AND SITE WORK. PLEASE PROVIDE A COPY OF A
 SIGNED CONTRACT AND/OR ESTIMATES AND INVOICES TO VERIFY
 TOTAL COSTS. NO DOCUMENTATION SUBMITTED OR RESPONSE
 MADE TO THE COMMENT.
  
 NEW COMMENT.
  
 1) THE NEW SUBMITTED PLANS SHEETS- M101A, P001, P002,
 P304 HAVE COPIED ENGINEER?S SEALS AND SIGNATURES. THEY
 ARE PAPER COPIES. PLEASE NOTE THAT ELECTRONICALLY
 TRANSMITTED PLAMNS SHALL BEAR THE DIGITAL SIGNATURES OF
 THE ENGINEER OF RECORD- FL. STATUTE 471.025, AND
 SECTION 61G15-23.005 FAC. PLEASE SEE SIGNATURE FOR
 ADDITIONAL INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-12-14 Cont ID  
Sent By ccole Date 2020-12-14 Time 10:07 Rev Time 0.00
Received By ccole Date 2020-12-14 Time 09:21 Sent To  
Notes
2020-12-14 10:08:041ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20120214
 12/14/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. PLEASE NOTE THAT THE FUEL
 GAS REVIEW AND COMPLIANCES FOR PERMITTING WERE REMOVED
 UNDER PERMIT 18120436. NO REVIEWS WERE PERFORMED.
  
 1) SHEET P101A: PLEASE PROVIDE A COMPLETE GAS RISER
 DRAWING SHOWING THE NEW AND EXISTING PIPING AND NEW AND
 EXISTING GAS LOADS REQUIRED BY SECTION 107.3.5.3 WPB,
 AND SECTIONS 401.3 & 401.4 FBC FG. PLEASE PROVIDE THE
 FOLLOWING INFORMATION ON THE RISER- FBC-17 FG.
 A) DELIVERY PRESSURE AT THE METER- SECTIONS 402.1,
 402.6.
 B) TYPES AND SIZES OF GAS PIPING- SECTIONS 402.3 &
 403.1
 C) TOTAL DEVELOPED LENGTH OF THE PIPING FROM THE METER
 TO THE MOST REMOTE GAS OUTLET- SECTION 402.4.1`.
 D) BRANCH AND CUT PIPING LENGTHS-SECTION 402.4.2.
 E) INDIVIDUAL GAS LOADS AT OUTLETS AND TOTAL LOAD OF
 THE SYSTEM- SECTION 402.2
 F) LOCATIONS OF REGULATORS AND OUTLET PRESSURES-
 SECTIONS 410.1 & 410.2. THERE IS A NOTE ON THE PLAN
 SPECIFYING A PRV'S FOR THE GAS PIPING TO THE WATER
 HEATERS. IS THIS VALVER TO BE INSTALLED IN ADDITON TO
 GAS REGULATORS WHICH ARE TYPICALLY USED TO REDUCE
 PRESSURE?
 G) PIPE SIZING TABLES- SECTION 402.4.
  
 2) P101A: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 WATER HEATER AND METHOD OF PROVIDING THE AIR- SECTION
 304.1 & 624.1 FBC FG.
  
 3) P101A: PROVIDE VENTING SPECIFICATRIONS AND DIAGRAMS
 FOR THE GAS-FIRED WATER HEATERS- SECTIONS 501.1 & 624.1
 FBC FG. SHOW THE TYPE AND SIZE OF VENTS, VENT RUNS AND
 TERMINATION LOCATIONS-
  
 4) PI0IA: PROVIDE VENTING DIAGRAMS FOR THE PRVS. SHOW
 THE TYPE AND SIZE OF VENTS, VENT RUNS AND TERMINATION
 LOCATIONS- SECTIONS 410.3 & 410.3.1 FBC FG.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATERS- SECTION 624.1 FBC FG.
  
 6) PLEASE ADJUST THE $2000.00 VALUE FOR INSTALLATION OF
 THE WATER HEATERS TO INCLUDE THE COST OF THE WATER
 HEATERS AND ALL OTHER APPURTENANCES SUCH AS THE
 VENTING- SECTIONS 109.3 WPB. PERMIT VALUE IS BASED ON
 LABOR, MATERIALS, EQUIPMENT, APPLIANCES, DESIGN FEES
 AND SITE WORK. PLEASE PROVIDE A COPY OF A SIGNED
 CONTRACT AND/OR ESTIMATES AND INVOICES TO VERIFY TOTAL
 COSTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-01-19 Time   Rev Time 0.00
Received By lmarchan Date 2021-01-14 Time 08:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-12-18 Time   Rev Time 0.00
Received By ccarvaja Date 2020-12-15 Time 13:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-12-14 Time   Rev Time 0.00
Received By ccarvaja Date 2020-12-04 Time 11:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-01-19 Cont ID  
Sent By ccole Date 2021-01-19 Time 10:07 Rev Time 0.00
Received By ccole Date 2021-01-19 Time 07:20 Sent To  
Notes
2021-01-19 10:21:39PLUMBING REVIEWED UNDER MASTER 18120436 AND REVISION
 20111206.

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-12-18 Cont ID  
Sent By ccole Date 2020-12-18 Time 11:58 Rev Time 0.00
Received By ccole Date 2020-12-18 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-12-14 Cont ID  
Sent By ccole Date 2020-12-14 Time 09:30 Rev Time 0.00
Received By ccole Date 2020-12-14 Time 09:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-01-20 Cont ID  
Sent By ccole Date 2021-01-20 Time 09:35 Rev Time 0.00
Received By ccole Date 2021-01-19 Time 07:20 Sent To  
Notes
2021-01-19 09:36:07 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-12-18 Cont ID  
Sent By ccole Date 2020-12-18 Time 11:59 Rev Time 0.00
Received By ccole Date 2020-12-18 Time 10:51 Sent To  
Notes
2020-12-18 11:59:382ND SIGNATURE REVIEW
 12/18/2020
  
 1) THE NEW SUBMITTED PLANS SHEETS- M101A, P001, P002,
 P304 HAVE COPIED ENGINEER?S SEALS AND SIGNATURES. THEY
 ARE PAPER COPIES. PLEASE NOTE THAT ELECTRONICALLY
 TRANSMITTED PLANS SHALL BEAR THE DIGITAL SIGNATURES OF
 THE ENGINEER OF RECORD- FL. STATUTE 471.025, AND
 SECTION 61G15-23.005 FAC. PLEASE SEE SIGNATURE FOR
 ADDITIONAL INFORMATION.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
  
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-14 Cont ID  
Sent By ccole Date 2020-12-14 Time 09:30 Rev Time 0.00
Received By ccole Date 2020-12-14 Time 09:21 Sent To  
Notes
***NONE***