Plan Review Details - Permit 20120141
Plan Review Stops For Permit 20120141
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-05-18 Cont ID  
Sent By cthroop Date 2021-05-18 Time 17:25 Rev Time 0.00
Received By cthroop Date 2021-05-18 Time 16:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-01 Cont ID  
Sent By cthroop Date 2021-03-01 Time 14:12 Rev Time 0.00
Received By cthroop Date 2021-03-01 Time 10:52 Sent To  
Notes
2021-03-01 14:26:36PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? PX3169 / 1&2 FAMILY - SFP306
 INSPECTOR ? BN4338
 BUILDING OFFICIAL ? BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE CANNOT BE DETERMINED AT THIS TIME. CONFLICTING
 SQ. FTG.OF ADDITION. APPLICATION STATES 421SF AND PLAN
 SHEET 2 OF 4 STATES 375SF. CONSTRUCTION TYPE VB.
 ICC BUILDING VALUATION DATA FOR TYPE VB IS $123.68/SF.
 CITY OF WPB CHPT. VALUE 109.3 BUILDING PERMIT
 VALUATIONS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  
 2. PROPOSED WINDOW W-2 IS NOT LISTED ON WINDOW
 SCHEDULE.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND EXT.
 DOORS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 4. DESIGNER TO STATE REQUIRED INSULATION AND R-VALUE
 FOR WALL AND CEILING INSULATION.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 5. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 6. PROVIDE A SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 7. REF. DETAIL 6/S2 FOR THE FOLLOWING:
 DESIGNER SHALL PROVIDE SPACING FOR HETAL 20 TRUSS
 ANCHORS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5
  
 NOTICE: PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED.
 SEE IMPACT FEE REVIEW COMMENTS.
  
 NOTICE: A SEPERATE ROOFING PERMIT IS REQUIRED. SEE
 ROOFING REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-06 Cont ID  
Sent By equinone Date 2021-05-06 Time 08:41 Rev Time 0.00
Received By equinone Date 2021-05-06 Time 08:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By equinone Date 2021-02-18 Time 08:53 Rev Time 0.00
Received By equinone Date 2021-02-18 Time 08:38 Sent To  
Notes
2021-02-18 08:56:46CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) TAMPER-RESISTANT RECEPTACLES REQUIRED AS PER FBC RE
 E4002.14, NEC 406.12 (A NOTE WILL SUFFICE)
 2) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN
 EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL
 UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAN 65
 LUMENS-PER-WATT?. A NOTE WILL SUFFICE. FBC EC R404.1
 3) ELECTRICAL WORK MUST COMPLY WITH NEC 2017, FBC RE
 2020. (PLEASE ADD NOTE)
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-05-06 Cont ID  
Sent By aborngra Date 2021-05-06 Time 16:52 Rev Time 0.00
Received By aborngra Date 2021-05-06 Time 16:52 Sent To  
Notes
2021-05-06 16:52:56PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
 1. THE EXISTING WOOD SASHES FOR THE WINDOWS THAT WILL
 BE REPLACED, SHALL BE RECYCLED, DONATED, OR STORED ON
 SITE TO PRESERVE AN IRREPARABLE HISTORIC RESOURCE.
 2. ALL NON-STREET FACING GLASS SHALL HAVE CLEAR GLASS
 OR CLEAR GLASS WITH LOW-E COATING. ALL STREET FACING
 GLASS SHALL HAVE CLEAR GLASS ONLY.
 3. ALL WINDOWS BEING REPLACED, SHALL BE SIZED TO FIT
 THE ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS)
 AND MATCH THE PLACEMENT/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS WITHIN THE WINDOW FRAME OPENING.
 4. THE EXISTING WOOD MULLION (CONNECTOR PIECE FOR
 PAIRED/MULTIPLE WINDOWS) MUST REMAIN OR BE REPLACED
 WITH A MULLION OF MATCHING WIDTH AND PLACEMENT.
 5. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS,
 GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION,
 LANDSCAPING, DRIVEWAY.
 6. THE LANDSCAPING INFORMATION SUPPLIED IN PERMIT
 #20120141 DOES NOT APPROVE LANDSCAPING. A SEPARATE
 LANDSCAPING PERMIT IS REQUIRED.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-03-03 Cont ID  
Sent By aborngra Date 2021-03-03 Time 14:52 Rev Time 0.00
Received By aborngra Date 2021-03-03 Time 14:51 Sent To  
Notes
2021-03-03 14:52:02THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. THE PERMIT VALUE EXCEEDS 50% OF THE IMPROVEMENT
 VALUE OF THE PROPERTY. THE PROPERTY IS REQUIRED TO
 COMPLY WITH CURRENT LANDSCAPING PERMITS PER SECTION
 94-442(C)(2) A. SINGLE FAMILY DWELLING UNITS. PLEASE
 SPEAK WITH RAY CARANCI, SENIOR LANDSCAPING PLANNER -
 [email protected] OR ANDREW BURNETT, LANDSCAPE PLANNER
 - [email protected] TO SHOW COMPLIANCE WITH CURRENT
 LANDSCAPING REQUIREMENTS OR SUBMIT A LANDSCAPING
 PERMIT. ZONING REVIEW WILL NOT PASS UNTIL A LANDSCAPING
 PERMIT NUMBER HAS BEEN ASSIGNED AND PAID FOR OR THE
 LANDSCAPE PLANNERS GIVE THE OKAY THAT IT COMPLIES.
 2. PROVIDE ALL PRODUCT APPROVALS.
 3. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS,
 GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION,
 LANDSCAPING, DRIVEWAY. PLEASE ACKNOWLEDGE THIS.
 4. SPECIFY THE EXTERIOR SIDING ?MATERIAL? AND PROVIDE
 PRODUCT APPROVAL.
 5. UPDATE PLANS TO INDICATE THAT THE FRONT ELEVATION
 WINDOWS PLUS THE WINDOW IMMEDIATELY ADJACENT TO THE
 DOOR ARE BEING RETAINED. (7 WINDOWS)
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE:
 1. THE EXISTING WOOD SASHES FOR THE WINDOWS THAT WILL
 BE REPLACED, SHALL BE RECYCLED, DONATED, OR STORED ON
 SITE TO PRESERVE AN IRREPARABLE HISTORIC RESOURCE.
 2. ALL NON-STREET FACING GLASS SHALL HAVE CLEAR GLASS
 OR CLEAR GLASS WITH LOW-E COATING. ALL STREET FACING
 GLASS SHALL HAVE CLEAR GLASS ONLY.
 3. ALL WINDOWS BEING REPLACED, SHALL BE SIZED TO FIT
 THE ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS)
 AND MATCH THE PLACEMENT/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS WITHIN THE WINDOW FRAME OPENING.
 4. THE EXISTING WOOD MULLION (CONNECTOR PIECE FOR
 PAIRED/MULTIPLE WINDOWS) MUST REMAIN OR BE REPLACED
 WITH A MULLION OF MATCHING WIDTH AND PLACEMENT.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-08-02 Cont ID  
Sent By medwards Date 2021-08-02 Time 07:16 Rev Time 0.00
Received By medwards Date 2021-07-30 Time 09:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-07-21 Cont ID  
Sent By medwards Date 2021-07-21 Time 08:04 Rev Time 0.00
Received By medwards Date 2021-07-20 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-07-16 Time   Rev Time 0.00
Received By aoliver Date 2021-07-14 Time 07:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-06-11 Time   Rev Time 0.00
Received By aoliver Date 2021-06-07 Time 10:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-18 Cont ID  
Sent By cthroop Date 2021-05-18 Time 17:25 Rev Time 0.00
Received By cthroop Date 2021-05-05 Time 15:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-03 Cont ID  
Sent By lmarchan Date 2021-03-03 Time 16:19 Rev Time 0.00
Received By lmarchan Date 2021-02-11 Time 14:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-07-07 Cont ID  
Sent By lmarchan Date 2021-07-07 Time 10:05 Rev Time 0.00
Received By lmarchan Date 2021-07-02 Time 08:20 Sent To  
Notes
2021-07-07 10:06:06RECEIPT MU-2021-032909 - $0.00 FEES DUE
2021-07-02 08:20:497/2/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-03-01 Cont ID  
Sent By cthroop Date 2021-03-01 Time 14:10 Rev Time 0.00
Received By cthroop Date 2021-03-01 Time 14:10 Sent To  
Notes
2021-03-01 14:11:47PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2021-08-02 Cont ID  
Sent By medwards Date 2021-08-02 Time 07:04 Rev Time 0.00
Received By medwards Date 2021-08-02 Time 07:04 Sent To  
Notes
2021-08-02 07:08:44THERE IS NO MECHANICAL SUB PERMIT FOR THIS PROJECT.
 PROFESSIONAL ELECTRIC CORP LICENSE # CAC1820745 HAS
 SIGNED BOTH THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS AND THE MECHANICAL DRAWINGS. THIS SAME
 CONTRACTOR MUST APPLY FOR THE MECHANICAL SUBPERMIT. A
 HOLD WILL BE PLACED ON THIS PROJECT UNTIL THE SUB
 PERMIT IS OBTAINED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2021-07-21 Cont ID  
Sent By medwards Date 2021-07-21 Time 07:59 Rev Time 0.00
Received By medwards Date 2021-07-21 Time 07:59 Sent To  
Notes
2021-07-21 08:04:121) I DO NOT SEE THAT A MECHANICAL PERMIT HAS BEEN
 ISSUED FOR THIS ADDRESS.
 2) THE DESIGNER OF THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS IS NOT A LICENSED ENGINEER NOR DOES HE
 HOLD THE MECHANICAL PERMIT TO INSTALL THE PROJECT. A
 LICENSED ENGINEER MUST SIGN AND SEAL THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS OR A LICENSED MECHANICAL
 CONTRACTOR THAT HOLDS THE PERMIT TO INSTALL THIS
 PROJECT CAN PRINT AND THEN SIGN THEIR NAME ON THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS. TIS MUST BE
 DONE BEFOR E THIS JOB WILL BE APPROVED IN PLAN REVIEW.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-07-15 Cont ID  
Sent By medwards Date 2021-07-15 Time 07:12 Rev Time 0.00
Received By medwards Date 2021-07-15 Time 07:12 Sent To  
Notes
2021-07-15 07:15:17PLEASE HAVE THE MECHANICAL CONTRACTOR SUBMIT THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS WITH HIS NAME
 PRINTED AND SIGNED. FS 471.003(H)
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-06-10 Cont ID  
Sent By medwards Date 2021-06-10 Time 07:15 Rev Time 0.00
Received By medwards Date 2021-06-10 Time 07:14 Sent To  
Notes
2021-06-10 07:17:12PLEASE SEE 2ND CYCLE REVIEW COMMENTS:
  
 1) A MECHANICAL SUB-PERMIT IS REQUIRED.
  
 2) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
 THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-05-06 Cont ID  
Sent By medwards Date 2021-05-06 Time 17:26 Rev Time 0.00
Received By medwards Date 2021-05-06 Time 17:26 Sent To  
Notes
2021-05-06 17:30:26PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS ADDITION TO THE EXISTING SYSTEM.
 THE MECHANICAL EQUIPMENT SIZING CALCULATIONS MUST BE
 FROM A FLORIDA LICENSED ENGINEER OR A FLORIDA LICENSED
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT TO INSTALL
 THIS PROJECT.
  
 1) A MECHANICAL SUB-PERMIT IS REQUIRED.
  
 2) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
 THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By hmoser Date 2021-02-18 Time 10:29 Rev Time 0.00
Received By hmoser Date 2021-02-18 Time 09:34 Sent To  
Notes
2021-02-18 10:38:45PLAN DENIED
 REFER TO SECTION M1401.3 EQUIPMENT AND APPLIANCE
 SIZING.
 HEAT LOADS AND ENERGY CALCULATIONS FOR ADDITION.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-07-16 Cont ID  
Sent By ccole Date 2021-07-16 Time 16:16 Rev Time 0.00
Received By ccole Date 2021-07-16 Time 15:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-06-11 Cont ID  
Sent By ccole Date 2021-06-11 Time 10:15 Rev Time 0.00
Received By ccole Date 2021-06-11 Time 09:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-05-06 Cont ID  
Sent By ccole Date 2021-05-06 Time 13:52 Rev Time 0.00
Received By ccole Date 2021-05-06 Time 11:48 Sent To  
Notes
2021-05-06 13:53:492ND REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20120141
 5/6/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4: THE KITCHEN SANITARY RISER AND PLAN DO NOT
 SHOW A VENT FOR THE NEW KITCHEN SINK FIXTURE DRAIN-
 SECTION P3101.2.1 FBC RES. PLEASE NOTE THAT 8 FT. IS
 THE MAX DISTANCE ALLOWABLE FOR A 2 IN. TRAP TO VENT-
 TABLE P3105.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By ccole Date 2021-02-18 Time 11:36 Rev Time 0.00
Received By ccole Date 2021-02-18 Time 10:26 Sent To  
Notes
2021-02-18 11:37:081ST REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20120141
 2/18/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4: PROVIDE A SANITARY ISOMETRIC DRAWING FOR
 THE RELOCATED KITCHEN SINK- SECTION 107.3.5.3 WPB.
  
 2) SHEET 2 SHOWER DETAIL: INDICATE THE FINISHED SHOWER
 FLOOR SHALL SLOPE UNIFORMLY TOWARD THE DRAIN NOT LESS
 THAN 1/4 UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT)- SECTIONS P2709.1 & P2709.2 FBC RES.
  
 3) SHEET 4: THE MECHANICAL PLAN SHOWS A WATER HEATER,
 WASHING MACHINE, AND SINK IN THE GARAGE. PLEASE CLARIFY
 THE SCOPE OF WORK FOR THE APPLIANCES AND FIXTURE.
 PLEASE LABEL THEM AS NEW OR EXISTING- SECTION 107.2.1
 WPB.
  
 4) SHEET 4: CLARIFY IF THERE WILL BE ANY NEW GAS FIRED
 APPLIANCES SUCH AS A TANKLESS WATER HEATER OR RANGE TO
 BE INSTALLED- SECTION 107.2.1 WPB. COMPLETE PLANS
 INCLUDING A GAS RISER DRAWING AND MANUFACTURER'S
 SPECIFICATIONS ARE REQUIRED FOR NEW GAS-FIRED APPLIANCE
 INSTALLATIONS.
  
 5) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB. A GAS-SUBMIT APPLICATION WILL ALSO BE
 REQUIRED IF GAS IS TO BE COVERED UNDER THIS MAIN
 PERMIT. GAS CAN ALSO BE COVERED UNDER A SEPARATE
 PRIMARY PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-03-01 Cont ID  
Sent By cthroop Date 2021-03-01 Time 14:08 Rev Time 0.00
Received By cthroop Date 2021-03-01 Time 10:52 Sent To  
Notes
2021-03-01 14:09:12PROVISO ON PLAN SHEET S2. SEPERATE ROOFING PERMIT
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status N Date 2021-07-14 Cont ID  
Sent By medwards Date 2021-07-14 Time 09:09 Rev Time 0.00
Received By medwards Date 2021-07-14 Time 09:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-11 Cont ID  
Sent By ccole Date 2021-06-11 Time 10:15 Rev Time 0.00
Received By ccole Date 2021-06-11 Time 09:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-18 Cont ID  
Sent By cthroop Date 2021-05-18 Time 17:25 Rev Time 0.00
Received By cthroop Date 2021-05-18 Time 16:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-01 Cont ID  
Sent By cthroop Date 2021-03-01 Time 14:07 Rev Time 0.00
Received By cthroop Date 2021-03-01 Time 10:52 Sent To  
Notes
2021-03-01 14:08:23CONTRACTOR SIGNED ARCH. PLANS, ENGINEER SIGNED
 STRUCTURAL PLANS. CT

Review Stop Z ZONING
Rev No 2 Status P Date 2021-05-06 Cont ID  
Sent By aborngra Date 2021-05-06 Time 16:53 Rev Time 0.00
Received By aborngra Date 2021-05-06 Time 16:53 Sent To  
Notes
2021-05-06 16:53:23CONDITIONAL APPROVAL FOR LANDSCAPING.
  
 PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
 1. THE EXISTING WOOD SASHES FOR THE WINDOWS THAT WILL
 BE REPLACED, SHALL BE RECYCLED, DONATED, OR STORED ON
 SITE TO PRESERVE AN IRREPARABLE HISTORIC RESOURCE.
 2. ALL NON-STREET FACING GLASS SHALL HAVE CLEAR GLASS
 OR CLEAR GLASS WITH LOW-E COATING. ALL STREET FACING
 GLASS SHALL HAVE CLEAR GLASS ONLY.
 3. ALL WINDOWS BEING REPLACED, SHALL BE SIZED TO FIT
 THE ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS)
 AND MATCH THE PLACEMENT/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS WITHIN THE WINDOW FRAME OPENING.
 4. THE EXISTING WOOD MULLION (CONNECTOR PIECE FOR
 PAIRED/MULTIPLE WINDOWS) MUST REMAIN OR BE REPLACED
 WITH A MULLION OF MATCHING WIDTH AND PLACEMENT.
 5. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS,
 GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION,
 LANDSCAPING, DRIVEWAY.
 6. THE LANDSCAPING INFORMATION SUPPLIED IN PERMIT
 #20120141 DOES NOT APPROVE LANDSCAPING. A SEPARATE
 LANDSCAPING PERMIT IS REQUIRED.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-03 Cont ID  
Sent By aborngra Date 2021-03-03 Time 14:52 Rev Time 0.00
Received By aborngra Date 2021-03-03 Time 14:52 Sent To  
Notes
2021-03-03 14:52:15THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. THE PERMIT VALUE EXCEEDS 50% OF THE IMPROVEMENT
 VALUE OF THE PROPERTY. THE PROPERTY IS REQUIRED TO
 COMPLY WITH CURRENT LANDSCAPING PERMITS PER SECTION
 94-442(C)(2) A. SINGLE FAMILY DWELLING UNITS. PLEASE
 SPEAK WITH RAY CARANCI, SENIOR LANDSCAPING PLANNER -
 [email protected] OR ANDREW BURNETT, LANDSCAPE PLANNER
 - [email protected] TO SHOW COMPLIANCE WITH CURRENT
 LANDSCAPING REQUIREMENTS OR SUBMIT A LANDSCAPING
 PERMIT. ZONING REVIEW WILL NOT PASS UNTIL A LANDSCAPING
 PERMIT NUMBER HAS BEEN ASSIGNED AND PAID FOR OR THE
 LANDSCAPE PLANNERS GIVE THE OKAY THAT IT COMPLIES.
 2. PROVIDE ALL PRODUCT APPROVALS.
 3. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS,
 GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION,
 LANDSCAPING, DRIVEWAY. PLEASE ACKNOWLEDGE THIS.
 4. SPECIFY THE EXTERIOR SIDING ?MATERIAL? AND PROVIDE
 PRODUCT APPROVAL.
 5. UPDATE PLANS TO INDICATE THAT THE FRONT ELEVATION
 WINDOWS PLUS THE WINDOW IMMEDIATELY ADJACENT TO THE
 DOOR ARE BEING RETAINED. (7 WINDOWS)
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE:
 1. THE EXISTING WOOD SASHES FOR THE WINDOWS THAT WILL
 BE REPLACED, SHALL BE RECYCLED, DONATED, OR STORED ON
 SITE TO PRESERVE AN IRREPARABLE HISTORIC RESOURCE.
 2. ALL NON-STREET FACING GLASS SHALL HAVE CLEAR GLASS
 OR CLEAR GLASS WITH LOW-E COATING. ALL STREET FACING
 GLASS SHALL HAVE CLEAR GLASS ONLY.
 3. ALL WINDOWS BEING REPLACED, SHALL BE SIZED TO FIT
 THE ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS)
 AND MATCH THE PLACEMENT/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS WITHIN THE WINDOW FRAME OPENING.
 4. THE EXISTING WOOD MULLION (CONNECTOR PIECE FOR
 PAIRED/MULTIPLE WINDOWS) MUST REMAIN OR BE REPLACED
 WITH A MULLION OF MATCHING WIDTH AND PLACEMENT.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  