| 2020-12-08 14:24:44 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20120003 |
| | ADD: 2400 S DIXIE HWY. |
| | CONT: BUTLER CONSTRUCTION |
| | TEL: 561-832-9700 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. DEC. 08TH/2020 |
| | ACTION: DENIED |
| | |
| | 1) MISSING CODE DATA NOT FOUND ON THE PLANS, NO LIFE |
| | SAFETY SHEET. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| | OR STRUCTURES. |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | |
| | 1A) MISSING CODE DATA: |
| | OCCUPANCY GROUP OLD AND PROPOSED NEW |
| | CHANGE OF OCCUPANCIES FOR A WHOLE BUILDING WOULD |
| | REQUIRE THE PLANS DESIGNED TO THE 2017 FBC-EXISTING |
| | BUILDING CODE, CHAPTER 10, AND SECTION 1001.2.2, FOR A |
| | FULL BUILDING. |
| | |
| | 1B) MINIMUM TYPE OF CONSTRUCTION SECTION 503 |
| | FIRE SPRINKLERED OR NOT |
| | FIRE RESISTANCE SEPARATION |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | FIRE BLOCKING AND DRAFT STOPPING AND CALCULATED FIRE |
| | RESISTANCE |
| | |
| | 1C) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | EARLY WARNING SMOKE EVACUATION SYSTEMS |
| | SCHEMATIC FIRE SPRINKLERS |
| | STANDPIPES |
| | PRE-ENGINEERED SYSTEMS |
| | RISER DIAGRAM |
| | |
| | 1D) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | SPECIFIC OCCUPANCY REQUIREMENTS |
| | CONSTRUCTION REQUIREMENTS |
| | |
| | 2) SHEET A002 SITE DETAILS / ACCESSIBLE STALL PARKING. |
| | THE DETAIL DOES NOT MEET THE CITY STANDARD FOR |
| | ACCESSIBLE PARKING SPACES, PLEASE REVIEW CITY OF W. P. |
| | B. STANDARD LINES ARE 4 INCHES WIDE WITH 12 INCHES/ 1 |
| | FOOT BETWEEN LINES. |
| | ACCESSIBLE PARKING SPACE / STALL PAINTING. |
| | |
| | 2A) 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE |
| | SPACES. EACH PARKING SPACE MUST BE AT LEAST 12 FEET |
| | WIDE, SHALL BE MARKED TO DEFINE THE WIDTH, AND SHALL |
| | HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH 502.3. |
| | ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR |
| | OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT |
| | MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| | WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485 |
| | ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL |
| | PAINTING. |
| | |
| | 2B) IN THESE DETAILS THE ELEVATIONS ARE NOT GIVEN AT |
| | THE CORNERS OF THE ACCESSIBLE PARKING SPACE AND |
| | ADJACENT ACCESS AISLE. |
| | 2017 FBC-ACCESSIBILITY CODE 502.4 ACCESS AISLE & |
| | PARKING SPACE SAME LEVEL/ 502.4, FLOOR AND GROUND |
| | SURFACES. PARKING SPACES AND THE ACCESS AISLES SERVING |
| | THEM SHALL COMPLY WITH 302. ACCESS AISLES SHALL BE AT |
| | THE SAME LEVEL AS THE PARKING SPACES THEY SERVE. |
| | CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES |
| | NOT GREATER THAN 1:48 SHALL BE PERMITTED. |
| | |
| | 3) SHEET A101: |
| | 3A) SHEET A101 IT IS ASSUMED TO BE THE PROPOSED LAYOUT |
| | OF THE BASEMENT PLAN. NO LIFE SAFETY INFORMATION WAS |
| | PROVIDED FOR THIS REVIEW. THE BASEMENT PLAN DOES NOT |
| | SHOW THE COMMON PATH OF TRAVEL FROM THE FURTHEST POINT |
| | TIN THE BASEMENT TO THE HEAD OF THE STAIRS AT WHICH YOU |
| | HAVE 2 CHOICES OF EXIT TRAVEL, PLEASE SHOW COMPLIANCE |
| | WITH THE 2017 FBC-B TABLE 1006.3.2(2). |
| | |
| | 3B) THERE IS NO INFORMATION ON THE STAIRWAY AND |
| | HANDRAILS IF THEY ARE EXISTING AND THE RISE / RUN OF |
| | THE STAIRS NOR IF THERE IS ANY HANDRAILS. SEE THE 2017 |
| | FBC-EXISTING BUILDING CODE SECTION 1012.4.2. |
| | |
| | 4) SHEET A102 THE PROPOSED 1ST FLOOR PLAN: |
| | 4A) THE PLANS DO NOT SHOW WHICH EGRESS DOORS ARE |
| | ACCESSIBLE EXITS. 2017 FBC-ACCESSIBILITY CODE SECTION |
| | 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION |
| | 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000 |
| | EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE |
| | INTERNATIONAL BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | 4B) THE PLANS DO NOT SHOW COMPLIANCE WITH SECTION |
| | 1007.1.1 OF THE 2017 FBC-B, TWO EXITS AND OR EXIT |
| | ACCESS DOORWAYS. |
| | WHERE 2 EXIT OR EXIT ACCESS DOORWAYS ARE REQUIRED FROM |
| | ANY PORTION OF THE EXIT ACCESS, THEY SHALL BE PLACED A |
| | DISTANCE APART EQUAL TO NOT LESS THAN ? THE OVERALL |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR |
| | AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN |
| | THEM. |
| | EXCEPTION BUILDINGS EQUIPPED THROUGHOUT WITH AN |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 903.3.1.1 OR 903.3.1.2, THE SEPARATION DISTANCE SHALL |
| | NOT BE LESS THAN 1/3RD OVERALL DIAGONAL DIMENSION OF |
| | THE BUILDING OR AREA TO BE SERVED MEASURED IN A |
| | STRAIGHT LINE BETWEEN THEM. |
| | |
| | 4C) PLEASE REVIEW THE STAIRWAY THAT LEADS FORM THE |
| | BASEMENT. THE 2017 FBC-B SECTION 1019.3 WOULD REQUIRE |
| | THE STAIRWAY TO BE ENCLOSED WITH A SHAFT ENCLOSURE |
| | CONSTRUCTED IN ACCORDANCE WITH 713. DOORS WILL NEED TO |
| | SHOW COMPLIANCE WITH 713.7 & 716 FOR FIRE BARRIER. |
| | DOORS SHALL BE SELF OR AUTOMATIC CLOSING BY SMOKE |
| | DETECTION IN ACCORDANCE WITH 716.5.9.3. |
| | |
| | 4D)(1) THE PROPOSED FLOOR PLAN SHOWS A NEW 800 SQ. FT. |
| | WALK IN COOLER. PLEASE NOTE WALK IN COOLERS REQUIRE A |
| | SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES. THEY ARE |
| | ALSO PART OF THE COMPONENTS AND CLADDING OF THE |
| | BUILDING AND REQUIRE PRODUCT APPROVALS. 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: (31)(G) EXTERIOR COOLER, FREEZERS |
| | |
| | 4D)(2) *00 SQ. FT. COOLERS WILL ALSO NEED TO SHOW |
| | COMPLIANCE WITH THE 2017 FBC-B SECTION 2603.4.1.2 AND |
| | 2603.4.1.3. |
| | |
| | 4E) THE PLAN INDICATES THERE IS 110 INDOOR SEATS. THE |
| | FLOOR PLAN DOES NOT SHOW ANY ACCESSIBLE SEATING. PLEASE |
| | SHOW COMPLIANCE WITH THE FOLLOWING ACCESSIBILITY |
| | REQUIREMENTS: |
| | |
| | 4E)(1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE |
| | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| | SEATING SPACES AND STANDING SPACES AT THE DINING |
| | SURFACES SHALL COMPLY WITH 902. 110X0.05= 6SEATS. |
| | |
| | 4E)(2) 226.2 DISPERSION. DINING SURFACES AND WORK |
| | SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 4E)(3) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN |
| | RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL |
| | BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR |
| | SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| | |
| | 4E)(4) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS, AND WHERE COVERED BY THE ADA SCOPING |
| | PROVISIONS, EMPLOYEE WORKSTATIONS (CHECK-OUT COUNTERS). |
| | |
| | 4E)(5)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR |
| | FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 4E)(5)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 4F) PLEASE LOOK AT DOORS 12 & 13 MISSING MANEUVERING |
| | CLEARANCES AT DOORS. ACCESS. CODE 404.2.4 MANEUVERING |
| | CLEARANCES. DOORS. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| | COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| | EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| | LATCH SIDE FOR SIDE CLEARANCE. |
| | |
| | 4G) PLEASE NOTE THE EXTERIOR DOOR LOCATED BY THE HAND |
| | SINK AND OLE HICKORY IS A INSWING DOOR THE OCCUPANT |
| | LOAD OF THE BUILDING IS WELL OVER 50. 2017 FBC-B |
| | 1010.1.2.1. DIRECTION OF SWING. PIOT OR SIDE-HINGED |
| | SWINGING DOORS SHALL SWING IN THE DIRECTION OF EGRESS |
| | TRAVEL WHERE SERVING ROOMS OR AREAS CONTAINING AN |
| | OCCUPANT LOAD OF 50 OR MORE. |
| | |
| | 5) SHEET A104 ENLARGES RESTROOM FLOOR PLAN & |
| | ELEVATIONS: |
| | 5A) THERE IS NO FINISHES SHEET FOR FLOORS, WALLS & |
| | CEILINGS. SHEET A104 IN THE SOUTH ELEVATION OF THE MENS |
| | RESTROOM STATES LINE OF SMOOTH, HARD, NONABSORBENT |
| | SURFACES ABOVE THE FLOOR. 2017 FBC-B 1210.2.2. WALLS & |
| | PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING |
| | OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO |
| | LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE. |
| | |
| | 5A)(1) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF |
| | SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT |
| | LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A |
| | TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 5A)(2) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET |
| | WALLS SHALL COMPLY WITH 1210.2. |
| | |
| | 5A)(3) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS |
| | AND PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY |
| | WITH SECTIONS 1210.1 THROUGH 1210.4. |
| | |
| | 5B) WITHIN THE LADIES RESTROOM WHEN THE BABY CHANGING |
| | TABLE IS IN THE DOWN POSITION YOU DO NOT HAVE THE |
| | MANEUVERING CLEARANCES AT DOOR # 07. ACCESS. CODE |
| | 404.2.4 MANEUVERING CLEARANCES. DOORS. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| | COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| | EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| | LATCH SIDE FOR SIDE CLEARANCE. FIGURE 404.2.4.1(A). |
| | |
| | 5C) IN BOTH THE MENS AND WOMENS RESTROOMS THE HEIGHT |
| | ABOVE THE FLOOR IS NOT GIVEN, SHOW COMPLIANCE WITH |
| | 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY CODE. MIRRORS |
| | LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE |
| | INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 5D) THE TOILET PAPER DISPENSER DOES NOT COMPLY WITH THE |
| | DISTANCE FROM THE FRONT OF THE WATER CLOSET. TOILET |
| | PAPER DISPENSERS. 604.7. THE TOILET PAPER DISPENSER |
| | SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM |
| | TO 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. |
| | |
| | 5E) THE ELEVATIONS FOR BOTH THE MENS AND LADIES |
| | RESTROOMS DEPICT THE GRAB BARS DIMENSIONED FROM THE |
| | CENTER LINE. PLEASE NOTE THE 2017 FBC-ACCESSIBILITY |
| | CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS |
| | SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES |
| | MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| | MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT |
| | CENTERLINE. |
| | |
| | 5F) THE ELEVATIONS FOR BOTH THE MENS AND LADIES |
| | RESTROOMS DEPICT THE LAVATORY WITH A PROTECTION BOARD |
| | FOR PREVENTING EXPOSED PIPES IN COMPLIANCE WITH 606.5. |
| | WHAT IS MISSING FROM THE DETAIL IS COMPLIANCE WITH |
| | 306.2 CLEARANCES FOR TOES AND 306.3 CLEARANCES FOR |
| | KNEES. |
| | |
| | 5G) WHAT DETAILS FOR ACCESSIBILITY WERE NOT PROVIDED |
| | AND OR EXCEPTION ARE FOR DRINKING FOUNTAINS. |
| | 5G)(1) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED. |
| | |
| | 5G)(2) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. |
| | CODE. SPOUT OUTLETS SHALL COMPLY WITH: |
| | 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS. |
| | 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE |
| | BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR. |
| | |
| | 5G)(3) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS |
| | 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES |
| | AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT |
| | PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE |
| | CIRCULATION PATH. |
| | |
| | 6) SHEET S101 THE ROOF FRAMING PLAN. THE WIND DESIGN |
| | CRITERIA ARE GIVEN ON THIS PLAN WHAT IS MISSING IS THE |
| | MEAN ROOF HEIGHT. WIND EXPOSURE. APPLICABLE WIND |
| | DIRECTION IF MORE THAN ONE WIND EXPOSURE IS UTILIZED. |
| | TABLE 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE |
| | 30.3.1. THE ELEVATIONS ON THE 200 SERIES OF DRAWINGS |
| | SHOWS THE ROOF AT 29.0 + PARAPET APPROX.. 30 FEET. |
| | |
| | 7) THE COMPONENT AND CLADDING PRESSURES FOUND ON S302 |
| | FOR THE ROOF AND WALL ZONES ARE GIVEN IN VASD. THANK |
| | YOU. THE WALL PRESSURES ARE UP TO 9.0 LBS. LOW PER PSF. |
| | WE ARE TAKING THE PRESSURES FROM AN ENGINEERS SPREAD |
| | SHEET FOR WALL COMPONENTS & CLADDING AND COMPARING TO |
| | ASCE 7-10 FIGURE 30.5.1, AS WELL AS THE PRESSURES FOUND |
| | IN THE 2017 RESIDENTIAL CODE THE SIMPLIFIED TABLE |
| | R301.2(2). |
| | |
| | 8) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| | WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| | REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF |
| | FRAMING INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 9) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP CURBS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 10) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 12) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| | FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| | OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| | THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| | WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| | ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| | STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| | IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| | |
| | 13) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 14) 2017 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS |
| | OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING |
| | ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED |
| | STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL |
| | WILL HAVE TO CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE |
| | GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN |
| | INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. |
| | SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER |
| | OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) IN HEIGHT |
| | OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS |
| | VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| | SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE |
| | LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER PARAPET |
| | WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE |
| | PARAPET WALL. |
| | |
| | 15) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE |
| | REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA |
| | PROJECT DOX UPON NOTIFICATION BY THIS OFFICE. |
| | NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL |
| | FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT |
| | (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT |
| | FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE |
| | FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN |
| | BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT |
| | ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| | YOUR PROJECT OR EMAIL IT TO [email protected] . |
| | |
| | 16) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |