| 2020-12-29 10:36:21 | 12/29/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THERE IS NO CHANGE OF OCCUPANCY FOR THIS BUILDING |
| | AND A FOUR TIMES FEE VIOLATION ON THIS STRUCTURE FOR |
| | WORK BEING DONE WITHOUT A PERMIT, ANY SUCH WORK TO BE |
| | DONE, SHALL FIRST MAKE AN APPLICATION TO THE BUILDING |
| | OFFICIAL AND OBTAIN THE REQUIRED PERMIT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 2. THE PERMIT APPLIED FOR WAS FOR PLUMBING, BUT AN |
| | INTERCEPTOR PERMIT IS REQUIRED. THE PERMIT TYPE HAS |
| | BEEN CHANGED TO AN INTERCEPTOR, AND THE FEE WILL NEED |
| | TO BE ADJUSTED. THE CLAIMED VALUE APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, AND PLEASE PROVIDE A |
| | BONA FIDE SIGNED CONTRACT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 109.3 BUILDING PERMIT VALUATIONS. |
| | |
| | 3. PROVIDE SIZING CALCULATIONS FOR GREASE INTERCEPTOR |
| | PDI BK-GT 70 INCLUDE ALL FIXTURES REQUIRED TO DISCHARGE |
| | THROUGH INTERCEPTOR THREE-COMPARTMENT SINK MOP SINK ANY |
| | OTHER SINK RECEIVING GREASE WASTE PER THE 2017 FBC SEC. |
| | P 1003. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |