| 2020-11-25 12:46:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET SITE PLAN - THE OCCUPANCY LOAD CALUCLATION |
| | DOES NOT APPEAR TO MEET THE REQUIRMENTS OF NFPA 101, CH |
| | 7 |
| | |
| | 13,237 SQ FT OF AN ASSEMBLY OCCUPANCY IS PER TABLE |
| | 7.3.1.2 AT 15 SQ FT/ PERSON. P OR 889 |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 1A) THERE ARE INDICATIONS OF STAIRS LEADING FROM EACH |
| | AREA AS A PART OF THE EGRESS PATH TO A PUBLIC WAY. |
| | |
| | THE CAPACITY AND CLACULATION OF STAIRS WITHIN AN EXIT |
| | TRAVLE PATH ARE CALCULATED DIFFERENT AND SEPARATE OF A |
| | SIMPLE EXIT OPENING. |
| | |
| | PER TABLE 7.3.3.1 - .3 IS THE REQUIRED FACTOR |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | 1B) BASED ON THE ABOVE THERE ARE INSUFFICIENT EGRESS |
| | CAPACITY TO ACCOMDATE THE REQUIREMENT. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 2) THERE IS AN INDICATION A FIRE SPRINKLERS AND A |
| | STATEMENT " AND SHALL HAS A FIRE ALARM SYSTEM" |
| | |
| | PLEASE DEFINE THIS STATEMENT AND PROVIDE WHAT TYPE OF |
| | FIRE ALARM IS EXISTING OR WILL BE PROVIDED. |
| | |
| | WHAT KIND/TYPE/LOCATION OF NOTIFICATION DEVICES ARE |
| | WITHIN THE PROPOSED AREA? |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | 2A) ANY WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 3) EXIT DOORS ARE INDICATED; HOWEVER, THERE ARE NO |
| | INDICATIONS OF THE EXIT HARDWARE TYPE. |
| | |
| | PANIC HARDWARE IS REQUIRED. |
| | |
| | PER NFPA 101, CH 12 ASSEMBLY OCCUPANCIES |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE |
| | PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| | IS PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| | UNLESS |
| | OTHERWISE PERMITTED BY ONE OF THE FOLLOWING |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | LOCKS AS |
| | PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| | ACCESS-CONTROLLED EGRESS DOORS |
| | AS PERMITTED IN 12.2.2.2.6. |
| | 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 |
| | SHALL BE PERMITTED |
| | TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS |
| | IF BOTH OF THE |
| | FOLLOWING CONDITIONS APPLY: |
| | (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| | AND THE ASSEMBLY |
| | OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. |
| | (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| | ASSEMBLY |
| | OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE |
| | RELEASED |
| | BY PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT. |
| | |
| | |
| | |
| | 4) PLEASE PROVIDE DETAILS OF WHAT KIND OF EVENT IS |
| | PROPOSED. |
| | |
| | WILL THERE BE ANY PYROTECHICS/ OPEN FLAME EFFECTS, |
| | ETC.? |
| | |
| | PLEASE PROVIDE DETAILS |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |