Plan Review Details - Permit 20111057
Plan Review Stops For Permit 20111057
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-03-29 Cont ID  
Sent By rmcphers Date 2021-03-29 Time 16:49 Rev Time 0.00
Received By rmcphers Date 2021-03-29 Time 16:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-02-17 Cont ID  
Sent By rmcphers Date 2021-02-17 Time 14:17 Rev Time 0.00
Received By rmcphers Date 2021-02-17 Time 14:17 Sent To  
Notes
2021-02-17 14:40:30NEW SIDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL PROVIDED IS FOR "REVEAL" AND
 "PRESSED REVEAL" 48" WIDE X 96" LONG - PLEASE PROVIDE
 THE PRODUCT APPROVAL FOR "HARDIEPLANK" LAP SIDING -
 FLORIDA STATE PRODUCT APPROVAL CAN BE FOUND AT ( HTTPS:
 //WWW.FLORIDABUILDING.ORG/PR/PR_APP_DTL.ASPX?PARAM=WGEV
 XQWTDQTSK%2BGNUU47OQXMAHRNHILDHQLEIJJDGBAR2WA%2BS4GYEG%
 3D%3D ). OR
 ( HTTPS://WWW.FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX )
 AND SEARCH FOR ( FL 13192 ) AND SEE IF THATS WHAT YOU
 ARE USING.
 2) THE JOB VALUE SHOWN ON THE BUILDING PERMIT
 APPLICATION APPEARS TO BE LOW - PLEASE REVISE THE
 BUILDING PERMIT APPLICATION TO SHOW THE CORRECT JOB
 VALUE - (JOB VALUE SHOULD INCLUDE MATERIALS + LABOR AS
 IF A CONTRACTOR PRICED THE JOB) - FBC WPB AMENDMENTS ?
 FOR PERMITTING PURPOSES THE VALUE OF ALL LABOR AND
 MATERIALS REQUIRED TO COMPLETE THE PROJECT ARE REQUIRED
 TO BE INCLUDED IN THE COST. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL ? SWIFT,
 MEANS, ETC.) AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-21 Cont ID  
Sent By rmcphers Date 2020-12-21 Time 13:12 Rev Time 0.00
Received By rmcphers Date 2020-12-21 Time 13:01 Sent To  
Notes
2020-12-21 13:12:36NEW SIDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A BUILDING LAYOUT SHOWING WHICH WALLS
 ARE TO RECEIVE SIDING.
 2) PLEASE WRITE A SCOPE OF WORK ON THE BUILDING LAYOUT
 DRAWING STATING WHAT YOU ARE DOING (REPLACING OLD
 SIDING?) (ADDING SIDING TO EXISTING STUCCO WALLS?)
 3) SIDING IS SUBJECT TO WIND LOADS - PLEASE PROVIDE A
 MIAMI DADE OR FLORIDA STATE PRODUCT APPROVAL WHICH WILL
 SHOW THE WIND PRESSURES AND HOW TO INSTALL THE SIDING
 OR PROVIDE DRAWINGS SHOWING HOW TO INSTALL THE SIDING
 ALONG WITH STRUCTURAL CALCULATIONS FOR THE WIND LOADS
 OR PROVIDE SIGNED AND SEALED SIDING ATTACHMENT DRAWINGS
 FROM AN ARCHITECT OR ENGINEER.
 TO COMPLY WITH FBC R703.1.2 WIND RESISTANCE.
 WALL COVERINGS, BACKING MATERIALS AND THEIR ATTACHMENTS
 SHALL BE CAPABLE OF RESISTING WIND LOADS IN ACCORDANCE
 WITH TABLES R301.2(2) AND R301.2(3) FOR WALLS USING AN
 EFFECTIVE WIND AREA OF 10 SQUARE FEET. WIND-PRESSURE
 RESISTANCE OF THE SIDING AND BACKING MATERIALS SHALL BE
 DETERMINED BY ASTM E330 OR OTHER APPLICABLE STANDARD
 TEST METHODS. WHERE WIND-PRESSURE RESISTANCE IS
 DETERMINED BY DESIGN ANALYSIS, DATA FROM APPROVED
 DESIGN STANDARDS AND ANALYSIS CONFORMING TO GENERALLY
 ACCEPTED ENGINEERING PRACTICE SHALL BE USED TO EVALUATE
 THE SIDING AND BACKING MATERIAL AND ITS FASTENING. ALL
 APPLICABLE FAILURE MODES INCLUDING BENDING RUPTURE OF
 SIDING, FASTENER WITHDRAWAL AND FASTENER HEAD
 PULL-THROUGH SHALL BE CONSIDERED IN THE TESTING OR
 DESIGN ANALYSIS. WHERE THE WALL COVERING AND THE
 BACKING MATERIAL RESIST WIND LOAD AS AN ASSEMBLY, USE
 OF THE DESIGN CAPACITY OF THE ASSEMBLY SHALL BE
 PERMITTED.

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2021-03-30 Cont ID  
Sent By fmittner Date 2021-03-30 Time 10:34 Rev Time 0.00
Received By fmittner Date 2021-03-30 Time 10:34 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-03-12 Cont ID  
Sent By fmittner Date 2021-03-12 Time 16:45 Rev Time 0.00
Received By fmittner Date 2021-03-12 Time 16:45 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2020-12-28 Cont ID  
Sent By fmittner Date 2020-12-28 Time 16:27 Rev Time 0.00
Received By fmittner Date 2020-12-28 Time 16:27 Sent To  
Notes
2020-12-28 16:28:23HISTORIC PROPERTY WITH WOOD SIDING, NEED TO RETAIN WOOD
 SIDING AND REPAIR WITH WOOD ON LIMITED BASIS. IF AREAS
 ARE NOT CURRENTLY WOOD SIDING NEED TO DEMONSTRATE WITH
 PHOTOS AND DIAGRAMS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-30 Cont ID  
Sent By lmarchan Date 2021-03-30 Time 14:24 Rev Time 0.00
Received By lmarchan Date 2021-03-17 Time 15:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-12 Cont ID  
Sent By lmarchan Date 2021-03-12 Time 17:02 Rev Time 0.00
Received By lmarchan Date 2021-02-03 Time 07:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-04 Cont ID  
Sent By shill Date 2021-01-04 Time 10:34 Rev Time 0.00
Received By shill Date 2020-12-15 Time 15:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-03-29 Cont ID  
Sent By rmcphers Date 2021-03-29 Time 16:49 Rev Time 0.00
Received By rmcphers Date 2021-03-29 Time 16:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-02-17 Cont ID  
Sent By rmcphers Date 2021-02-17 Time 14:41 Rev Time 0.00
Received By rmcphers Date 2021-02-17 Time 14:41 Sent To  
Notes
2021-02-17 14:41:59SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-21 Cont ID  
Sent By rmcphers Date 2020-12-21 Time 13:12 Rev Time 0.00
Received By rmcphers Date 2020-12-21 Time 13:12 Sent To  
Notes
2020-12-21 13:13:22SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 2 Status P Date 2021-03-12 Cont ID  
Sent By fmittner Date 2021-03-12 Time 16:45 Rev Time 0.00
Received By fmittner Date 2021-03-12 Time 16:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-28 Cont ID  
Sent By kalexand Date 2020-12-28 Time 16:28 Rev Time 0.00
Received By fmittner Date 2020-12-28 Time 16:28 Sent To  
Notes
2020-12-28 16:28:47SEE HISTORIC COMMENTS


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved