| 2021-03-04 09:56:41 | SECOND BUILDING REVIEW COMMENTS FOR REVISED DRAWINGS TO |
| | COMPLY WITH PROVISO: |
| | |
| | ARCHITECTS-ENGINEERS |
| | FLORIDA STATUTE 553.80(2)(B): |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| | |
| | |
| | 1- SHEET A4.2: |
| | A)OK. |
| | |
| | ORIGINAL COMMENT: |
| | B)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW THE |
| | TOP AND BOTTOM EXTENSION AT RAMP. AND PROVIDE DETAILS. |
| | SEC. 505.10.1 FBC-ACCESSIBILITY. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NO ADDRESSED. RAMP SHOWS TOP AND BOTTOM |
| | EXTENSIONS BUT DETAILS WERE NOT PROVIDED. NOTE: SEE |
| | FIGURE 505.10.1 FBC-ACCESSIBILITY FOR HANDRAIL |
| | EXTENSION DETAIL AT RAMPS AND PROVIDE DETAIL AS |
| | REQUIRED. |
| | |
| | C)DETAIL #14 AND DETAIL #17: THE BOTTOM EXTENSION AT |
| | STAIRS NEED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT |
| | AS REQUIRED BY SEC. 505.10.3 FBC-ACCESSIBILITY. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. DETAIL #17 AND DETAIL #14 DON'T SHOW |
| | THE BOTTOM EXTENSION AT THE SLOPE OF THE STAIR FLIGHT |
| | AS REQUIRED BY SEC. 505.10.3 FBC-ACCESSIBILITY. REVISE |
| | AS REQUIRED. |
| | NOTE: REVISE DETAIL #22 ON SHEET A4.3 ALSO TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 2- OK. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |