| 2020-11-20 17:29:57 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- "SHAKER" PVC DOORGLASS ASSEMBLY SUBMITTED (FLORIDA |
| | PRODUCT APPROVAL FL30712.1) |
| | IS NOT A COMPLETE DOOR ASSEMBLY. ACCORDING TO GENERAL |
| | NOTE #6 ON SHEET 1 OF 4 THIS DOORGLASS ASSEMBLY WAS |
| | TESTED WITH THE SPECIFIC PANELS SHOWN ON SHEET 4 OF 4. |
| | PROVIDE COMPLETE PRODUCT APPROVAL FOR ANY DOOR LISTED |
| | ON SHEET 4 OF 4 OR PROVIDE COMPLETE SITE SPECIFIC |
| | ENGINEERING FOR ANOTHER DOOR PRODUCT APPROVAL. |
| | |
| | THERMA TRU DOOR PRODUCT APPROVAL SUBMITTED (FL7640.1) |
| | REQUIRES SITE SPECIFIC ENGINEERING WHEN THERE IS A |
| | DEVIATION/CHANGES TO THE DOOR ASSEMBLY. SEE GENERAL |
| | NOTE #5 ON SHEET 1 OF 9. |
| | |
| | SEC. 107.2.1.2 CITY AMENDMENTS AND SEC. 61G20-3.001 |
| | F.A.C. |
| | |
| | 2- FLORIDA PRODUCT APPROVALS SUBMITTED ARE INCOMPLETE. |
| | NEED TO PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL |
| | INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE THAT |
| | CORRESPONDS TO THE DRAWINGS SUBMITTED. THE FLORIDA |
| | PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS IF |
| | PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT. CHAPTER |
| | 553 F.S. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |