Plan Review Details - Permit 20110700
Plan Review Stops For Permit 20110700
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By cthroop Date 2020-12-07 Time 13:37 Rev Time 0.00
Received By cthroop Date 2020-12-07 Time 06:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 15:29 Rev Time 0.00
Received By cthroop Date 2020-11-30 Time 09:16 Sent To  
Notes
2020-11-30 15:39:32PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PROVISO: PROVIDE ICC-ES REPORT FOR SPRAY FOAM
 INSULATION TO CITY INSPECTOR.
  
 PROVISO: A SEPERATE ROOFING PERMIT IS REQUIRED.
  
 NOTICE: PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED.
  
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED WINDOWS AND
 EXT. DOORS.
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 NOTICE: YOU MAY DEFER YOUR PRODUCT APPROVALS:
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By cthroop Date 2020-12-07 Time 14:16 Rev Time 0.00
Received By cthroop Date 2020-12-07 Time 06:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 15:48 Rev Time 0.00
Received By cthroop Date 2020-11-30 Time 14:11 Sent To  
Notes
2020-11-30 15:49:56PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. HIGH EFFICACY LAMPS
  
 PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS".
  
 A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1
  
 2. EQUIPMENT SERVICE OUTLETS
  
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 3. 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A
 BUILDING.
 WHERE AN ADDITION IS MADE TO A BUILDING OR STRUCTURE OF
 A GROUP R OR I-1 OCCUPANCY, THE EXISTING BUILDING SHALL
 BE PROVIDED WITH SMOKE ALARMS AS REQUIRED BY THE
 FLORIDA FIRE PREVENTION CODE OR SECTION R314 OF THE
 FLORIDA BUILDING CODE, RESIDENTIAL AS APPLICABLE.
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 R314.1 GENERAL.
 SMOKE ALARMS SHALL COMPLY WITH NFPA 72 AND SECTION
 R314.
  
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. 1.IN EACH SLEEPING ROOM.
 2. 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE
 IMMEDIATE VICINITY OF THE BEDROOMS.
 3. 3.ON EACH ADDITIONAL STORY OF THE DWELLING,
 INCLUDING BASEMENTS AND HABITABLE ATTICS AND NOT
 INCLUDING CRAWL SPACES AND UNINHABITABLE ATTICS. IN
 DWELLINGS OR DWELLING UNITS WITH SPLIT LEVELS AND
 WITHOUT AN INTERVENING DOOR BETWEEN THE ADJACENT
 LEVELS, A SMOKE ALARM INSTALLED ON THE UPPER LEVEL
 SHALL SUFFICE FOR THE ADJACENT LOWER LEVEL PROVIDED
 THAT THE LOWER LEVEL IS LESS THAN ONE FULL STORY BELOW
 THE UPPER LEVEL.
 4. 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3
 FEET (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF
 A BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS
 THIS WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED
 BY SECTION R314.3
  
 R314.4 INTERCONNECTION.
 WHERE MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT IN
 ACCORDANCE WITH SECTION R314.3, THE ALARM DEVICES SHALL
 BE INTERCONNECTED IN SUCH A MANNER THAT THE ACTUATION
 OF ONE ALARM WILL ACTIVATE ALL OF THE ALARMS IN THE
 INDIVIDUAL DWELLING UNIT. PHYSICAL INTERCONNECTION OF
 SMOKE ALARMS SHALL NOT BE REQUIRED WHERE LISTED
 WIRELESS ALARMS ARE INSTALLED AND ALL ALARMS SOUND UPON
 ACTIVATION OF ONE ALARM.
  
 4. FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER
 PROTECTION. INCLUDE IN ELECTRICAL NOTES:
  
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 16:11 Rev Time 0.00
Received By cthroop Date 2020-11-30 Time 16:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 16:13 Rev Time 0.00
Received By cthroop Date 2020-11-30 Time 16:13 Sent To  
Notes
2020-11-30 16:15:03PLAN REVIEW / FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: N/A
  
 NO FUEL GAS REVIEW PERFORMED AT THIS TIME.
  
 1. SEPARATE GAS PERMIT REQUIRED
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS PIPING AND
 GAS APPLIANCE INSTALLATIONS.
 PROVIDE A COMPLETE SET OF PLANS AND PRODUCT SUBMITTALS.
 INCLUDE A GAS RISER DRAWING, COMBUSTION AIR
 CALCULATIONS AND VENTING DIAGRAMS.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-09 Cont ID  
Sent By lmarchan Date 2020-12-09 Time 14:48 Rev Time 0.00
Received By lmarchan Date 2020-12-04 Time 15:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-02 Cont ID  
Sent By cthroop Date 2020-12-02 Time 09:47 Rev Time 0.00
Received By cthroop Date 2020-11-16 Time 09:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-12-11 Cont ID  
Sent By ccarvaja Date 2020-12-11 Time 12:06 Rev Time 0.00
Received By ccarvaja Date 2020-12-09 Time 14:48 Sent To  
Notes
2020-12-11 12:07:5012/11/20 PER PBC IMPACT FEES OFFICE - NO FEES ARE DUE.
 PLANS STAMPED. CC
2020-12-09 14:48:2312/9/20 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 15:30 Rev Time 0.00
Received By cthroop Date 2020-11-30 Time 15:30 Sent To  
Notes
2020-11-30 15:30:39PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By hmoser Date 2020-12-07 Time 13:20 Rev Time 0.00
Received By hmoser Date 2020-12-07 Time 11:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 15:39 Rev Time 0.00
Received By cthroop Date 2020-11-30 Time 14:11 Sent To  
Notes
2020-11-30 15:48:33PLAN REVIEW / MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE TIE DOWN DETAIL FOR CU-4.
  
 PROVIDE ENGINEERING FOR INSTALLATION OF THE CONDENSER
 PAD AND MOUNTING OF THE CONDENSER- SECTIONS
 M1305.1.4.1, M1307.2 AND M1401.4 FBC RES.
  
 M1401.4EXTERIOR INSTALLATIONS.
 EQUIPMENT AND APPLIANCES INSTALLED OUTDOORS SHALL BE
 LISTED AND LABELED FOR OUTDOOR INSTALLATION. SUPPORTS
 AND FOUNDATIONS SHALL PREVENT EXCESSIVE VIBRATION,
 SETTLEMENT OR MOVEMENT OF THE EQUIPMENT. SUPPORTS AND
 FOUNDATIONS SHALL BE IN ACCORDANCE WITH SECTION
 M1305.1.4.1.
  
 2. PROVIDE SERVICE OUTLET FOR CU-4.
  
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 3. PROVIDE DETAIL FOR AH-4 CONDENSATE DISPOSAL.
  
 M1411.3 CONDENSATE DISPOSAL.
 CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE
 CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE
 OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM
 HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT
 LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A
 NUISANCE.
  
 4. PROVIDE DETAIL FOR BATHROOM EXHAUST FANS.
  
 M1501.1OUTDOOR DISCHARGE.
 THE AIR REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM
 SHALL BE DISCHARGED TO THE OUTDOORS IN ACCORDANCE WITH
 SECTION M1506.3. AIR SHALL NOT BE EXHAUSTED INTO AN
 ATTIC, SOFFIT, RIDGE VENT OR CRAWL SPACE.
  
 5. PROVIDE LOCKING FREON PORTS.
  
 M1411.8 LOCKING ACCESS PORT CAPS.
 REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL
 BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR
 SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By cthroop Date 2020-12-07 Time 13:56 Rev Time 0.00
Received By cthroop Date 2020-12-07 Time 06:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-02 Cont ID  
Sent By cthroop Date 2020-12-02 Time 09:40 Rev Time 0.00
Received By cthroop Date 2020-11-30 Time 14:11 Sent To  
Notes
2020-11-30 16:29:28PLAN REVIEW / PLUMBING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SHOWER PAN DETAIL.
  
 P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1
 WHERE A SHOWER RECEPTOR HAS A FINISHED CURB THRESHOLD,
 IT SHALL BE NOT LESS THAN 1 INCH (25 MM) BELOW THE
 SIDES AND BACK OF THE RECEPTOR. THE CURB SHALL BE NOT
 LESS THAN 2 INCHES (51 MM) AND NOT MORE THAN 9 INCHES
 (229 MM) DEEP WHEN MEASURED FROM THE TOP OF THE CURB TO
 THE TOP OF THE DRAIN. THE FINISHED FLOOR SHALL SLOPE
 UNIFORMLY TOWARD THE DRAIN NOT LESS THAN 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) NOR
 MORE THAN 1/2 UNIT VERTICAL PER 12 UNITS HORIZONTAL
 (4-PERCENT SLOPE) AND FLOOR DRAINS SHALL BE FLANGED TO
 PROVIDE A WATER-TIGHT JOINT IN THE FLOOR.
 P2709.3 SHOWER PAN LINING INSTALLATION.
 LINING MATERIALS SHALL BE SLOPED ONE FOURTH UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) TO
 WEEP HOLES IN THE SUBDRAIN BY MEANS OF A SMOOTH,
 SOLIDLY FORMED SUBBASE, SHALL BE PROPERLY RECESSED AND
 FASTENED TO APPROVED BACKING SO AS NOT TO OCCUPY THE
 SPACE REQUIRED FOR THE WALL COVERING, AND SHALL NOT BE
 NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH
 (25.4 MM) ABOVE THE FINISHED THRESHOLD.
  
 P2708.4SHOWER CONTROL VALVES. INDIVIDUAL SHOWER AND
 TUB/ SHOWER COMBINATION VALVES SHALL BE EQUIPPED WITH
 CONTROL VALVES OF THE PRESSURE-BALANCE,
 THERMOSTATIC-MIXING OR COMBINATION
 PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A
 HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME
 A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET
 TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN
 120?F (49?C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 USED FOR COMPLIANCE WITH THIS SECTION.
  
 2. PROVIDE WATER HAMMER DETAIL. IDENTIFY LOCATION ON
 PLAN.
  
 P2903.5WATER HAMMER.
  
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010.
  
 3. P2708.4SHOWER CONTROL VALVES.
  
 INDIVIDUAL SHOWER AND TUB/ SHOWER COMBINATION VALVES
 SHALL BE EQUIPPED WITH CONTROL VALVES OF THE
 PRESSURE-BALANCE, THERMOSTATIC-MIXING OR COMBINATION
 PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A
 HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME
 A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET
 TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN
 120?F (49?C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 USED FOR COMPLIANCE WITH THIS SECTION.
  
  
  
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 15:03 Rev Time 0.00
Received By cthroop Date 2020-11-30 Time 09:16 Sent To  
Notes
2020-11-30 15:04:26PROVISO: A SEPERATE ROOFING PERMIT IS REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By cthroop Date 2020-12-07 Time 13:35 Rev Time 0.00
Received By cthroop Date 2020-12-07 Time 06:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 14:44 Rev Time 0.00
Received By cthroop Date 2020-11-30 Time 09:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-12-09 Cont ID  
Sent By rthermid Date 2020-12-09 Time   Rev Time 0.00
Received By rthermid Date 2020-12-09 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2020-12-08 Time   Rev Time 0.00
Received By   Date 2020-12-08 Time   Sent To I
Notes
2020-12-08 09:30:13ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 12/8/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A SURVEY OF THE PROPERTY SHOWING ALL
 SETBACKS TO ALL PROPERTY LINES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By rthermid Date 2020-12-01 Time   Rev Time  
Received By rthermid Date 2020-12-01 Time   Sent To I
Notes
2020-12-01 14:48:41ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 12/1/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ADDRESS BUILDING AND IMPACT FEE COMMENTS.
 2. PLEASE PROVIDE A SURVEY OF THE PROPERTY SHOWING THE
 SETBACKS OF ALL PROPOSED IMPROVEMENTS TO THE PROPERTY
 LINES.
 3.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved