| 2020-12-21 06:24:52 | 2ND REVIEW FBC-2017 GAS |
| | PERMIT-20110604 |
| | 12/21/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC FG SEC. 409.4, FBC |
| | FG. SEC. G2420.4. |
| | 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FG |
| | SECS. 402.4.1, 402.4.2. OR 2017 FBC FG RES SECS. |
| | G2413.4.1, G2413.4.2. |
| | 3) SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL.FBC |
| | FG SEC.305.1, FBC-RES. SEC.G2408.1. |
| | 4) THE COPY OF TABLE 402.4(20) IS FROM AN OUTDATED FUEL |
| | GAS CODE. THE FUEL GAS CODE IN EFFECT IS THE 2017 FBC |
| | FG. SUBMIT THE CORRECT SIZING TABLES. WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1. |
| | 5) THE SITE PLAN SHOWS A GAS GRILL. THE PIPE SIZE OF |
| | EACH SECTION OF GAS PIPING SHALL BE DETERMINED USING |
| | THE LONGEST LENGTH OF PIPING FROM THE POINT OF DELIVERY |
| | TO THE MOST REMOTE OUTLET AND THE LOAD ON THE SECTION. |
| | SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER) TO THE MOST REMOTE OUTLET IN THE BUILDING AND / |
| | OR SYSTEM PER THE 2017 FBC-FUEL GAS SEC.402.4.1, |
| | 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, |
| | G2413.4.2.2017 FBC-FUEL GAS SEC. 402.4.1. |
| | 6) A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS |
| | TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE |
| | MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD, |
| | 2017 FBC FG SEC.G2408.1. |
| | 7) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| | 2017 FBC FUEL GAS SECS. 401.4, 401.8, 402.1, 402.2, |
| | 402.3 OR 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, |
| | G2413.1, G2413.2, G2413.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |