| Plan Review Stops For Permit 20110518 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-02-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-02-05 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-02-05 |
Time |
10:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-19 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-19 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2021-01-19 13:45:06 | SFR DETACHED GARAGE/LIVING UNIT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) FLOOR/CEILING SYSTEM HAS BEEN REVISED. PLEASE SHOW | | | THE FIRE SEPARATION FROM THE GARAGE AND THE LIVING | | | SPACE ABOVE TO COMPLY WITH FBC R302.6 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-12-07 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-07 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2020-12-07 15:12:17 | SFR DETACHED GARAGE/LIVING UNIT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE REQUIRED FLOOD VENT SIZES AND | | | LOCATIONS TO COMPLY WITH FBC R322.2.2 ( THE DESIGN | | | FLOOD ELEVATION IS 8.00 NAVD - CITY ORDINANCE REQUIRES | | | 2 FOOT ABOVE THE BASE FLOOD ELEVATION) | | | 2) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE STANDING SEAM METAL PANEL | | | ROOFING SYSTEM - REVIEWED AND MARKED APPROVED BY THE | | | BUILDING DESIGNER OF RECORD. | | | 3) ON THE ROOF FRAMING PLAN - PLEASE SHOW THE LOCATION | | | OF THE STRAPPING PER THE CONNECTOR SCHEDULE SHOWN ON | | | THE ROOF FRAMING PLAN. | | | 4) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT FROM | | | AN ARCHITECT OR ENGINEER. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-01-11 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-01-11 |
Time |
14:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-12-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-12-09 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-12-08 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2020-12-09 08:18:10 | PLAN REVIEW / ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2014 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: VALUE HAS BEEN INCREASED BASED ON THE ICC | | | BUILDING VALUATION TABLES AS FOLLOWS: | | | NEW CONDITIONED SPACE - 709 SQ/FT @ $123.68 PER SQ/FT = | | | $87,689 | | | NEW STORAGE (GARAGE) - 709 SQ/FT @ $62.20 PER SQ/FT = | | | $44,100 | | | NEW UTILITY (COVERED PATIO - 400 SQ/FT AND BREEZEWAY - | | | 70 SQ/FT) - 470 SQ/FT @ $48.79 PER SQ/FT = $22,931 | | | TOTAL VALUE = $154,720 | | | | | | 1. PROVIDE GFCI OUTLET AT COVERED PATIO. | | | PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE OUTLET | | | FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING UNIT. NEC | | | 210.52(E)(3); FBC RE E3901.7 | | | | | | 2.PROVIDE OUTLETS AT WET BAR AREA. | | | E3901.4.1 WALL COUNTERTOP SPACE. | | | A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL | | | COUNTERTOP SPACE 12 INCHES (305 MM) OR WIDER. | | | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT | | | ALONG THE WALL LINE IS MORE THAN 24 INCHES (610 MM), | | | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT | | | SPACE. [210.52(C)(1)] | | | | | | 3. PROVIDE GFCI OUTLET AT BATHROOM LAV'S. | | | E3901.6 BATHROOM. | | | AT LEAST ONE WALL RECEPTACLE OUTLET SHALL BE INSTALLED | | | IN BATHROOMS AND SUCH OUTLET SHALL BE LOCATED WITHIN 36 | | | INCHES (914 MM) OF THE OUTSIDE EDGE OF EACH LAVATORY | | | BASIN. | | | | | | 4. SMOKE ALARM REQUIRED AT EACH LEVEL. | | | PROVIDE SMOKE ALARM ON EACH STORY OF THE DWELLING. FBC | | | R R314.3 | | | | | | 5. OUTLET SPACING IN LIVING AREA. | | | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT | | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL | | | SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. | | | PROVIDE CORRECTION. NEC 210.52; FBC RE E3901.2.1 | | | | | | 6. PROVIDE OUTLETS FOR MINI FRIDGE AND MICROWAVE. | | | E3901.3 SMALL APPLIANCE RECEPTACLES. | | | IN THE KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR | | | SIMILAR AREA OF A DWELLING UNIT, THE TWO OR MORE | | | 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY | | | SECTION E3703.2, SHALL SERVE ALL WALL AND FLOOR | | | RECEPTACLE OUTLETS COVERED BY SECTIONS E3901.2 AND | | | E3901.4 AND THOSE RECEPTACLE OUTLETS PROVIDED FOR | | | REFRIGERATION APPLIANCES. [210.52(B)(1)] | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
P |
Date |
2020-12-09 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-12-09 |
Time |
06:49 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-12-09 |
Time |
06:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2021-01-11 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-01-11 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-01-11 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2021-01-11 14:47:24 | 01/11/21 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-11-30 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-11-30 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-11-30 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2020-11-30 15:38:11 | 11/30/20 1ST GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. SUBMIT A HOUSE PLAN SHOWING THE LOCATION OF THE | | | TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF | | | ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER | | | HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY | | | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE | | | HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO | | | THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | 2. SUBMIT MANUFACTURER?S SPECIFICATION | | | SHEETS/INSTALLATION MANUAL FOR TANKLESS GAS EQUIPMENT | | | TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. | | | | | | 3. ON SHEET P1.01 IT SHOWS TWO TANKLESS IN SERIES BUT | | | ON ISOMETRIC THEY ARE 120? APART, PLEASE SHOW DETAIL | | | WITH ONLY ONE UNIT PER THE WPB AMENDMENTS TO FBC | | | SEC.107.2.1. | | | | | | 4. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF | | | EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. | | | | | | 5. GAS UNITS REQUIRE CONDENSATE AND THEY NEED TO BE 1' | | | AWAY FROM STRUCTURE PER THE 2017 FBC SEC R318.5. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-02-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-02-05 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-22 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-01-21 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-01-21 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-01-08 |
Time |
18:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-12-29 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-12-29 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-11-23 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2021-02-03 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-02-03 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-01-20 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2021-01-25 15:10:55 | RECEIPT - MU-2021-002911 - $22.46 - PAID | | 2021-01-20 14:48:51 | 1/20/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-12-07 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-07 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2020-12-07 15:22:55 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2020-12-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-01 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-01 |
Time |
17:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
P |
Date |
2021-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-19 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-19 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2021-01-19 13:48:35 | DETACHED GARAGE | | | AE 6 | | | FLOOD VENTS PROPOSED |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2020-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-12-07 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-07 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2020-12-07 15:21:10 | NEW DETACHED GARAGE WITH UPPER LEVEL LIVING SPACE. | | | AE 6 | | | GARAGE FLOOR BELOW THE DESIGN FLOOD ELEVATION OF 8.00 | | | NAVD | | | FLOOD VENTS ARE REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-01-11 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-01-11 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-01-11 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2021-01-11 14:24:33 | 01/11/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2020-11-30 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-11-30 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-11-30 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2020-11-30 15:42:13 | 11/30/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2021-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-19 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-19 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-12-07 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-07 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2020-12-07 15:22:03 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-02-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-02-05 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-02-05 |
Time |
10:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-19 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-19 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-12-07 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-07 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2020-12-07 15:18:30 | THE STRUCTURAL DRAWINGS = SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC | | | PLAN REVIEW. DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | | DIGITAL | | | SIGNATURE - YOU CAN SUBMIT THE ORIGINAL SIGNED AND | | | SEALED DRAWINGS/DOCUMENTS TO THE BUILDING DIVISION AT | | | CITY HALL. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-01-21 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2021-01-21 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2021-01-21 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-12-28 |
|
|
Cont ID |
|
| Sent By |
kalexand |
Date |
2020-12-28 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-12-28 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2020-12-28 14:08:14 | 12/28/20- FAILED. WHAT IS THE FRONT SETBACK FOR THE | | | GARAGE ADDITION 5'1" OR 25'. | | | | | | ANGELLA VANN | | | [email protected] | | | 561-822-1441 |
|
|