| 2020-12-03 14:47:30 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110399 |
| | 12/3/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 201 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | PLEASE NOTE THE PLUMBING REVIEW OF THE PROPOSED PROJECT |
| | DID NOT INCLUDE A REVIEW OF THE PLUMBING SYSTEMS, |
| | FIXTURES, EQUIPMENT, DEVICES ETC. INSTALLED INSIDE THE |
| | STERIS MOBILE SPD UNIT. AT THE TIME OF THIS REVIEW IT |
| | WAS NOT DETERMINED IF THE WPB BUILDING DEPT. WILL BE |
| | THE AGENCY RESPONSIBLE TO PERFORM PLAN REVIEWS AND |
| | INSPECTIONS OF THE UNIT. |
| | |
| | 1) PROVIDE DOCUMENTATION TO VERIFY THE STERIS MOBILE |
| | SPD UNIT IS A FL. STATE APPROVED MANUFACTURED BUILDING |
| | PER SECTION 107.3 (1) WPB AMENDMENTS TO THE FBC-17. |
| | |
| | 2) REFER TO SECTIONS 449.1.1 & 499.3.3 FBC B: PROVIDE |
| | DOCUMENTATION TO VERIFY THE MOBILE UNIT HAS BEEN |
| | APPROVED FOR USE AT THE HOSPITAL BY AHCA- AGENCY FOR |
| | HEALTH CARE ADMINISTRATION; AND HAS BE DESIGNED AND |
| | CONSTRUCTED IN ACCORDANCE WITH THE APPLICABLE |
| | REQUIREMENTS OF THE FBC-17, THE GUIDELINES FOR DESIGN |
| | AND CONSTRUCTION OF HOSPITALS AND OUTPATIENT |
| | FACILITIES, PART 3 OUTPATIENT FACILITIES, CHAPTER 3.13 |
| | SPECIFIC REQUIREMENTS FOR MOBILE, TRANSPORTABLE, AND |
| | RELOCATABLE UNITS. |
| | |
| | 3) SHEET P3.0: PROVIDE WATER SERVICE PIPE AND WATER |
| | DISTRIBUTION PIPE SPECIFICATIONS- SECTIONS 605.3 & |
| | 605.4 FBC P. |
| | |
| | 4) P3.0: PROVIDE SANITARY SEWER PIPE AND SANITARY |
| | DRAINAGE PIPE SPECIFICATIONS- SECTION 702 FBC P. REFER |
| | TO SECTION 603.2 FOR WATER SERVICE AND SERVICE PIPE |
| | MATERIALS IN THE SAME TRENCH AND VERIFY COMPLIANCE. |
| | |
| | 5) P3.0: PROVIDE THE EFFICIENCY RATINGS OF THE WATER |
| | HEATERS IN THE SCHEDULE- TABLE 404.2 FBC EC. |
| | |
| | 6) PROVIDE HOT WATER PIPE INSULATIONS SPECIFICATIONS- |
| | SECTION 607.5 FBC P. |
| | |
| | 7) P3.2: REFER TO SECTION 712.3.1 FBC P AND VERIFY THE |
| | EXISTING SEWAGE EJECTOR HAS LARGE ENOUGH CAPACITY AND |
| | HEAD TO EJECT THE INCREASED SEWER LOAD. |
| | |
| | 8) P3.1 & P3.2: REFER TO PAGE 50 OF THE STERIS MOBILE |
| | SPD GUIDE. THE GUIDE RECOMMENDS INSTALLATION OF A P |
| | TRAP ON THE SEWER LINE TO MINIMIZE POTENTIAL ODORS. |
| | |
| | 9) P3.1 & P3.2: INDICATE WHICH EQUIPMENT SHOWN ON PAGE |
| | 8 OF THE MOBILE MANUAL IS DISCHARGING WASTE AND |
| | CONDENSATION. PLEASE NOTE THAT AN APPROVED DILUTION OR |
| | NEUTRALIZING DEVICE SHALL BE REQUIRED FOR THE SANITARY |
| | AND CONDENSATION DRAIN SYSTEMS IF CORROSIVE LIQUIDS, |
| | SPENT ACIDS OR OTHER HARMFUL CHEMICALS THAT DESTROY OR |
| | INJURE A DRAIN, SEWER, SOIL OR WASTE PIPE, OR CREATE |
| | NOXIOUS OR TOXIC FUMES OR INTERFERE WITH SEWAGE |
| | TREATMENT PROCESSES ARE DRAINING FROM FIXTURES, |
| | APPLIANCE, OR EQUIPMENT INSIDE THE MOBILE UNIT. AT THIS |
| | TIME THERE HAS NOT BEEN A REVIEW OF THE PLUMBING |
| | SYSTEMS AND PROCESSES THAT WILL OCCUR IN THE UNIT. SUCH |
| | DEVICES SHALL BE AUTOMATICALLY PROVIDED WITH A |
| | SUFFICIENT SUPPLY OF DILUTING WATER OR NEUTRALIZING |
| | MEDIUM SO AS TO MAKE THE CONTENTS NON-INJURIOUS BEFORE |
| | DISCHARGE INTO THE DRAINAGE SYSTEM. THE NATURE OF THE |
| | CORROSIVE OR HARMFUL WASTE AND THE METHOD OF ITS |
| | TREATMENT OR DILUTION SHALL BE APPROVED PRIOR TO |
| | INSTALLATION. |
| | |
| | 10) P3.2: IT APPEARS THAT PUMPS WILL BE REQUIRED FOR |
| | THE DRAINAGE FROM THE WATER HEATER AND WATER SOFTENER |
| | TO DISCHARGE INTO THE EXISTING FLOOR DRAIN- SECTION |
| | 314.1 FBC P. PLEASE REVISE THE DETAILS. |
| | |
| | 11) P3.1 & P3.2: SHOW THE LOCATIONS OF THE REQUIRED |
| | CLEANOUTS FOR THE SEWER PIPE- SECTIONS 708.1.3 & |
| | 708.1.4 FBC P. |
| | |
| | 12) P3.0: PROVIDE EQUIPMENT SCHEDULES FOR THE |
| | RECIRCULATION PUMP AND MIXING VALVE- SECTION 607.1.2 |
| | FBC P. |
| | |
| | 13) P3.0 & P3.2: INDICATE HOW THE WATER FILTERING |
| | SYSTEM WILL BE PROTECTED AGAINST CONTAMINATION- SECTION |
| | 608.3 FBC P. |
| | |
| | 14) P3.2, BACKFLOW PREVENTER: A FLORIDA LICENSED |
| | PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| | INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND |
| | SECTION 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE WPB BUILDING |
| | DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL |
| | OPERATIONS DEPT. AT 561-822-2210 FOR FURTHER |
| | INFORMATION. |
| | |
| | 15) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| | 105.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |