Plan Review Details - Permit 20110398
Plan Review Stops For Permit 20110398
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-04-09 Cont ID  
Sent By cpuell Date 2021-04-09 Time 12:25 Rev Time 0.00
Received By cpuell Date 2021-04-09 Time 12:25 Sent To  
Notes
2021-04-09 12:26:22NO SUITE IDENTIFIED BUT ADDED A DESCRIPTION OF THE
 LOCATION OF THE WORK

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-02-10 Cont ID  
Sent By cpuell Date 2021-02-10 Time 14:36 Rev Time 0.00
Received By cpuell Date 2021-02-10 Time 14:36 Sent To  
Notes
2021-02-10 14:38:38PLEASE IDENTIFY THE LOCATION OF THE WORK TO DO DONE,
 WILL IT BE THE WHOLE BUILDING, A CERTAIN FLOOR OR
 SUITE. PLEASE CONTACT [email protected] WITH RESPONCES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-04-12 Cont ID  
Sent By jwitmer Date 2021-04-12 Time 14:31 Rev Time 0.00
Received By jwitmer Date 2021-04-12 Time 14:28 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By jwitmer Date 2020-11-25 Time 10:19 Rev Time 0.00
Received By jwitmer Date 2020-11-25 Time 09:47 Sent To  
Notes
2020-11-25 10:19:18COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2021-05-27 Time 09:15 Rev Time 0.00
Received By jwitmer Date 2021-05-27 Time 09:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-12 Cont ID  
Sent By jwitmer Date 2021-04-12 Time 15:43 Rev Time 0.00
Received By jwitmer Date 2021-04-12 Time 14:27 Sent To  
Notes
2021-04-12 15:39:02WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110398
 ADD: 1309 N. FLAGLER DR/ AKA 1301 N. FLAGLER DR.
 CONT: WESTBROOKE CORPORATION
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 25TH/ 2020
 ACTION: DENIED
  
 1) COMPLIED
  
 2)COMPLIED/ NOT APPLICABLE.
  
 3)2ND REQUEST. SHEET A-3.1 SHOWS A NEW TRANSFER TYPE
 STAFF SHOWER T3035. THE ENLARGED DETAIL DOES NOT GIVE
 ANY SHOWER DETAILS FOUND ON SHEET A-0.2. PLEASE SHOW
 DETAILS THAT WILL COMPLY WITH TRANSFER TYPE ACCESSIBLE
 SHOWERS IN COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE
 SECTION:
  
 608.2.1 TRANSFER SHOWERS ARE AN ABSOLUTE 36 X 36 INCHES
 AND REQUIRE A CLEAR FLOOR SPACE 36 INCHES BY 48 INCHES
 LONG MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
  
 608.3.1 GRAB BARS SHALL BE CONFIGURED AS SHOWN IN
 FIGURE 608.3.1.
  
 608.5.1 THE CONTROL VALVES FOR A TRANSFER TYPE SHOWER
 ON THE SIDE WALL OPPOSITE SIDE OF THE SEAT AT 38 INCHES
 MINIMUM AND 48 INCHES MAXIMUM ABOVE THE SHOWER FLOOR
 AND LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM FROM
 THE CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING.
  
 609.4 POSITION OF GRAB BARS FOR HEIGHT. ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 610.3. TRANSFER TYPE SHOWERS SHOWER COMPARTMENT SEAT
 SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT
 WITHIN 3 INCHES OF THE COMPARTMENT ENTRY.
 THERE WAS NO ATTACHMENT FOR A PREFABRICATED ADA SHOWER
 TECHNICAL SHEET THIS REVIEW CYCLE.
  
 4) COMPLIED. MIAMI-DADE NOA 15-0209.02 FIRESTONE ULTRA
 PLY TPO SA SINGLE PLY ROOF SYSTEM, 96 PAGE REPORT.
  
 5). SHEET A-4.1 ROOF CURB DETAIL FOR ROOF TOP FAN.
 SHEET S-2.00 DETAIL # 1 SHOWS:
  
 5A) 2ND REQUEST. 2ND REQUEST, NO CURB WAS SUBMITTED
 THIS REVIEW. NEW PREFABRICATED NOA RATED METAL CURB.
 PLEASE PROVIDE COMPLIANCE WITH 1609.6.4.4.1 COMPONENTS
 & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOF TOP CURB.
  
 5B) SEMI-COMPLIED NOA 17-1221.35 BUT NONE OF THE
 DETAILS WERE IDENTIFIED FOR THIS APPLICATION AND
 ANCHORING.
  
 5C) COMPLIED.
  
 6) N/A/ NOT APPLICABLE.
  
 7)COMPLIED.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By jwitmer Date 2020-11-25 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2020-11-25 Time 09:46 Sent To  
Notes
2020-11-25 12:30:17 
 WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110398
 ADD: 1309 N. FLAGLER DR/ AKA 1301 N. FLAGLER DR.
 CONT: WESTBROOKE CORPORATION
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 25TH/ 2020
 ACTION: DENIED
  
 1) BOTH THE PERMIT APPLICATION AND THE COVERSHEET OF
 THE PLANS HAVE THE ADDRESS OF 1309 N. FLAGLER DR. ON
 THE SUBMITTED DOCUMENTS. PLEASE NOTE THAT ADDRESS
 BELONGS TO THE VICTOR FARRIS BUILDING. THE ADDRESS FOR
 THE GOOD SAMARITAN MEDICAL CENTER IS 1301 N FLAGLER DR.
 PLEASE CORRECT THE PERMIT APPLICATION AND PLANS FOR
 ADDRESSING. PLEASE ALSO NOTE THE GIVEN PCN ON THE
 PERMIT APPLICATION IS NOT FOUND IN THE COUNTY PROPERTY
 APPRAISERS WEB SITE.
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) SHEET A-0.2:
 2A) THE PLANS INDICATE THE GRAB BARS BEING MEASURED TO
 THE CENTERLINE, NOT THE TOP OF THE GRASPING SURFACE.
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
 2B) THERE ARE NO ACCESSIBLE DETAILS FOR DRINKING
 FOUNTAINS. 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
  
 PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. CODE.
 SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
 3) SHEET A-3.1 SHOWS A NEW TRANSFER TYPE STAFF SHOWER
 T3035. THE ENLARGED DETAIL DOES NOT GIVE ANY SHOWER
 DETAILS FOUND ON SHEET A-0.2. PLEASE SHOW DETAILS THAT
 WILL COMPLY WITH TRANSFER TYPE ACCESSIBLE SHOWERS IN
 COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE SECTION
 608.2.1 ,608.3.1, 608.5.1, 609.4 & 610.3.2
 4) SHEET A4.1 INDICATES ROOF PATCH DETAIL, DETAIL # 3.
 ROOF REPAIR PATCH TO BE EPDM ROOF. PLEASE PROVIDE
 COMPLIANCE WITH 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES.
 5) SHEET A-4.1 ROOF CURB DETAIL FOR ROOF TOP FAN. SHEET
 S-2.00 DETAIL # 1 SHOWS:
 5A) NEW PREFABRICATED NOA RATED METAL CURB. PLEASE
 PROVIDE COMPLIANCE WITH 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOF TOP CURB.
 5B) NEW ROOF TOP FAN WITH THE COMMENT ATTACH UNIT TO
 CURB PER UNITS MANUFACTURERS RECOMMENDATIONS. SUBMITTED
 NOA 17-1221.35 BUT NONE OF THE DETAILS WERE IDENTIFIED
 FOR THIS APPLICATION AND ANCHORING.
 5C) DESIGN WIND PRESSURES/ SERVICE ARE GIVEN BUT THERE
 IS NO WIND DESIGN DATA FOR THESE PRESSURES. 2017 FBC-B
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 6) SHEET A-7.3:
 6A) NITROUS OXIDE STORAGE ROOM T3006 SHOWS A 1-HOUR
 FIRE BARRIER WALL, NO DOOR IDENTIFICATION NOR RATING.
 SHOW COMPLIANCE WITH 2017 FBC-B TABLE 716.5.
  
 6B) NITROGEN STORAGE ROOM T3007 SHOWS A 1-HOUR FIRE
 BARRIER WALL, NO DOOR IDENTIFICATION NOR RATING. SHOW
 COMPLIANCE WITH 2017 FBC-B TABLE 716.5.
  
 7) WALL FINISHES SHEET A-11.1 WALL FINISHES ARE SHOWN
 W4 INDICATES THE USE OF CERAMIC TILE, W5 SHOWS THE USE
 OF EPOXY PAINT. I COULD NOT FIND WHERE THESE PRODUCT
 WERE TO BE USED IN THE ROOMS. PLEASE SEE THE CONCERN WE
 HAVE.
 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION. IN
 RESTROOMS EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH
 HARD, NON-ABSORBENT SURFACE.
  
 7A) WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 7B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 7C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-10 Cont ID  
Sent By jleahy Date 2021-04-10 Time 10:01 Rev Time 0.00
Received By jleahy Date 2021-04-10 Time 08:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-12-17 Cont ID  
Sent By jleahy Date 2020-12-17 Time 11:07 Rev Time 0.00
Received By jleahy Date 2020-12-17 Time 08:28 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-04-21 Cont ID  
Sent By jleahy Date 2021-04-21 Time 16:37 Rev Time 0.00
Received By jleahy Date 2021-04-21 Time 16:34 Sent To  
Notes
2021-04-21 16:38:10VOICE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-05-27 Cont ID  
Sent By pleduc Date 2021-05-27 Time   Rev Time 0.00
Received By pleduc Date 2021-05-27 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-04-12 Cont ID  
Sent By pleduc Date 2021-04-12 Time   Rev Time 0.00
Received By pleduc Date 2021-04-12 Time 10:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-11-24 Cont ID  
Sent By pleduc Date 2020-11-24 Time   Rev Time 0.00
Received By pleduc Date 2020-11-24 Time 14:34 Sent To  
Notes
2020-11-24 14:38:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FP 1.0 - THIS DRAWING IS INDICATED AS NOT
 BEING UPLAODED PROPERLY AND DOES NOT SHOW UP.
  
 BE SURE TO INCLUDE THAT ANY FS WORK, INCLUDING DEMO,
 SHALL BE SUBMITTED UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS
  
 PLEASE REVIEW AND UPLOAD SO IT IS VIEWABLE.
  
  
  
 2) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF FIRE
 ALARM WORK, INCLUDING DEMO.
  
 PLEASE REVIEW AND PROVIDE INDICATIONS OF FA WORK,
 INCLUDING DEMO, UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-05-27 Time   Rev Time 0.00
Received By aoliver Date 2021-05-21 Time 10:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-22 Cont ID  
Sent By lmarchan Date 2021-04-22 Time 10:51 Rev Time 0.00
Received By lmarchan Date 2021-04-09 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-12-18 Time   Rev Time 0.00
Received By lmarchan Date 2020-11-19 Time 11:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-04-19 Cont ID  
Sent By medwards Date 2021-04-19 Time 13:59 Rev Time 0.00
Received By medwards Date 2021-04-19 Time 13:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-12-15 Cont ID  
Sent By medwards Date 2020-12-15 Time 16:57 Rev Time 0.00
Received By medwards Date 2020-12-15 Time 14:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-05-27 Cont ID  
Sent By ccole Date 2021-05-27 Time 13:52 Rev Time 0.00
Received By ccole Date 2021-05-27 Time 11:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-04-19 Cont ID  
Sent By ccole Date 2021-04-19 Time 18:35 Rev Time 0.00
Received By ccole Date 2021-04-19 Time 12:35 Sent To  
Notes
2021-04-19 18:36:072ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20110398
 4/19/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES.
  
 4) FAILED. P2.2: REFER TO SECTION 803.1 FBC P AND
 PROVIDE DILUTION OR NEUTRALIZING DEVICES FOR ANY
 CENTRAL STERILE WORKROOM AND STORAGE FIXTURES OR
 EQUIPMENT DISCHARGING CORROSIVE LIQUIDS, ACIDS OR
 CHEMICALS THAT COULD DAMAGE THE DRAINAGE SYSTEM OR
 CREATE NOXIOUS OR TOXIC FUMES. THE PLANS SHOW EYE WASH
 STATIONS WHICH ARE TYPICALLY REQUIRED FOR EXPOSURE TO
 CORROSIVE MATERIALS. THE ARCHITECT IS STATING IN HIS
 RESPONSE THAT ACCORDING TO THE MEDICAL EQUIPMENT
 SUPPLIER THE FIXTURES OR EQUIPMENT DO NOT DISCHARGE
 CORROSIVE LIQUIDS OR ACIDS OR DAMAGING CHEMICALS ETC.,
 HOWEVER EYE WASH STATIONS ARE BEING INSTALLED. PLEASE
 NOTE THAT SHEET EQ300 WHICH IS THE MEDICAL EQUIPMENT
 PLAN HAS NOT BEEN SUBMITTED. THE PLANS ALSO INDICATE
 INSTALLATION OF CHEMICAL RESISTANT PVDF PIPING FOR THE
 R0/DI SYSTEM. AT THIS TIME MORE INFORMATION AND
 EVIDENCE IS REQUIRED TO DETERMINE IF COMPLIANCE WITH
 SECTION 803.1 WILL APPLY.
 THE OSHA REQUIREMENTS FOR EMERGENCY EYEWASHES AND
 SHOWERS, FOUND AT 29 CFR 1910.151(C), SPECIFY THAT
 "WHERE THE EYES OR BODY OF ANY PERSON MAY BE EXPOSED TO
 INJURIOUS CORROSIVE MATERIALS, SUITABLE FACILITIES FOR
 QUICK DRENCHING OR FLUSHING OF THE EYES AND BODY SHALL
 BE PROVIDED WITHIN THE WORK AREA FOR IMMEDIATE
 EMERGENCY USE. AS THE STANDARD STATES, AN EYEWASH
 AND/OR SAFETY SHOWER WOULD BE REQUIRED WHERE AN
 EMPLOYEE'S EYES OR BODY COULD BE EXPOSED TO INJURIOUS
 CORROSIVE MATERIALS.
  
 7) FAILED. P2.2, P4.2: PROVIDE CENTRAL STERILE NP AND
 PW PIPING SPECIFICATIONS- SECTION 107.2.1 WPB. PLEASE
 PROVIDE NON-POTABLE SPECIFICATIONS AND SIGNAGE
 REQUIRMENTS ON THE PLAN:
 SECTION 608.9.2 DISTRIBUTION PIPE LABELING AND
 MARKING.NONPOTABLE DISTRIBUTION PIPING SHALL BE PURPLE
 IN COLOR AND SHALL BE EMBOSSED, OR INTEGRALLY STAMPED
 OR MARKED, WITH THE WORDS: 'CAUTION: NONPOTABLE WATER '
 DO NOT DRINK' OR THE PIPING SHALL BE INSTALLED WITH A
 PURPLE IDENTIFICATION TAPE OR WRAP. PIPE IDENTIFICATION
 SHALL INCLUDE THE CONTENTS OF THE PIPING SYSTEM AND AN
 ARROW INDICATING THE DIRECTION OF FLOW. HAZARDOUS
 PIPING SYSTEMS SHALL ALSO CONTAIN INFORMATION
 ADDRESSING THE NATURE OF THE HAZARD. PIPE
 IDENTIFICATION SHALL BE REPEATED AT INTERVALS NOT
 EXCEEDING 25 FEET (7620 MM) AND AT EACH POINT WHERE THE
 PIPING PASSES THROUGH A WALL, FLOOR OR ROOF. LETTERING
 SHALL BE READILY OBSERVABLE WITHIN THE ROOM OR SPACE
 WHERE THE PIPING IS LOCATED.
 608.9 IDENTIFICATION OF NONPOTABLE WATER SYSTEMS.
 WHERE NONPOTABLE WATER SYSTEMS ARE INSTALLED, THE
 PIPING CONVEYING THE NONPOTABLE WATER SHALL BE
 IDENTIFIED EITHER BY COLOR MARKING, METAL TAGS OR TAPE
 IN ACCORDANCE WITH SECTIONS 608.9.1 THROUGH 608.9.2.3.
  
 608.9.1SIGNAGE REQUIRED.
 NONPOTABLE WATER OUTLETS, SUCH AS HOSE CONNECTIONS,
 OPEN ENDED PIPES AND FAUCETS, SHALL BE IDENTIFIED WITH
 SIGNAGE THAT READS AS FOLLOWS: 'NONPOTABLE WATER IS
 UTILIZED FOR [APPLICATION NAME]. CAUTION: NONPOTABLE
 WATER ' DO NOT DRINK.' THE WORDS SHALL BE LEGIBLY AND
 INDELIBLY PRINTED ON A TAG OR SIGN CONSTRUCTED OF
 CORROSION-RESISTANT WATERPROOF MATERIAL OR SHALL BE
 INDELIBLY PRINTED ON THE FIXTURE. THE LETTERS OF THE
 WORDS SHALL BE NOT LESS THAN 0.5 INCH IN HEIGHT AND IN
 COLORS IN CONTRAST TO THE BACKGROUND ON WHICH THEY ARE
 APPLIED. IN ADDITION TO THE REQUIRED WORDAGE, THE
 PICTOGRAPH SHOWN IN FIGURE 608.9.1 SHALL APPEAR ON THE
 REQUIRED SIGNAGE.
  
 9) FAILED. A3.1: THE DOOR SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE OF THE SHOWER- SECTION 603.2.3 FBC
 ACC. SHEET A3.1A SHOWS THE DOOR SWINGING INTO THE CLEAR
 FLOOR SPACE OF THE SHOWER.
  
 11) FAILED. A0.2 & A3.1: PROVIDE DETAILS SHOWING SHOWER
 SEAT POSITIONING, LENGTHS, AND MOUNTING HEIGHTS-
 SECTION 608.4 & 610.3 FBC ACC. REFER TO SECTION AND
 FIGURE 610.3.2 L-SHAPED SEATS- PROVIDE A DIMENSIONED
 SEAT DETAIL ON THE PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-18 Cont ID  
Sent By ccole Date 2020-12-18 Time 18:10 Rev Time 0.00
Received By ccole Date 2020-12-18 Time 08:23 Sent To  
Notes
2020-12-18 18:11:12 
 1ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20110398
 12/18/20
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P0.1, P1.1, & P: PLEASE NOTE SEPARATE PERMIT
 APPLICATIONS AND PLAN SUBMITTALS ARE REQUIRED FOR
 INSTALLATION OF THE BACKFLOW PREVENTER AND THE MEDICAL
 GAS SYSTEM ALTERATIONS- SECTION 105.1 & 107.2.1 WPB.
  
 A) A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 B) A FL. LICENSED PLUMBER HOLDING A MEDICAL GAS PIPING
 INSTALLATION OBTAINED IN ACCORDANCE WITH FL. STATUTE
 489.1136 CERTIFICATE SHALL SUBMIT A SEPARATE PRIMARY
 APPLICATION AND COMPLETE PLANS FOR THE MED GAS SYSTEM
 ALTERATIONS.
  
 2) P2.2: NOTE-8- SHOW THE POINT OF CONNECTION FOR THE
 NEW 1? NPSCW AT STERILIZER TO THE EXISTING LINE-
 SECTION 107.2.1 WPB.
  
 3) P2.2: PLEASE PROVIDE AN ENLARGED TYPICAL INDIRECT
 WASTE DISCHARGE DETAIL FOR THE 3-COMPARTMENT SINKS IN
 THE SOILED WORKROOM, AND SCOPE ROOM; AND PROVIDE A
 TYPICAL INDIRECT WASTE DETAIL FOR ALL OTHER FLOOR SINKS
 LOCATED BELOW THE STERILIZER AND OTHER CENTRAL STERILE
 WORKROOM AND STORAGE FIXTURES AND EQUIPMENT- SECTION
 713.3 FBC P.
  
 4) P2.2: REFER TO SECTION 803.1 FBC P AND PROVIDE
 DILUTION OR NEUTRALIZING DEVICES FOR ANY CENTRAL
 STERILE WORKROOM AND STORAGE FIXTURES OR EQUIPMENT
 DISCHARGING CORROSIVE LIQUIDS, ACIDS OR CHEMICALS THAT
 COULD DAMAGE THE DRAINAGE SYSTEM OR CREATE NOXIOUS OR
 TOXIC FUMES.
  
 5) P2.2, P2.3, P4.1: PROVIDE TRAP PRIMERS FOR FLOOR
 DRAINS AND FLOOR SINKS WITH SEALS SUBJECT TO
 EVAPORATION- SECTION 1002.4.1 FBC P. SHOW THE LOCATIONS
 ON THE PIPING PLAN AND ISOMETRIC DRAWING, AND PROVIDE A
 DETAIL.
  
 6) P2.2: PLEASE INCLUDE THE FLOOR SINKS, FAUCETS,
 SPRAYERS, HOSES, VALVES, AND ALL OTHER PLUMBING
 FIXTURES AND DEVICES TO BE INSTALLED IN THE CENTRAL
 STERILE WORK AND STORAGE ROOMS- SECTION 107.2.1 WPB.
  
 7) P2.2, P4.2: PROVIDE CENTRAL STERILE NP AND PW PIPING
 SPECIFICATIONS- SECTION 107.2.1 WPB.
  
 8) P4.2: PROVIDE SYMBOLS TO SHOW THE WATER HAMMER
 ARRESTOR LOCATIONS- SECTION 604.9 FBC P.
  
 9) A3.1: THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE OF THE SHOWER- SECTION 603.2.3 FBC ACC.
  
 10) A0.2 & A3.1: PROVIDE DETAILS SHOWING SHOWER GRAB
 BAR POSITIONING, LENGTHS, AND MOUNTING HEIGHTS- SECTION
 608.3.1 & 609.1 FBC ACC.
  
 11) A0.2 & A3.1: PROVIDE DETAILS SHOWING SHOWER SEAT
 POSITIONING, LENGTHS, AND MOUNTING HEIGHTS- SECTION
 608.4 & 610.3 FBC ACC.
  
 12) A0.2 & A3.1: SHOW THE SHOWER CONTROL AND FAUCET
 LOCATIONS PER SECTION 608.5.1 FBC ACC.
  
 13) A0.2: SHOW THE TOILET ROOM GRAB HEIGHTS FROM THE
 FINISHED FLOORS TO THE TOP OF THE GRIPPING SURFACES-
 SECTION 609.4 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-27 Cont ID  
Sent By ccole Date 2021-05-27 Time 13:56 Rev Time 0.00
Received By ccole Date 2021-05-27 Time 13:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-21 Cont ID  
Sent By jleahy Date 2021-04-21 Time 16:38 Rev Time 0.00
Received By jleahy Date 2021-04-21 Time 16:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-15 Cont ID  
Sent By medwards Date 2020-12-15 Time 17:15 Rev Time 0.00
Received By medwards Date 2020-12-15 Time 17:14 Sent To  
Notes
2020-12-15 17:22:04THE ENGINEER KURT PENNER MUST HAVE HIS DIGITAL
 SIGNATURE 3RD PARTY VERIFIED. HE HAS BEEN TOLD SEVERAL
 TIMES.
 PLEASE CONTACT THE ENGINEER DENNIS HERGENRETHER AND LET
 HIM KNOW THAT WE CAN ACCEPT HIS SELF CERTIFICATION ONE
 TIME BUT THAT FROM THIS POINT FORWARD HE MUST HAVE A
 THIRD PARTY VERIFICATION.
  
 61G15?23.004 F.A.C.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS: (A) UNIQUE TO THE PERSON USING IT; (B) CAPABLE OF
 VERIFICATION; AS OF NOVEMBER 16, 2020 63 (C) UNDER THE
 SOLE CONTROL OF THE PERSON USING IT; AND, (D) LINKED TO
 A DOCUMENT IN SUCH A MANNER THAT THE DIGITAL SIGNATURE
 AND CORRESPONDINGLY THE DOCUMENT IS INVALIDATED IF ANY
 DATA IN THE DOCUMENT IS CHANGED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-04-22 Cont ID  
Sent By eschneid Date 2021-04-22 Time 09:25 Rev Time 0.50
Received By eschneid Date 2021-04-22 Time 08:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By eschneid Date 2020-12-07 Time 15:33 Rev Time 0.50
Received By eschneid Date 2020-12-07 Time 15:33 Sent To  
Notes
2020-12-07 15:34:49FAILED
  
 1) THE DEVELOPMENT REGULATIONS FOR THE GOOD SAMARITAN
 MEDICAL CENTER REQUIRE THAT ALL NEW ROOFTOP MECHANICAL
 EQUIPMENT BE SCREENED FROM VIEW OF THE PUBLIC. PROVIDE
 DRAWINGS TO VERIFY THAT THE NEW ROOFTOP EQUIPMENT
 (EXHAUST FANS, ETC) SHOWN ON SHEETS A4.1, S-200 ARE
 SCREENED FROM VIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]