Plan Review Details - Permit 20110397
Plan Review Stops For Permit 20110397
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-02-11 Cont ID  
Sent By jwitmer Date 2021-02-11 Time 10:42 Rev Time 0.00
Received By jwitmer Date 2021-02-11 Time 08:59 Sent To  
Notes
2021-02-11 10:36:24BUILDING PASSED
 BUILDING PROVISO:
 THE SUBMITTED ROOF PRODUCT APPROVAL NOA 15-1026.04
 HAS EXPIRED. ATHE TIME OF PERMIT APPLICATION 11/10/2020
 THE PRODUCT APPROVAL WAS STILL GOOD.TTHE PRODUCT
 APPROVAL EXPIRED ON 01/05/2021.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By jwitmer Date 2020-11-30 Time 15:57 Rev Time 0.00
Received By jwitmer Date 2020-11-30 Time 11:18 Sent To  
Notes
2020-11-30 11:19:33WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110397
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 30TH/ 2020
 ACTION: DENIED
  
 1) SHEET S-000 HEADING FOUNDATION INDICATES A SOILS
 REPORT BY ALTERRA ENGINEERING & TESTING, REPORT #
 12-197. THIS SOILS TEST REPORT WAS SUBMITTED AND PAGE 4
 OF 7 THERE WERE 3 PROVISIONAL PILE TYPE
 RECOMMENDATIONS. THEY WERE HELICAL PILE, CASED
 MICRO-PILES, & AUGER CAST PILE. SHEET S-000 UNDER THE
 HEADING OF FOUNDATION / PILES IT WOULD APPEAR THAT
 HELICAL PILE WILL BE INSTALLED. AT THE TIME OF THIS
 REVIEW THERE IS NO ADDITIONAL DOCUMENTATION THE ALTERRA
 WILL BE HIRED TO ENGAGE IN THE MONITORING OF THE
 INSTALLATION OF HELICAL PILE AND TO WHAT SERVICES
 ALTERRA WILL PERFORM. 2017 FBC-B 1810.3.1.5. HELICAL
 PILE.
  
 2) SINCE THE CHOICE OF HELICAL PILE HAS BEEN MADE THERE
 WILL BE ADDITIONAL INFORMATION REQUIRED TO THE SOILS
 REPORT AS TO THE REQUIRED PILE CAPACITY AND THE
 REQUIRED DEPTH, ASSUMPTION TO MEET THE REQUIRED TONNAGE
 FOR FUTURE 4 STORY MEDICAL BUILDING ADDITION. 2017
 FBC-B 1810.2. ANALYSIS.
  
 3) STRUCTURAL SHEETS SHOW VARIOUS DETAILS WHERE FIELD
 WIELDING IS GOING TO TAKE PLACE DURING THE STRUCTURAL
 PHASE OF THE WORK PLEASE SHOW COMPLIANCE WITH: WELDED
 OR BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-05 Cont ID  
Sent By jleahy Date 2021-03-05 Time 07:36 Rev Time 0.00
Received By jleahy Date 2021-03-05 Time 07:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-12-15 Cont ID  
Sent By jleahy Date 2020-12-15 Time 13:19 Rev Time 0.00
Received By jleahy Date 2020-12-15 Time 12:59 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-12-15 Cont ID  
Sent By jleahy Date 2020-12-15 Time 13:20 Rev Time 0.00
Received By jleahy Date 2020-12-15 Time 13:20 Sent To  
Notes
2020-12-15 13:21:16TELEPHONE/DATA, SECURITY, CATV, INMTERCOM, NURSE CALL,
 AND CLOCK SYSTEMS JLEAHY

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2020-11-19 Cont ID  
Sent By rrossano Date 2020-11-19 Time   Rev Time  
Received By rrossano Date 2020-11-19 Time   Sent To  
Notes
2020-11-19 23:52:03REVIEWED UNDER FORMAL ENGINEERING SUBMITTAL E20020019.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-02-12 Cont ID  
Sent By pleduc Date 2021-02-12 Time   Rev Time 0.00
Received By pleduc Date 2021-02-12 Time 11:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-12-02 Cont ID  
Sent By pleduc Date 2020-12-02 Time   Rev Time 0.00
Received By pleduc Date 2020-11-23 Time 13:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-03-10 Time   Rev Time 0.00
Received By lmarchan Date 2021-03-08 Time 07:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-03-05 Time   Rev Time 0.00
Received By ccarvaja Date 2021-02-10 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-12-17 Time   Rev Time 0.00
Received By lmarchan Date 2020-11-18 Time 16:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-12-23 Cont ID  
Sent By ccarvaja Date 2020-12-23 Time 07:47 Rev Time 0.00
Received By ccarvaja Date 2020-12-11 Time 17:34 Sent To  
Notes
2020-12-23 07:49:3412/23/20 RECEIPT MU 2020-049614 - UPLOADED - $26,500.96
 - PAID
  
  
2020-12-11 17:35:0812/11/20 IMPACT FEES QUESTIONNAIRE UPLOADED. PBC IMPACT
 FEES OFFICE HAS BEEN NOTIFIED. CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By jwitmer Date 2020-11-30 Time 11:24 Rev Time 0.00
Received By jwitmer Date 2020-11-30 Time 11:18 Sent To  
Notes
2020-11-30 11:24:28IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-02 Cont ID  
Sent By medwards Date 2021-03-02 Time 09:07 Rev Time 0.00
Received By medwards Date 2021-03-02 Time 07:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-15 Cont ID  
Sent By medwards Date 2020-12-15 Time 13:30 Rev Time 0.00
Received By medwards Date 2020-12-15 Time 08:58 Sent To  
Notes
2020-12-15 13:30:411ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110397
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS NEW ADDITION. FBC EC C403.2.1
  
 2) PLEASE PROVIDE A PROCEDURAL PROCESS DOCUMENT SHOWING
 THE PROCESS OF THE USE OF THIS SPACE. FBC 107.2.1
  
 3) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS. FBC M TABLE
 403.3.1.1
  
 4) PLEASE PROVIDE SPECS AS TO WHAT EF-1 AND EF-3 ARE
 EXHAUSTING AND CALCULATIONS AS TO THE CFM?S OF EACH
 EXHAUST FAN. ASHRAE 4.3.3
  
 5) PLEASE PROVIDE CALCULATIONS FOR TOTAL AIR CHANGES
 FOR EACH AREA. FBC M 407: ASHRAE-170 TABLE 7-1
  
 6) PLEASE SHOW PRESSURE RELATIONSHIP OF EACH SPACE TO
 ADJACENT AREAS. FBC M 407: ASHRAE 170 TABLE 7-1
  
 7) PLEASE SHOW THAT THE STEAMER MEETS SECTION 7.4.2 OF
 ASHRAE 170 FOR THE EXHAUST OF STEAM.
  
 8) PLEASE SHOW HOW THE AIR INTAKE FOR THE AHU MEETS
 RAIN ENTRAINMENT. FBC M 407: ASHRAE-170 6.2: ASHRAE
 62.1 5.5
  
 9) PLEASE SHOW ROOF ACCESS. FBC M 306.5
  
 10) PLEASE PROVIDE A COMPLETE LIST OF EQUIPMENT FOR
 THIS NEW ADDITION I.E. THE STEAMER FBC 107.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-03-10 Cont ID  
Sent By ccole Date 2021-03-10 Time 11:25 Rev Time 0.00
Received By ccole Date 2021-03-10 Time 09:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-03-05 Cont ID  
Sent By ccole Date 2021-03-05 Time 07:57 Rev Time 0.00
Received By ccole Date 2021-03-04 Time 15:32 Sent To  
Notes
2021-03-05 07:58:142ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20110397
 3/5/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 BASED ON THE RESUBMITTED PLANS AND NARRATIVBE RESPONSE,
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH NOTES IN CAP LETTERS ADDED FOR CLARIFICATION.
  
 1) FAILED. PLEASE PROVIDE SANITARY DRAINAGE AND WATER
 DISTRIBUTION ISOMETRIC DRAWINGS- SECTION 107.3.5.1.3
 WPB. SHEETS P2.0 & P6.0, CONFLICT WITH THE DRAWINGS:
 THE FLOOR DRAINS IN THE MECHANICAL ROOM SHOWN IN THE
 NEW ISOMETRIC (P6.0) HAVE BEEN REMOVED FROM THE FLOOR
 PLAN (P2.0). PLEASE CLARIFY WHAT THE DESIGN INTENTION
 IS, AND NOTE THAT BOILER ROOMS SHALL BE EQUIPPED WITH A
 FLOOR DRAIN OR OTHER APPROVED MEANS FOR DISPOSING OF
 LIQUID WASTE- SECTION 1004.6 FBC M. PLEASE NOTE THE WH
 DETAIL ON P.73 SHOWS FLOOR DRAINS.
  
 3) FAILED.P2.0, P5.1: PLEASE PROVIDE AN ENLARGED
 TYPICAL INDIRECT WASTE DISCHARGE DETAIL FOR THE
 3-COMPARTMENT SINKS IN THE SOILED WORKROOM, AND A
 TYPICAL INDIRECT WASTE DISCHARGE DETAIL FOR ALL OTHER
 FLOOR SINKS LOCATED UNDER CENTRAL STERILE EQUIPMENT AND
 FIXTURES- SECTION 713.3 FBC P. THE DETAIL ON P7.1 IS
 FOR A SINGLE INDIRECT WASTE DRAIN PIPE. PLEASE PROVIDE
 A 3-COMPARTMENT DRAIN DETAIL AS REQUESTED.
  
 6) FAILED. P0.1, P2.1, P5.1: PLEASE PROVIDE A SCHEDULE
 FOR THE REQUIRED BACKFLOW PREVENTERS TO BE INSTALLED ON
 SUPPLY LINES TO THE STERILIZERS, RO GENERATOR AND ALL
 OTHER PLUMBING FIXTURES PERFORMING A SPECIAL FUNCTION-
 SEE SECTIONS 422.2, 608.3, AND TABLE 608.1 FBC P.
 PLEASE SHOW THE BACKFLOW PREVENTER LOCATIONS ON THE
 PLUMBING PIPING PLANS AND ISOMETRIC DRAWING, AND
 PROVIDE AN INSTALLATION DETAIL. PLEASE SHOW LOCATION OF
 THE RO BF PREVENTER.
  
 8) FAILED. P0.1, P.2.1, P.51: PROVIDE ENLARGED WATER
 HEATER PIPING DETAILS SHOWING POTABLE WATER INLET AND
 OUTLET CONNECTIONS, PIPING CONNECTIONS TO RECIRCULATION
 PUMPS, BACKFLOW PREVENTERS- SECTION 502.1, 607.2, AND
 608.3 FBC P. PLEASE SHOW HOW STEAM CONDENSATION AND
 RELIEF VALVE DISCHARGE WILL BE DRAINED TO AN APPROVED
 LOCATION OR WASTE RECEPTOR-SECTION 314.2.1 AND 504.6
 FBC P. THE DETAIL ON SHEET P7.3 DOES NOT SHOW THERMAL
 EXPANSION TANKS FOR THE WATER HEATERS. PLEASE SEE
 MANUFACTURERS SPECIFICATIONS AND - SECTION 607.3 FBC P
 AND 1003.1 FBC M.
  
 12) ROOF AND STORM DRAINS- FBC P.
 C) FAILED. P2.2: PLEASE SHOW THE PRIMARY AND OVERFLOW
 SCUPPERS THAT ARE SHOWN ON SHEET A3.1- SECTION 107.2.1
 WPB AND 1101.7. NOT PROVIDED ON SHEET P2.2, AND ARE
 REQUIRED FOR PLUMBING COMPLIANCE.
 D) FAILED. PROVIDE SIZING CALCULATIONS FOR THE PRIMARY
 VERTICAL LEADERS AND HORIZONTAL BRANCHES BASED ON
 SECTIONS 1106.1 & 1106.2. REFER TO TABLE 1106.2 FBC P.
 PLEASE CLARIFY WHAT THE FIGURES IN PARENTHESES
 REPRESENT. REFER TO TABLE 1106.2 FOR GPM FLOW CAPACTIES
 OF STORM DRAIN PIPING AND PROVIDE CORRECT CALCULATIONS.
 E) FAILED. PROVIDE SIZING CALCULATIONS FOR THE
 SECONDARY ROOF DRAINS- SECTION 1108.3. NOT PROVIDED.
 SEE COMMENT 12D NOTES ABOVE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-17 Cont ID  
Sent By ccole Date 2020-12-17 Time 16:30 Rev Time 0.00
Received By ccole Date 2020-12-17 Time 10:28 Sent To  
Notes
2020-12-17 16:31:051ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20110397
 12/17/20
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SANITARY DRAINAGE AND WATER
 DISTRIBUTION ISOMETRIC DRAWINGS- SECTION 107.3.5.1.3
 WPB.
  
 2) SHEET P0.1: PLEASE PROVIDE A SCHEDULE FOR THE VENDOR
 SUPPLIED FIXTURES AND EQUIPMENT IN THE CENTRAL STERILE
 - TRIPLE BASIN PROCESSING SINKS, STEAM STERILIZERS, RO
 GENERATOR, WASHER/DISINFECTOR, CART WASHERS, SINK
 FAUCETS, SPRAYERS ETC. INCLUDE THE MAKES AND MODELS AND
 THE AGENCY LISTING APPROVAL NUMBERS- SECTION 422.1 &
 422.2 FBC P. PLEASE NOTE THAT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS FOR ALL
 PLUMBING FIXTURES, EQUIPMENT, AND DEVICES MAY BE
 DEFERRED SUBMITTALS OR BE ONSITE AT TIME OF INSPECTION-
 SECTIONS 107.2.1 AND 107.3.4.1 WPB.
  
 3) P2.0, P5.1: PLEASE PROVIDE AN ENLARGED TYPICAL
 INDIRECT WASTE DISCHARGE DETAIL FOR THE 3-COMPARTMENT
 SINKS IN THE SOILED WORKROOM, AND A TYPICAL INDIRECT
 WASTE DISCHARGE DETAIL FOR ALL OTHER FLOOR SINKS
 LOCATED UNDER CENTRAL STERIL EQUIPMENT AND FIXTURES-
 SECTION 713.3 FBC P.
  
 4) P2.0, P5.1: REFER TO SECTION 803.1 FBC P AND PROVIDE
 DILUTION OR NEUTRALIZING DEVICES FOR ANY CENTRAL
 STERILE FIXTURES OR EQUIPMENT DISCHARGING CORROSIVE
 LIQUIDS, ACIDS OR CHEMICALS THAT COULD DAMAGE THE
 DRAINAGE SYSTEM OR CREATE NOXIOUS OR TOXIC FUMES.
  
 5) P2.0, P5.1: PROVIDE TRAP PRIMERS FOR FLOOR SINKS
 WITH SEALS SUBJECT TO EVAPORATION- SECTION 1002.4.1 FBC
 P. SHOW THE LOCATIONS ON THE PIPING PLAN AND ISOMETRIC
 DRAWING AND PROVIDE INSTALLATION DETAILS.
  
 6) P0.1, P2.1, P5.1: PLEASE PROVIDE A SCHEDULE FOR THE
 REQUIRED BACKFLOW PREVENTERS TO BE INSTALLED ON SUPPLY
 LINES TO THE STERILIZERS, RO GENERATOR AND ALL OTHER
 PLUMBING FIXTURES PERFORMING A SPECIAL FUNCTION- SEE
 SECTIONS 422.2, 608.3, AND TABLE 608.1 FBC P. PLEASE
 SHOW THE BACKFLOW PREVENTER LOCATIONS ON THE PLUMBING
 PIPING PLANS AND ISOMETRIC DRAWING, AND PROVIDE AN
 INSTALLATION DETAIL.
  
 7) P0.1, P2.1, P5.1: SHOW THE LOCATIONS OF THE REQUIRED
 WATER HAMMER ARRESTORS FOR SUPPLY LINES TO FIXTURES AND
 EQUIPMENT WITH QUICK CLOSING VALVES- SECTION 604.9 FBC
 P.
  
 8) P0.1, P.2.1, P.51: PROVIDE ENLARGED WATER HEATER
 PIPING DETAILS SHOWING POTABLE WATER INLET AND OUTLET
 CONNECTIONS, PIPING CONNECTIONS TO RECIRCULATION PUMPS,
 BACKFLOW PREVENTERS- SECTION 502.1, 607.2, AND 608.3
 FBC P. PLEASE SHOW HOW STEAM CONDENSATION AND RELIEF
 VALVE DISCHARGE WILL BE DRAINED TO AN APPROVED LOCATION
 OR WASTE RECEPTOR-SECTION 314.2.1 AND 504.6 FBC P.
  
 9) P2.1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED
 TO THE LAVATORIES- SECTIONS 416.5 & 607.1.2 FBC P.
  
 10) P2.1 & P5.1: PLEASE LABEL THE HW & HWR LINES ON
 P2.1 & P5.1, AND THE RO SUPPLY AND RETURN LINES ON
 P5.1- SEE NOTE #11 AND SECTION 107.2.1 WPB.
  
 11) P5.1: PROVIDE THE CORRESPONDING TEXT FOR KEYNOTES
 12,13, & 14 SHOWN AT THE WATER HEATER/COMPRESSOR ROOM-
 SECTION 107.2.1 WPB.
  
 12) ROOF AND STORM DRAINS- FBC P.
  
 A) P2.0 & P2.2: PROVIDE A STORM DRAIN ISOMETRIC DRAWING
 SHOWING THE ROOF DRAIN VERTICAL LEADERS, UNDERSLAB
 HORIZONTAL STORM DRAINS, AND LOCATIONS OF REQUIRED
 CLEANOUTS- SECTIONS 1106.1, 1106.1, & 1108.1.
  
 B) P2.2: VERIFY THE ROOF AND DRAINAGE SYSTEM HAS BEEN
 DESIGNED IN COMPLIANCE WITH SECTION 1101.7 FOR MAXIMUM
 DEPTH OF PONDING WATER AND DEFLECTED STRUCTURAL
 ELEMENTS.
  
 C) P2.2: PLEASE SHOW THE PRIMARY AND OVERFLOW SCUPPERS
 THAT ARE SHOWN ON SHEET A3.1- SECTION 107.2.1 WPB AND
 1101.7.
  
 D) PROVIDE SIZING CALCULATIONS FOR THE PRIMARY VERTICAL
 LEADERS AND HORIZONTAL BRANCHES BASED ON SECTIONS
 1106.1 & 1106.2.
  
 E) PROVIDE SIZING CALCULATIONS FOR THE SECONDARY ROOF
 DRAINS- SECTION 1108.3.
  
 13) PROVIDE CIVIL PLANS SHOWING POINTS OF CONNECTIONS
 TO EXISTING SANITARY SEWER AND STORM DRAIN MAINS-
 SECTION 107.2.1 WPB.
  
 14) PROVIDE A PLUMBING SUB-PERMIT APPLICATIONS- SECTION
 105.1 WPB.
  
 15) PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTERS IN ACCORDANCE WITH SECTION 105.1
 WPB AND SEC, 90-33 WPB CODE OF ORDINANCES. THE DEVICE
 SHALL BE TESTED AND CERTIFIED BY THE WPB UTILITIES
 DEPARTMENT PRIOR TO FINAL INSPECTION BY THE BUILDING
 DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL
 OPERATIONS DEPT.AT 561-822-2210 FOR FURTHER
 INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2020-11-30 Cont ID  
Sent By jwitmer Date 2020-11-30 Time 16:01 Rev Time 0.00
Received By jwitmer Date 2020-11-30 Time 11:18 Sent To  
Notes
2020-11-30 16:01:26ROOFING PRODUCT APPROVAL: NOA 15-1026.04
 SEE PAGE 5 OF 8 MAXIMUM DESIGN PRESSURE -117PSF.
 LIMITATION #9.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-10 Cont ID  
Sent By ccole Date 2021-03-10 Time 11:25 Rev Time 0.00
Received By ccole Date 2021-03-10 Time 09:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-15 Cont ID  
Sent By medwards Date 2020-12-15 Time 13:44 Rev Time 0.00
Received By medwards Date 2020-12-15 Time 13:44 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By jwitmer Date 2021-02-17 Time 08:27 Rev Time 0.00
Received By jwitmer Date 2021-02-11 Time 08:59 Sent To  
Notes
2021-02-11 10:01:122/17/2021 MR. BOB LAKE SENT E-MAIL STATING THAT
 CONTRACTOR/ OWNER SIGNATURE PAGE WAS INCLUDED IN THE
 THRESHOLD INSPECTOR PACKAGE ON FIRST SUBMITTAL WHEN I
 WENT BACK INTO PROJECT DOX PAGE 27 OF 27 WAS A SIGNED
 CONTRACTOR/ OWNER PAGE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By jwitmer Date 2020-12-01 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2020-12-01 Time 14:45 Sent To  
Notes
2020-12-01 15:28:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW- THRESHOLD BUILDINGS
 W. P. B. PERMIT: 20110397
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 01ST/ 2020
 ACTION: DENIED
  
 1) PLEASE NOTE THIS IS A ONE-STORY ADDITION TO AN
 EXISTING 4 STORY BUILDING (THRESHOLD BUILDING). WITHIN
 THE ALTERRA SOILS REPORT UNDER THE HEADING PROJECT
 INFORMATION ALTERRA UNDERSTANDS THE PROJECT MAY BE
 CONSTRUCTED INITIALLY AS A 1-STORY ADDITION WITH
 ADDITIONAL FLOORS TO BE ADDED AT A LATER TIME.
 BECAUSE OF THE BUILDING BEING 4 STORIES AND MEETING THE
 THRESHOLD REQUIREMENTS THE CITY OF WEST PALM BEACH IS
 CONSIDERING THIS AS A THRESHOLD PROJECT.
 THRESHOLD DOCUMENT WILL BE SENT TO:
 [email protected] 15:25TUE. 12-01-2020.
  
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-03-04 Cont ID  
Sent By eschneid Date 2021-03-04 Time 10:04 Rev Time 0.50
Received By eschneid Date 2021-03-04 Time 09:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By eschneid Date 2020-12-07 Time 13:25 Rev Time 0.75
Received By eschneid Date 2020-12-07 Time 10:58 Sent To  
Notes
2020-12-07 13:25:22FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THERE ARE TREES PROPOSED TO BE REMOVED IN THE
 LOCATION OF THE STERILE PROCESSING DEPARTMENT
 EXPANSION. ZONING WILL NOT APPROVE THIS PERMIT UNTIL
 EVIDENCE IS PROVIDED THAT A TREE ALTERATION PERMIT HAS
 BEEN SUBMITTED TO AND APPROVED BY THE PLANNING
 DIVISION. PLEASE CONTACT RAY CARANCI, SENIOR LANDSCAPE
 PLANNER, AT (561) 822-1462 IF YOU REQUIRE ADDITIONAL
 INFORMATION.
  
 2) PROVIDE A SURVEY COVERING THE AREA OF WORK. PREVIOUS
 PLANS SUBMITTED TO THE PLANNING DIVISION SHOW A UTILITY
 EASEMENT WITHIN THE PROJECT BOUNDARIES. PROVIDE COPIES
 OF THE LETTERS OF NO OBJECTION FROM FPL, FPU, COMCAST
 AND AT&T FOR YOUR CONSTRUCTION OVER THE EASEMENT.
  
 3) THE CIVIL PLAN PROVIDED WITH THE ORIGINAL MINOR
 PLANNED DEVELOPMENT AMENDMENT REVIEW BY THE PLANNING
 DIVISION SHOWS AN EXISTING ELECTRIC LINE WITHIN THE
 PROPOSED BUILDING FOOTPRINT. THE PLANS DO NOT INDICATE
 HOW THIS IS BEING PROTECTED OR RELOCATED. PLEASE
 CLARIFY THE STATUS OF THE ELECTRIC LINE. IF THE LINE IS
 TO REMAIN IN PLACE, FPL SHALL SPECIFICALLY INDICATE IN
 THEIR LETTER THAT THEY DO NOT OBJECT TO THE LINE
 REMAINING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  