Plan Review Details - Permit 20110320
Plan Review Stops For Permit 20110320
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-02-24 Cont ID  
Sent By jwitmer Date 2021-02-24 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2021-02-24 Time 09:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-01-10 Cont ID  
Sent By jwitmer Date 2021-01-10 Time 09:24 Rev Time 0.00
Received By jwitmer Date 2021-01-10 Time 09:00 Sent To  
Notes
2021-01-10 09:23:51WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:20110320
 ADD: 1700 PALM BEACH LAKES BLVD. SUITE: 130 / AMENITY
 CENTER
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-251-2459
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN, JAN. 10TH/ 2021
 ACTION: DENIED
  
 1) A ASBESTOS LETTER WAS SUBMITTED BY W & J GENERAL
 CONTRACTORS, BUT TO DATE THEY ARE NOT NAMED AS THE CGC
 ON THE PERMIT APPLICATION. THIS REVIEW THERE IS NO CGC
 NAMED TO BE DETERMINED.
  
 COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-02-24 Cont ID  
Sent By jwitmer Date 2021-02-24 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2021-02-24 Time 09:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-10 Cont ID  
Sent By jwitmer Date 2021-01-10 Time 10:05 Rev Time 0.00
Received By jwitmer Date 2021-01-10 Time 09:00 Sent To  
Notes
2021-01-10 10:05:25WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:20110320
 ADD: 1700 PALM BEACH LAKES BLVD. SUITE: 130 / AMENITY
 CENTER
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-251-2459
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN, JAN. 10TH/ 2021
 ACTION: DENIED
  
 1) SHEET A0.01 GENERAL INFORMATION.
  
 1A) NEITHER THE PERMIT APPLICATION NOR THE TITLEBLOCK
 FOUND ON THE PLANS STATES WHERE THE WORK IS TO OCCUR
 UNDER THIS PERMIT BY SUITE NUMBER FOR IDENTIFICATION.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 1B) UNDER THE HEADING PROJECT INFORMATION THE OCCUPANCY
 TYPE IS DECLARED AS A BUSINESS OCCUPANCY. PLEASE
 EXPLAIN WHY YOU BELIEVE THIS TO BE A BUSINESS
 OCCUPANCY. IT APPEARS TO BE AN ASSEMBLY OCCUPANCY
 BETWEEN A-2 AND A-3 OCCUPANCY TYPES. THE FLOOR AREA IS
 OVER 750 SQ. FT. AND THE SEATING ALONE IS 79 SEATS, NOT
 INCLUDING THE BEHIND THE COUNTER AREA/ KITCHEN THAT
 SHOULD BE 200 SQ. FT. OCCUPANT LOAD FACTOR. 2017 FBC-B
 SECTION 303.1.
  
 2) THE LIFE SAFETY SHEET A0.02 SHOWS THE FLOOR PLAN FOR
 SEATING BUT DOES NOT SHOW ACCESSIBLE SEATING. 79 SEATS
 X 0.05= 4 REQUIRED ACCESSIBLE SEATS. SHEETS A4.21 AND
 A4.22 SHOW COUNTER HEIGHTS BUT WITHOUT SHOWING WHERE
 THE ACCESSIBLE SEATS ARE THE DETAILS ONLY SHOW PART OF
 THE PICTURE. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING
 ACCESSIBLE REQUIREMENTS.
  
 2A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 2B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 2D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 2E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-04-07 Cont ID  
Sent By jleahy Date 2021-04-07 Time 07:16 Rev Time 0.00
Received By jleahy Date 2021-04-07 Time 06:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-01-13 Cont ID  
Sent By jleahy Date 2021-01-13 Time 13:44 Rev Time 0.00
Received By jleahy Date 2021-01-13 Time 13:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-22 Cont ID  
Sent By jleahy Date 2021-01-22 Time 13:46 Rev Time 0.00
Received By jleahy Date 2021-01-13 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-01-13 Cont ID  
Sent By jleahy Date 2021-01-13 Time 13:44 Rev Time 0.00
Received By jleahy Date 2021-01-13 Time 13:44 Sent To  
Notes
2021-01-13 13:45:00VOICE, DATA, TV ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-04-09 Time   Rev Time 0.00
Received By bdolan Date 2021-04-09 Time 10:20 Sent To  
Notes
2021-04-09 10:20:37THIS PLAN HAS BEEN REVIEWED AND APPROVED BY THE FIRE
 DEPARTMENT.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-12-15 Cont ID  
Sent By bdolan Date 2020-12-15 Time 10:05 Rev Time 0.00
Received By bdolan Date 2020-12-15 Time 10:03 Sent To  
Notes
2020-12-15 10:04:581) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-04-21 Cont ID  
Sent By lmarchan Date 2021-04-21 Time 10:39 Rev Time 0.00
Received By lmarchan Date 2021-04-20 Time 10:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-09 Cont ID  
Sent By medwards Date 2021-04-09 Time 10:25 Rev Time 0.00
Received By lmarchan Date 2021-03-17 Time 13:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-06 Cont ID  
Sent By medwards Date 2021-03-10 Time   Rev Time 0.00
Received By lmarchan Date 2021-02-23 Time 05:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-13 Cont ID  
Sent By jleahy Date 2021-01-13 Time 13:45 Rev Time 0.00
Received By jleahy Date 2020-12-14 Time 16:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-04-05 Cont ID  
Sent By medwards Date 2021-04-05 Time 08:24 Rev Time 0.00
Received By medwards Date 2021-04-05 Time 08:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-03-10 Cont ID  
Sent By medwards Date 2021-03-10 Time 12:06 Rev Time 0.00
Received By medwards Date 2021-03-10 Time 10:47 Sent To  
Notes
2021-03-10 12:07:311ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20110320
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN THIS BUSINESS YOU HAVE OFFICES, 2 CONFERENCE
 ROOMS AND 2 LOUNGE AREAS. PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS FOR EACH OF THESE AREAS. EACH DIFFERENT
 USE OF SPACE IN THIS BUSINESS MUST HAVE A SEPARATE
 OUTDOOR AIR CALCULATION. THE LOUNGE AREAS MUST MATCH UP
 WITH EITHER ?CAFETERIA, FAST FOOD? OR DINING ROOMS.
 USING THE ASHRAE 62.1-2013 THE AREA OUTDOOR RATE FOR
 CAFETERIA/FAST FOOD IS .18 AND THE PEOPLE OUTDOOR RATE
 IS 7.5 THE LOUNGE OUTDOOR AIR WOULD BE 495 CFM. THIS
 SHOULD BE USED FOR THE LOUNGE AREA.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-07 Cont ID  
Sent By medwards Date 2021-01-07 Time 15:13 Rev Time 0.00
Received By medwards Date 2021-01-07 Time 14:53 Sent To  
Notes
2021-01-07 15:13:371ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110320
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REWORK THE OUTDOOR AIR CALCULATIONS THEY SEEM
 TO BE LOW. EXAMPLE:
 SMALL CONFERENCE ROOM_ 597/1000= .597; .597 X 50 X 5 =
 149.25; + 597 X .06 = 35.82; 149.25 + 35.82 = 185.07.
 FBC M TABLE 403.3.1.1
  
 2) PLEASE IDENTIFY THE LOUNGE AREA TO ONE OF THE
 OCCUPANCY CLASSIFICATIONS THAT BEST FITS IT?S USE IN
 TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-04-21 Cont ID  
Sent By tklarge Date 2021-04-21 Time 05:30 Rev Time 0.00
Received By tklarge Date 2021-04-21 Time 05:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-04-09 Cont ID  
Sent By tklarge Date 2021-04-09 Time 06:12 Rev Time 0.00
Received By tklarge Date 2021-04-07 Time 13:04 Sent To  
Notes
2021-04-09 05:29:301) SHT. P0.1 - SUBMIT THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION MANUAL FOR THE LIBERTY SUMP PUMP. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) THE SINK IN THE OPEN OFFICE AREA CANNOT DISCHARGE
 INTO THE WET VENT PER FBC-PLUMBING SEC.912.1. THE SINK
 SHALL CONNECT TO THE HORIZONTAL DRAI DOWNSTREAM OF THE
 WATER CCLOSET.
 3) A FULL OPEN SHUTOFF VALVE IS REQUIRED ON THE
 DISCHARGE SIDE OF THE CHECK VALVE ON THE SUMP PUMP PERR
 FBC- PLUMBING SEC. 712.2.
 4) A BACKFLOW DEVICE COMPLYING WITH ASSE 1022 IS
 REQUIRED ON THE COFFEE MACHINE AND ICEMAKER.
 FBC-PLUMBING SEC.608.16.10.
 5) THE DISHWASHER SHALL BE EQUIPPED WITH A BACKFLOW
 DEVICE COMPLYING WITH ASSE 1024 PER FBC-PLUMBING TABLE
 608.1.
 6) SHT. P0.1 - SIZE THE VENT FOR THE SINKS, WATER
 CLOSET AND LAVATORY. COMPLY WITH FBC-PLUMBING
 SEC.906.1, TABLE 906.1. THE DIAMETER OF THE VENT SHALL
 BE NO LESS THAN ONE-HALF THE DIAMETER OF THE DRAIN
 SERVED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-01-11 Cont ID  
Sent By tklarge Date 2021-01-11 Time 11:14 Rev Time 0.00
Received By tklarge Date 2021-01-07 Time 11:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-05 Cont ID  
Sent By medwards Date 2021-04-05 Time 08:48 Rev Time 0.00
Received By medwards Date 2021-04-05 Time 08:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-10 Cont ID  
Sent By medwards Date 2021-03-10 Time 12:14 Rev Time 0.00
Received By medwards Date 2021-03-10 Time 12:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-07 Cont ID  
Sent By medwards Date 2021-01-07 Time 15:45 Rev Time 0.00
Received By medwards Date 2021-01-07 Time 15:45 Sent To  
Notes
***NONE***