Plan Review Details - Permit 20110265
| Plan Review Stops For Permit 20110265 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-04-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-04-27 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-04-27 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2021-04-27 08:01:18 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NOT COMPLIED. FBC 107.2.1 - INFORMATION ON | | | CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. | | | | | | 2) NOT COMPLIED. [ PROVIDE TOTAL INSURANCE REPLACEMENT | | | COST. ] THE VALUE OF $300.00 APPEARS TO BE LOW FOR THIS | | | PROJECT. FBC 109.3 BUILDING PERMIT VALUATION. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 3) COMPLIED. | | | | | | 4) NOT COMPLIED. PROVIDE THE MANUFACTURE'S | | | SPECIFICATIONS AND INSTALLATION REQUIREMENTS WITH | | | REQUIRED CLEARANCES, ETC. FBC 107 | | | | | | 5) NOT COMPLIED. PROVIDE STRUCTURAL DRAWINGS OF THE | | | OUTDOOR KITCHEN. SPECIFY THE FOUNDATION, ALL | | | CONSTRUCTION MATERIALS, REINFORCING, CONNECTORS, | | | ANCHORS, ETC. FBC 107 | | | | | | 6) NOT COMPLIED. SHOW THAT THE PROPOSED STRUCTURE IS | | | CAPABLE OF RESISTING THE REQUIRED WINDLOADS. FBC-R301 | | | | | | 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE | | | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON | | | THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS | | | MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED. | | | | | | 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | | | | 9) NEW COMMENT. THIS PROJECT WAS APPLIED FOR BEFORE | | | DECEMBER 31, 2020 THE DATE THAT THE 2020 FBC SEVENTH | | | EDITION WENT INTO EFFECT. THIS PROJECT IS UNDER THE | | | 2017 FBC SIXTH EDITION. THE PLANS THAT WERE SUBMITTED | | | REFERENCE THE 2020 FBC AND SHOULD BE REFERENCING THE | | | 2017 FBC. PLEASE CORRECT. FS CHAPTER 553 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-01-06 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-01-06 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2021-01-06 09:12:23 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) THE VALUE OF $300.00 APPEARS TO BE LOW FOR THIS | | | PROJECT. FBC 109.3 BUILDING PERMIT VALUATION. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 3) PROVIDE A SITE PLAN THAT SHOWS THE LOCATION OF THE | | | PROPOSED WORK. IF IT IS UNDER A COVERED PORCH, PROVIDE | | | DETAILS OF THE PORCH. SHOW WHICH SIDES ARE OPEN, THE | | | CEILING HEIGHT, CEILING MATERIAL (COMBUSTIBLE OR NOT), | | | ETC. FBC 107 | | | | | | 4) PROVIDE THE MANUFACTURE'S SPECIFICATIONS AND | | | INSTALLATION REQUIREMENTS WITH REQUIRED CLEARANCES, | | | ETC. FBC 107 | | | | | | 5) PROVIDE STRUCTURAL DRAWINGS OF THE OUTDOOR KITCHEN. | | | SPECIFY THE FOUNDATION, ALL CONSTRUCTION MATERIALS, | | | REINFORCING, CONNECTORS, ANCHORS, ETC. FBC 107 | | | | | | 6) SHOW THAT THE PROPOSED STRUCTURE IS CAPABLE OF | | | RESISTING THE REQUIRED WINDLOADS. FBC-R301 | | | | | | 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE | | | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON | | | THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS | | | MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED. | | | | | | 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-04-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-04-26 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-04-26 |
Time |
14:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-01-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-01-05 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-01-05 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2021-01-05 14:53:59 | PLAN DOES NOT EXPLAIN WHAT THE ELECTRIC IS AND WHAT IT | | | IS FOR. PLEASE EXPLAIN. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-04-29 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-04-29 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-04-21 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2021-01-06 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-12-18 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2021-04-29 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-04-29 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-04-29 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2021-04-29 10:52:28 | 04/29/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1) TOTAL JOB COST SEEMS LOW. THE VALUE MUST INCLUDE THE | | | COST OF ALL EQUIPMENT, LABOR, AND MATERIALS. PROVIDE | | | BONA FIDE SIGNED CONTRACT PER WPB AMENDMENTS TO THE FBC | | | 109.3. | | | | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF THE BUILDING, ALTERATION, | | | STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR PLUMBING | | | SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE | | | APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE | | | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR | | | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO | | | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR | | | PERMITTING PURPOSES, THE VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR | | | FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN | | | FEES, MARKETING COSTS, OVERHEAD, AND PROFIT, EXCLUDING | | | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE | | | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST | | | ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS | | | PUBLISHED BY INTERNATIONAL CODE CONGRESS. THE FINAL | | | BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING | | | OFFICIAL. | | | | | | 2) PLEASE PROVIDE A SOURCE OF HOT WATER AND THE | | | LOCATION OF CONNECTION PER THE 2020 FBC SEC. FBC R | | | 2722.2. | | | | | | 3) IF HOT WATER IS COMING FROM THE MAIN HOUSE AND | | | UNDERGROUND NEEDS TO BE INSULATED WITH A MINIMUM R-3 | | | PER THE 2020 FBC SEC. RE 403.5.3. | | | | | | 4) PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, | | | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT | | | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO | | | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | 5) THE PLUMBING SCOPE TO BE DONE IS UNCLEAR. PLEASE | | | PROVIDE A SANITARY AND WATER ISOMETRIC DRAWING PER THE | | | WPB AMEND TO FBC 107.3.5.3 (12) RESIDENTIAL PLUMBING. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2021-01-06 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2021-01-06 |
Time |
14:17 |
Sent To |
I |
|
| Notes |
| 2021-01-06 15:25:04 | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT-20110265 | | | 1/6/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) TOTAL JOB COST SEEMS LOW. THE VALUE MUST INCLUDE THE | | | COST OF ALL EQUIPMENT, LABOR AND MATERIALS. PROVIDE | | | BONA FIDE SIGNED CONTRACT PER WPB AMENDMENTS TO THE FBC | | | 109.3 | | | 2) THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON | | | PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION | | | ON CONSTRUCTION DOCUMENTS. | | | 3) THE SCOPE OF THE PLUMBING TO BE DONE IS UNCLEAR | | | PLEASE PROVIDE PLUMBING PLAN INCLUDING A SANITARY AND | | | WATER ISOMETRIC DRAWING. PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | 4) A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME DUE TO NOT ENOUGH INFORMATION ON THE PROVIDED | | | PLAN. ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED | | | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
N |
Date |
2021-04-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-04-27 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-04-27 |
Time |
08:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-01-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-01-05 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-01-05 |
Time |
14:48 |
Sent To |
|
|
| Notes |
|
|
|