Plan Review Details - Permit 20110223
Plan Review Stops For Permit 20110223
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-01-20 Cont ID  
Sent By cthroop Date 2021-01-20 Time 08:42 Rev Time 0.00
Received By cthroop Date 2021-01-20 Time 08:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-14 Cont ID  
Sent By cthroop Date 2020-12-14 Time 15:55 Rev Time 0.00
Received By cthroop Date 2020-12-14 Time 14:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-11-17 Cont ID  
Sent By cthroop Date 2020-11-17 Time 16:10 Rev Time 0.00
Received By cthroop Date 2020-11-17 Time 15:58 Sent To  
Notes
2020-11-12 18:02:39GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-12-09 Cont ID  
Sent By ppetty Date 2020-12-09 Time 09:24 Rev Time 0.00
Received By ppetty Date 2020-12-09 Time 07:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By ppetty Date 2020-12-07 Time 10:59 Rev Time 0.00
Received By ppetty Date 2020-12-07 Time 10:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By ppetty Date 2020-11-19 Time 11:45 Rev Time 0.00
Received By ppetty Date 2020-11-19 Time 10:31 Sent To  
Notes
2020-11-19 11:47:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-11-12 Cont ID  
Sent By lcrespo Date 2020-11-12 Time 18:02 Rev Time 0.00
Received By lcrespo Date 2020-11-12 Time 18:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-01-20 Cont ID  
Sent By cthroop Date 2021-01-20 Time 08:43 Rev Time 0.00
Received By cthroop Date 2021-01-07 Time 02:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-14 Cont ID  
Sent By cthroop Date 2020-12-14 Time 15:56 Rev Time 0.00
Received By cthroop Date 2020-12-07 Time 14:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-07 Cont ID  
Sent By shill Date 2020-12-07 Time 11:12 Rev Time 0.00
Received By shill Date 2020-12-02 Time 13:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-19 Cont ID  
Sent By ppetty Date 2020-11-19 Time 11:48 Rev Time 0.00
Received By ppetty Date 2020-11-05 Time 14:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-08 Cont ID  
Sent By lcrespo Date 2020-12-08 Time 22:38 Rev Time 0.00
Received By lcrespo Date 2020-12-08 Time 19:33 Sent To  
Notes
2020-12-08 19:34:0112/08/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING, POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-11-12 Cont ID  
Sent By lcrespo Date 2020-11-12 Time 18:14 Rev Time 0.00
Received By lcrespo Date 2020-11-12 Time 18:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-01-20 Cont ID  
Sent By cthroop Date 2021-01-20 Time 08:42 Rev Time 0.00
Received By cthroop Date 2021-01-20 Time 08:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-12-17 Cont ID  
Sent By jgomez Date 2020-12-17 Time 10:14 Rev Time 0.00
Received By jgomez Date 2020-12-17 Time 09:19 Sent To  
Notes
2020-12-17 10:12:28SIGNATURE REVIEW DENIED:
  
 SHEET 1 OF 2 AND SHEET 2 OF 2 SUBMITTED ARE NOT THE
 DRAWINGS THAT WERE REQUESTED ON THE PREVIOUS COMMENTS.
 PLAN REVIEWER WAS ASKING ONLY FOR DRAWING E-103 TO HAVE
 THE ENGINEER'S ORIGINAL SEAL/SIGNATURE. SEE COPY OF
 COMMENTS BELOW. NEED TO SUBMIT DRAWING E-103 WITH
 ENGINEER'S ORIGINAL SEAL/SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
 PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PLAN PAGE E-103
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-12-14 Cont ID  
Sent By cthroop Date 2020-12-14 Time 15:55 Rev Time 0.00
Received By cthroop Date 2020-12-14 Time 14:51 Sent To  
Notes
2020-12-14 15:56:36PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PLAN PAGE E-103
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-12-07 Cont ID  
Sent By shill Date 2020-12-07 Time 11:10 Rev Time 0.00
Received By shill Date 2020-12-07 Time 11:10 Sent To  
Notes
2020-12-07 11:12:25SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL. THE PLANS UPLOADED HAVE AN IMAGE OF A
 SIGNATURE AND SEAL BUT ARE NOT DIGITALLY SIGNED.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
  
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6724.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By ppetty Date 2020-11-19 Time 11:48 Rev Time 0.00
Received By ppetty Date 2020-11-19 Time 11:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-12-14 Cont ID  
Sent By rthermid Date 2020-12-14 Time   Rev Time 0.00
Received By rthermid Date 2020-12-14 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-11-12 Cont ID  
Sent By rthermid Date 2020-11-12 Time   Rev Time  
Received By rthermid Date 2020-11-12 Time   Sent To I
Notes
***NONE***