Plan Review Details - Permit 20110186
Plan Review Stops For Permit 20110186
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-11-13 Cont ID  
Sent By jwitmer Date 2020-11-13 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2020-11-13 Time 14:28 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-11-09 Cont ID  
Sent By jwitmer Date 2020-11-09 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2020-11-09 Time 08:59 Sent To  
Notes
2020-11-09 09:59:39TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-27 Cont ID  
Sent By jwitmer Date 2020-11-27 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2020-11-27 Time 10:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-09 Cont ID  
Sent By jwitmer Date 2020-11-09 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2020-11-09 Time 08:59 Sent To  
Notes
2020-11-09 09:56:38WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110186
 ADD: 701 S. OLIVE AVE. # 1204
 CONT: MARTINGALE BUILDERS INC.
 TEL: 561-371-0568
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 09/2020
 ACTION: DENIED
 1) PLEASE NOTE 3 OF THE 5 PAGES ARE COPY OF APPROVED
 PLANS WITH CITY STAMPS ON THEM WITH THE TITLE BLOCK CUT
 OFF. SHEET E3.24 HAS THE FULL TITLEBLOCK AND ENGINEERS
 NAME JIMENEZ MCDOWELL ON THE SHEET. PLEASE NOTE THERE
 ARE COPYRIGHT LAWS BEING VIOLATED. 61G15-23.002
 ENGINEER SEAL SIGNATURE AND DATE SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN BY HAND THE
 LICENSEE?S HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT
 ACCEPTABLE) AND AFFIX THE LICENSEE?S SEAL:
 (A) TO ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS,
 REPORTS, OR DOCUMENTS PREPARED OR ISSUED BY THE
 LICENSEE AND BEING FILED FOR PUBLIC RECORD.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) PAGES DO NOT HAVE NUMBERS TO IDENTIFY THEM, THE
 PROPOSED FLOOR PLAN SHOWS BOTH A NEW WALL AND DROPPED
 CEILINGS.
  
 2A) THE PROPOSED WALL DOES NOT PROVIDE A LENGTH, DOES
 IT EXTEND TO THE CEILING ABOVE, WHAT TYPE OF STUDS AND
 SPACING OF VERTICAL FRAMING MEMBERS, TYPE OF DRYWALL,
 THICKNESS AND IS THERE BACKING FOR THE CABINETS.
 ADMINISTRATION 107.2.1. W.P.B. ADMINISTRATIVE CODE/2017
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2B) THE PROPOSED FLOOR PLAN ALSO NOTES AN AREA WHERE
 THE CEILINGS ARE TO BE DROPPED. THE PLAN IS SILENT AS
 TO WHAT HEIGHT THE CEILINGS ARE TOO DROPPED. PLEASE
 NOTE HABITABLE SPACES AND CORRIDORS SHALL HAVE CEILING
 HEIGHTS OF NOT THAN 7 FEET 6 INCHES, BATHROOMS, TOILET
 ROOMS, KITCHENS, STORAGE ROOMS AND LAUNDRY ROOMS SHALL
 NOT HAVE CEILING HEIGHT OF NOT LESS THAN 7 FEET. SEE
 2017 FBC-B SECTION 1208.2 MINIMUM CEILING HEIGHTS.
  
 2C) THE PLANS ARE SILENT AS TO THE FRAMING MEMBERS FOR
 THE DROPPED CEILINGS, SIZE, MATERIAL, ASSUMED METAL
 STUDS, GAUGE OF METAL, SPACING OF METAL, ALLOWABLE
 SPAN, IF MID SPAN SUPPORT IS REQUIRED, STIFF-BACKS,
 ANCHORS TO WALLS, ANCHORS METAL TO METAL, TYPE OF
 FINISH MATERIAL AND THICKNESS. ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
  
 3) THE PERMIT APPLICATION MENTIONS FLOOR REPAIR, PLEASE
 EXPOUND ON THAT COMMENT. A REPAIR IS TO REPLACE WITH
 LIKE MATERIAL. OR IS THE WHOLE FLOOR IN A SINGLE ROOM
 BE REPLACED. IF THE FLOOR IS TO BE REPLACED THEN SHOW
 COMPLIANCE WITH: FOR TILE, STONE, MARBLE, VINYL AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
 TYPE I AND II BUILDINGS
  
 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2017 FBC-B.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-02 Cont ID  
Sent By equinone Date 2020-12-02 Time 10:04 Rev Time 0.00
Received By equinone Date 2020-12-02 Time 10:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-24 Cont ID  
Sent By equinone Date 2020-11-24 Time 08:51 Rev Time 0.00
Received By equinone Date 2020-11-24 Time 08:51 Sent To  
Notes
2020-11-24 08:53:14CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) CLARIFY WHAT THE TWO 110 VOLTS CIRCUITS ARE FEEDING.
 IF INSTALLING NEW RECEPTACLES, THEY NEED TO BE GFCI
 PROTECTED. NEC 210.8
 2) PLEASE SEE SIGNATURE COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-25 Cont ID  
Sent By pleduc Date 2020-11-25 Time   Rev Time 0.00
Received By pleduc Date 2020-11-25 Time 09:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-11-10 Cont ID  
Sent By pleduc Date 2020-11-10 Time   Rev Time 0.00
Received By pleduc Date 2020-11-10 Time 11:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-02 Cont ID  
Sent By equinone Date 2020-12-02 Time 10:04 Rev Time 0.00
Received By equinone Date 2020-11-24 Time 15:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-24 Cont ID  
Sent By equinone Date 2020-11-24 Time 08:53 Rev Time 0.00
Received By equinone Date 2020-11-05 Time 13:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-27 Cont ID  
Sent By jwitmer Date 2020-11-27 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2020-11-27 Time 10:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-09 Cont ID  
Sent By jwitmer Date 2020-11-09 Time 09:58 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-11-09 09:58:241) PLEASE NOTE 3 OF THE 5 PAGES ARE COPY OF APPROVED
 PLANS WITH CITY STAMPS ON THEM WITH THE TITLE BLOCK CUT
 OFF. SHEET E3.24 HAS THE FULL TITLEBLOCK AND ENGINEERS
 NAME JIMENEZ MCDOWELL ON THE SHEET. PLEASE NOTE THERE
 ARE COPYRIGHT LAWS BEING VIOLATED. 61G15-23.002
 ENGINEER SEAL SIGNATURE AND DATE SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN BY HAND THE
 LICENSEE?S HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT
 ACCEPTABLE) AND AFFIX THE LICENSEE?S SEAL:
 (A) TO ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS,
 REPORTS, OR DOCUMENTS PREPARED OR ISSUED BY THE
 LICENSEE AND BEING FILED FOR PUBLIC RECORD.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  