Plan Review Details - Permit 20110119
Plan Review Stops For Permit 20110119
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-05-26 Cont ID  
Sent By cthroop Date 2021-05-26 Time 17:07 Rev Time 0.00
Received By cthroop Date 2021-05-26 Time 15:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-04-08 Cont ID  
Sent By cthroop Date 2021-04-08 Time 16:49 Rev Time 0.00
Received By cthroop Date 2021-04-08 Time 16:07 Sent To  
Notes
2021-04-08 16:50:45PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED WINDOWS AND
 DOORS. CORRECTED
  
 NEW COMMENTS:
  
 2. REF: PLAN PAGE A-1. GOVERNING CODES STATED AS FBC
 2020 7TH ED. THIS PROJECT SHALL BE DESIGNED UNDER THE
 FBC 2017 6TH ED. PLEASE CORRECT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. REF: PLAN PAGE A-2. IDENTIFY THE INSULATION TYPE AND
 R-VALUE OF THE EXTERIOR MASONRY WALLS.
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
  
 4. PROVIDE AN ENERGY SUBMITTAL. CORRECTED
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-02-10 Cont ID  
Sent By cthroop Date 2021-02-10 Time 11:11 Rev Time 0.00
Received By cthroop Date 2021-02-10 Time 09:54 Sent To  
Notes
2021-02-10 11:18:43PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED WINDOWS AND
 DOORS. CORRECTED
  
 NEW COMMENTS:
  
 2. REF: PLAN PAGE A-1. GOVERNING CODES STATED AS FBC
 2020 7TH ED. THIS PROJECT SHALL BE DESIGNED UNDER THE
 FBC 2017 6TH ED. PLEASE CORRECT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. REF: PLAN PAGE A-2. IDENTIFY THE INSULATION TYPE AND
 R-VALUE OF THE EXTERIOR MASONRY WALLS.
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
  
 4. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By cthroop Date 2020-11-19 Time 12:50 Rev Time 0.00
Received By cthroop Date 2020-11-19 Time 12:10 Sent To  
Notes
2020-11-19 12:53:01PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED WINDOWS AND
 DOORS.
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-03-30 Cont ID  
Sent By equinone Date 2021-03-30 Time 13:59 Rev Time 0.00
Received By equinone Date 2021-03-30 Time 13:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-02-11 Cont ID  
Sent By equinone Date 2021-02-11 Time 16:13 Rev Time 0.00
Received By equinone Date 2021-02-09 Time 07:56 Sent To  
Notes
2021-02-11 16:14:49CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 1) ELECTRICAL DRAWING SUBMITTED FOR GAS WATER HEATER
 NOT CLEAR:
 ? BOX LABELED ?EXISTING OUTDOOR LIGHTING?: IS THIS A
 SUBPANEL, JUNCTION BOX? PLEASE CLARIFY FBC 107
 ? BOX IS LABELED EXISTING OUTDOOR LIGHTING, BUT DIAGRAM
 MENTIONS THAT YOU ARE ADDING 2#12 CU CONDUCTORS TO FEED
 THE BOX. IS THERE AN EXISTING CIRCUIT TO THE BOX BEING
 REPLACED? FBC 107
 ? CIRCUIT FROM EXISTING CUTTLER HAMMER PANEL TO
 ?EXISTING OUTDOOR LIGHTING? BOX SHOWS 2#12 CONDUCTORS
 WITH NO EQUIPMENT GROUNDING. PLEASE SPECIFY EQUIPMENT
 GROUNDING. NEC 250
 ? WHAT IS THE SIZE OF CONDUCTORS CONNECTING TO THE
 ?EXISTING OUTDOOR LIGHTING?? WHAT IS THE EXISTING LOAD
 ON THIS CIRCUIT? WHAT WILL BE THE TOTAL LOAD ON THIS
 CIRCUIT IF IT IS ALSO FEEDING THE GAS WATER HEATER?
  
 2) ELECTRICAL DRAWING FOR GAS WATER HEATER MUST HAVE
 THE NAME AND SIGNATURE OF CONTRACTOR QUALIFIER
 PREPARING THE DRAWINGS FBC 107
 3) NEW A-3 MEP DRAWINGS SUBMITTED ARE DISTORTED AND
 DIFFICULT TO READ.
 4) ELECTRICAL SUB-PERMIT REQUIRED
 5) PLEASE SEE ALSO SIGNATURE COMMENTS FOR DRAWINGS FBC
 107
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By equinone Date 2020-11-20 Time 11:54 Rev Time 0.00
Received By equinone Date 2020-11-20 Time 11:54 Sent To  
Notes
2020-11-20 11:54:32CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) AT LEAST ONE ADDITIONAL RECEPTACLE REQUIRED ON
 BEDROOM (WALL NEXT TO DOOR OR CLOSET WALL). PLEASE
 VERIFY REST OF RECEPTACLE SPACING. NEC 210.52
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-03-24 Cont ID  
Sent By lcrespo Date 2021-03-24 Time 10:19 Rev Time 0.00
Received By lcrespo Date 2021-03-24 Time 09:51 Sent To  
Notes
2021-03-24 10:19:5703/24/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-02-10 Cont ID  
Sent By lcrespo Date 2021-02-10 Time 10:25 Rev Time 0.00
Received By lcrespo Date 2021-02-10 Time 10:25 Sent To  
Notes
2021-02-10 11:14:5102/10/21 1ST REVIEW PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE RESIDENCE'S PHYSICAL ADDRESS MUST BE ON PLANS IN
 FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED THE
 ISOMETRIC, ALL PIPE SIZES, AND THE CORRESPONDING EHD
 NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF
 APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED
 FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC.
 G2421.1.
  
 5. PLEASE PROVIDE THE TANK-LESS WATER HEATER'S LOCATION
 AND THE DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE WATER HEATER'S
 LOCATION SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 6. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION. PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. THE OVERALL VALUE IS LOW. SUPPOSE, IN THE
 BUILDING OFFICIAL'S OPINION, THE BUILDING'S CLAIMED
 VALUATION, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION. IN THAT CASE, THE
 PERMIT SHALL BE DENIED UNLESS THE APPLICANT CAN SHOW
 DETAILED QUANTITY ESTIMATES AND BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE BUILDING
 OFFICIAL'S APPROVAL. FOR PERMITTING PURPOSES, THE
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD, AND PROFIT, EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS POSTED BY
 INTERNATIONAL CODE CONGRESS. THE BUILDING OFFICIAL'S
 FINAL BUILDING PERMIT VALUATION SHALL BE SET PER THE
 WPB AMENDMENTS TO THE FBC SEC. 109.3 BUILDING PERMIT
 VALUATIONS.
  
 7. PLEASE PROVIDE THE TYPE OF GAS (LP OR NATURAL) PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER THE 2020 FBC FG SEC. 402.2 OR 2020 FBC
 RES. SEC. G2413.2.
  
 9. PLEASE LIST EACH APPLIANCE'S BTU LOAD AND THE TOTAL
 BTU LOAD ON THE SYSTEM. THE BTU LOAD OF THE EXISTING
 GAS SYSTEM MUST BE ADDED TO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS SIZED
 CORRECTLY. IF UNDERSIZED, THE EXISTING SYSTEM MUST BE
 REDONE TO ENSURE A SAFE OPERATING SYSTEM PER THE 2020
 FBC RES. SECS. G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
  
 10. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND SYSTEM PER THE 2020 FBC RES.
 SEC. G2413.4.1.
  
 11. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR GAS RANGE EQUIPMENT TO
 VERIFY COMPLIANCE, AND GAS APPLIANCES SHALL BE LISTED
 AND LABELED PER THE 2020 FBC RES. SEC. G2408.1.
  
 12. PLEASE SUBMIT A COPY OF THE SIZING TABLE USED IN
 THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH
 SETS OF PLANS LISTING THE SIZING TABLES FROM GAS CODES
 OR ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM
 PER THE 2020 FBC RES. SEC. G2413.3.
  
 13. PLEASE SHOW AND LABEL UNION IN FRONT OF REGULATOR
 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC G2421.2.
  
 14. PLEASE SHOW AND LABEL THE SHUTOFF VALVES ON GAS
 ISOMERIC. PLEASE NOTE THAT THE STOVE'S VALVE SHALL BE
 ACCESSIBLE WITHOUT MOVING THE UNIT PER THE 2020 FBC
 RES. SEC. G2401.1.3.
  
 15. PLEASE SHOW AND LABEL DRIP LEG ON EQUIPMENT
 INSTALLED, EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD
 GRILLS PER THE 2020 FBC RES. SEC. G2419.2.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-07-16 Cont ID  
Sent By lcrespo Date 2021-07-16 Time 12:17 Rev Time 0.00
Received By lcrespo Date 2021-06-22 Time 12:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-06-03 Cont ID  
Sent By jleahy Date 2021-06-03 Time 07:19 Rev Time 0.00
Received By jleahy Date 2021-05-03 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-15 Cont ID  
Sent By lmarchan Date 2021-04-15 Time 08:37 Rev Time 0.00
Received By lmarchan Date 2021-03-22 Time 07:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-02 Cont ID  
Sent By lmarchan Date 2021-03-02 Time 13:38 Rev Time 0.00
Received By lmarchan Date 2021-01-22 Time 08:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-04 Cont ID  
Sent By equinone Date 2020-12-04 Time 15:41 Rev Time 0.00
Received By lmarchan Date 2020-11-06 Time 14:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-07-21 Cont ID  
Sent By lmarchan Date 2021-07-21 Time 11:23 Rev Time 0.00
Received By lmarchan Date 2021-07-16 Time 12:31 Sent To  
Notes
2021-07-20 13:56:22RECEIPT MU-2021-35103 - $1945.04 - PAID
2021-07-16 12:31:107/16/21 EMAILED IMPACT FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By cthroop Date 2020-11-19 Time 12:53 Rev Time 0.00
Received By cthroop Date 2020-11-19 Time 12:53 Sent To  
Notes
2020-11-19 12:54:19PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-05-12 Cont ID  
Sent By medwards Date 2021-05-12 Time 16:06 Rev Time 0.00
Received By medwards Date 2021-05-12 Time 15:52 Sent To  
Notes
2021-05-12 16:07:27APPROVED WITH PRIVISO:
  
 THE BEDROOM MUST HAVE A RETURN AIR PATH BACK TO THE
 AHU. NOTE: IT SHOULD NOT PASS THROUGH THE BATHROOM. FBC
 RES M1602.3 & M1602.2(4)
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-03-31 Cont ID  
Sent By medwards Date 2021-03-31 Time 15:53 Rev Time 0.00
Received By medwards Date 2021-03-31 Time 15:53 Sent To  
Notes
2021-03-31 15:54:421ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20110119
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A MECHANICAL EQUIPMENT SIZING
 CALCULATION TO SHOW THAT THE EXISTING EQUIPMENT IS
 SIZED LARGE ENOUGH TO SUPPORT THE ADDITIONAL LOAD OF
 THE ADDED SQUARE FOOTAGE. FBC EC C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-02-09 Cont ID  
Sent By medwards Date 2021-02-09 Time 08:51 Rev Time 0.00
Received By medwards Date 2021-02-09 Time 08:30 Sent To  
Notes
2021-02-09 08:52:44PLEASE ADDRESS ORIGINAL MECHANICAL REVIEW COMMENTS
 LISTED BELOW.
  
  
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110119
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
  
 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING FOR THIS
 ADDITION TO THE EXISTING EQUIPMENT. PLEASE SHOW THAT
 THE EXISTING EQUIPMENT IS SIZED TO HANDLE THE
 ADDITIONAL LOAD. FBC EC R403.7.1
  
 3) PLEASE SHOW RETURN AIR PATH FROM NEW BEDROOM BACK TO
 THE EXISTING AHU. FBC RES M1602.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-09 Cont ID  
Sent By medwards Date 2020-11-09 Time 10:59 Rev Time 0.00
Received By medwards Date 2020-11-09 Time 10:44 Sent To  
Notes
2020-11-09 11:03:311ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110119
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
  
 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING FOR THIS
 ADDITION TO THE EXISTING EQUIPMENT. PLEASE SHOW THAT
 THE EXISTING EQUIPMENT IS SIZED TO HANDLE THE
 ADDITIONAL LOAD. FBC EC R403.7.1
  
 3) PLEASE SHOW RETURN AIR PATH FROM NEW BEDROOM BACK TO
 THE EXISTING AHU. FBC RES M1602.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-03-24 Cont ID  
Sent By lcrespo Date 2021-03-24 Time 10:14 Rev Time 0.00
Received By lcrespo Date 2021-03-24 Time 09:51 Sent To  
Notes
2021-03-24 10:14:0503/24/21 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING RISER DIAGRAM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL
 PLUMBING.
 NO P-1 FOUND
  
 2. NOTED.
  
 3. DONE.
  
 4. DONE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-02-10 Cont ID  
Sent By lcrespo Date 2021-02-10 Time 10:26 Rev Time 0.00
Received By lcrespo Date 2021-02-10 Time 10:16 Sent To  
Notes
2021-02-10 10:31:1702/10/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING RISER DIAGRAM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL
 PLUMBING.
  
 2. THE GAS HEATER IS IN A SEPARATE BUILDING ACCORDING
 TH THE NEW GAS DRAWING AND IF IT GOING TO HAVE LINE TO
 THE NEW STRUCTURE PLEASE PROVIDE VERBIAGE ON PLAN PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 3. PIPES NOT IN CONDITION SPACE RUNNING TO THE NEW
 STRUCTURE NEED TO BE INSULATED WITH A MINIMUM R-3 PER
 THE 2017 FBC SEC. RE 403.5.3.
  
 4. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By lcrespo Date 2020-11-19 Time 09:45 Rev Time 0.00
Received By lcrespo Date 2020-11-19 Time 09:27 Sent To  
Notes
2020-11-19 09:46:4411/19/20 1STPLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING RISER DIAGRAM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL
 PLUMBING.
  
 2. PLEASE PROVIDE A SOURCE OF HOT WATER AND THE
 LOCATION OF CONNECTION PER THE 2017 FBC SEC. FBC R
 2722.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2020-11-19 Cont ID  
Sent By cthroop Date 2020-11-19 Time 12:50 Rev Time 0.00
Received By cthroop Date 2020-11-19 Time 12:10 Sent To  
Notes
2020-11-19 12:50:19EXISTING ROOF. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-05-26 Cont ID  
Sent By cthroop Date 2021-05-26 Time 17:08 Rev Time 0.00
Received By cthroop Date 2021-05-26 Time 15:47 Sent To  
Notes
2021-05-26 17:08:54SEE FRONT SCREEN NOTE. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-22 Cont ID  
Sent By equinone Date 2021-03-22 Time 09:17 Rev Time 0.00
Received By equinone Date 2021-03-22 Time 09:16 Sent To  
Notes
2021-03-22 09:18:39PAPER DRAWINGS, ENERGY CALCULATONS HAVE ORIGINAL SEAL
 AND SIGNATURE. ROUTED TO STORAGE. EQ

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-02-09 Cont ID  
Sent By medwards Date 2021-02-09 Time 08:54 Rev Time 0.00
Received By medwards Date 2021-02-09 Time 08:54 Sent To  
Notes
2021-02-09 08:55:27PLEASE ADDRESS ORIGINAL SIGNATURE REVIEW COMMENTS
 LISTED BELOW.
  
 DESIGNER OF THE DRAWINGS MUST DIGITSLLY SIGN AND SEAL
 THE DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-09 Cont ID  
Sent By medwards Date 2020-11-09 Time 11:06 Rev Time 0.00
Received By medwards Date 2020-11-09 Time 11:05 Sent To  
Notes
2020-11-09 11:08:17DESIGNER OF THE DRAWINGS MUST DIGITSLLY SIGN AND SEAL
 THE DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2021-07-15 Cont ID  
Sent By kalexand Date 2021-07-15 Time 15:53 Rev Time 0.00
Received By kalexand Date 2021-07-15 Time 15:52 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2021-06-02 Cont ID  
Sent By kalexand Date 2021-06-02 Time 17:05 Rev Time 0.00
Received By kalexand Date 2021-06-02 Time 17:05 Sent To I
Notes
2021-06-02 17:06:34PREVIOUS ZONING COMMENTS NOT ADDRESSED.

Review Stop Z ZONING
Rev No 3 Status F Date 2021-04-14 Cont ID  
Sent By kalexand Date 2021-04-14 Time 08:10 Rev Time 0.00
Received By kalexand Date 2021-04-14 Time 08:10 Sent To I
Notes
2021-04-14 08:14:38ZONING PLAN REVIEW
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE ILLUSTRATE THE FOLLOWING ON THE SURVEY:
 - LOCATION OF THE PROPOSED ADDITION/WORK.
 - SETBACK DIMENSIONS FROM ANY EXTERIOR IMPROVEMENTS TO
 ALL ADJACENT PROPERTY LINES.
  
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-03-01 Cont ID  
Sent By kalexand Date 2021-03-01 Time 08:34 Rev Time 0.00
Received By kalexand Date 2021-03-01 Time 08:34 Sent To I
Notes
2021-03-01 08:45:35ZONING PLAN REVIEW
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PREVIOUS ZONING COMMENTS NOT ADRESSED. PROVIDE A
 PROPERTY SUREVEY INDICATIONG LOCATION OF PROPOSED WORK
 AS WELL AS THE SETBACK DIMENSIONS FROM ANY EXTERIOR
 IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES. PURSUANT
 TO THE ZLDR, SECTION 94-72(A)(2): SINGLE-FAMILY LOW
 DENSITY (SF7) RESIDENTIAL DISTRICT - MINIMUM SETBACKS
 FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
  A. FRONT: 25 FEET;
  
  B. CORNER: 12.5 FEET;
  
  C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH,
 WHICHEVER IS LESS;
  
  D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-04 Cont ID  
Sent By kalexand Date 2020-12-04 Time 13:56 Rev Time 0.00
Received By kalexand Date 2020-12-04 Time 13:56 Sent To I
Notes
2020-12-04 13:59:03ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE A PROPERTY SURVEY INDICATING LOCATION OF
 PROPOSED WORK AND SETBACKS FROM PROPERTY LINE.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  