Plan Review Details - Permit 20110110
Plan Review Stops For Permit 20110110
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-04-29 Cont ID  
Sent By cpuell Date 2021-04-29 Time 12:18 Rev Time 0.00
Received By cpuell Date 2021-04-29 Time 12:18 Sent To  
Notes
2021-04-29 12:19:31ADDRESS CHANGED FRO 201 BLOOMFIELD DR TO 6255
 WASHINGTON RD. GUEST HOUSE CHANGED TO FITNESS CABANA
 ACCESSORY UNIT NO LONGER NEEDS SECOND ADDRESS.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-04-20 Cont ID  
Sent By cpuell Date 2021-04-20 Time 16:42 Rev Time 0.00
Received By cpuell Date 2021-04-20 Time 16:42 Sent To  
Notes
2021-04-20 16:43:42COMMENTS NOT ADDRESSED:
 PRIMARY ADDRESS NEEDS TO BE CHANGED DUE TO THE NEW
 FOOTPRINT OF THE PROPOSED PROPERTY AND THE CITY'S
 CENTERLINES. THE GUEST HOUSE WILL ALSO NEED ITS OWN
 ADDRESS. PLEASE CONTACT [email protected] TO DISCUSS
 ADDRESSING ALLOCATIONS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-11-18 Cont ID  
Sent By cpuell Date 2020-11-18 Time 09:23 Rev Time 0.00
Received By cpuell Date 2020-11-18 Time 09:23 Sent To  
Notes
2020-11-18 09:28:33PRIMARY ADDRESS NEEDS TO BE CHANGED DUE TO THE NEW
 FOOTPRINT OF THE PROPOSED PROPERTY AND THE CITY'S
 CENTERLINES. THE GUEST HOUSE WILL ALSO NEED ITS OWN
 ADDRESS. PLEASE CONTACT [email protected] TO DISCUSS
 ADDRESSING ALLOCATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-06-25 Cont ID  
Sent By pvalenti Date 2021-06-25 Time 14:31 Rev Time 0.00
Received By pvalenti Date 2021-06-25 Time 14:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-06-21 Cont ID  
Sent By pvalenti Date 2021-06-21 Time 11:15 Rev Time 0.00
Received By pvalenti Date 2021-06-21 Time 11:15 Sent To  
Notes
2021-06-21 11:19:55****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE THE PRODUCT APPROVAL
 NUMBERS TO EACH OPENING LETTER DESIGNATION ON
 WINDOW/DOOR SCHEDULE LOCATED AT SHEET 3 OF 14.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-17 Cont ID  
Sent By pvalenti Date 2021-06-17 Time 15:50 Rev Time 0.00
Received By pvalenti Date 2021-06-17 Time 13:58 Sent To  
Notes
2021-06-17 16:49:38****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW DENIED:
  
 NOTE: THE ITEMS LISTED BELOW ARE THE ITEMS THAT STILL
 NEED TO BE ADDRESSED FROM LAST REVIEW:
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GUEST HOUSE.
 PRO-RATE THE VALUES AS FOLLOWS: MAIN HOUSE $531, 076.00
 AND GUEST HOUSE $93, 924.00.
 SUBMIT THE GUEST HOUSE PERMIT TO
 [email protected]. PLANS FOR BOTH STRUCTURES WILL
 REMAIN UNDER 20110110.
  
 3) FBC B 1803.1, PROVIDE A SOILS REPORT, THIS REPORT
 NEEDS TO INCLUDE A DESIGN PROFESSIONAL APPROVED
 GEO-TECHNICAL INVESTIGATION REPORT.
  
 5) FBC B 107.2/FBC EC 101.5.1.1.2, SUBMIT A COMPLETED
 ENERGY (RESIDENTIAL) FORM R405.
  
 8) FBC B 107.2, PROVIDE THE PRODUCT APPROVALS/NOA'S
 (REVIEW STAMPED BY DESIGNER OF RECORD) FOR ALL WINDOWS
 & DOORS TO BE INSTALLED. ALSO ON SHEET 3 OF 14, PROVIDE
 THE PRODUCT APPROVAL/NOA AT EACH OPENING DESIGNATION ON
 OPENING SCHEDULE FOR WINDOWS AND DOORS.
  
 9) FBC B 107.3.4.1, FOR ALL PRODUCT APPROVALS AND
 PRODUCT SUBMITTALS TO BE DEFERRED, PROVIDE A LIST OF
 THEM ON CONTRACT DRAWINGS INCLUDING: WINDOWS/DOORS AND
 ROOFING MATERIALS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-04 Cont ID  
Sent By cthroop Date 2021-05-04 Time 14:12 Rev Time 0.00
Received By cthroop Date 2021-05-03 Time 15:02 Sent To  
Notes
2021-05-04 14:24:24PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
 A SEPERATE PERMIT IS REQUIRED FOR THE GUEST HOUSE.
 PRO-RATE THE VALUES AS FOLLOWS: MAIN HOUSE $531,076 AND
 GUEST HOUSE $93,924.
 SUBMIT THE GUEST HOUSE PERMIT APPLICATION TO -
 [email protected]
 PLANS FOR BOTH STRUCTURES WILL REMAIN UNDER 20110110 -
 MAIN HOUSE.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1. PROVIDE A SITE DRAINAGE PLAN.
  
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 2. PROVIDE THE FINISHED FLOOR ELEVATION.
  
 FINISH FLOOR ELEVATION NON-FLOOD ZONE
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 3. PROVIDE A SOILS REPORT.
  
 GEOTECHNICAL INVESTIGATIONS
 FBC 1803.1 GENERAL. GEOTECHNICAL INVESTIGATIONS SHALL
 BE CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 4.NOTICE ONLY: PALM BEACH COUNTY IMPACT FEES REQUIRED.
 SEE COMMENTS UNDER IMPACT FEE REVIEW.
  
 5. STATE R VALUE OF 3/4" RIGID WALL INSULATION ON PLAN.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 6. COMPLETE
  
 7. COMPLETE
  
 8. DESINER SHALL SELECT MODEL OF SGD TO BE INSTALLED.
 NOTICE:
 OPENING PROTECTION REQUIRED IF N0N-IMPACT RATED DOOR
 SELECTED.
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 9. NOTICE ONLY: SUBMIT A ROOFING SUB-PERMIT AND
 REQUIRED PRODUCT APPROVALS OR A PROVISO WILL BE PLACED
 ON THE PLAN "SEPERATE ROOFING PERMIT REQUIRED.".
  
 PERMITS - 105.1 REQUIRED.
  
 PROVISO: PROVIDE ICC-ES REPORT FOR SPRAY FOAM
 INSULATION TO CITY INSPECTOR.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 ***THESE COMMENTS APPLY TO BOTH STRUCTURES AND WILL BE
 TRANSFERRED TO NEW GUEST HOUSE PERMIT***
  
 ***REDLINED ADDRESS ON ALL PLAN PAGES PER SH***
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-18 Cont ID  
Sent By cthroop Date 2020-11-18 Time 09:59 Rev Time 0.00
Received By cthroop Date 2020-11-18 Time 06:15 Sent To  
Notes
2020-11-18 11:03:22PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
 A SEPERATE PERMIT IS REQUIRED FOR THE GUEST HOUSE.
 PRO-RATE THE VALUES AS FOLLOWS: MAIN HOUSE $531,076 AND
 GUEST HOUSE $93,924.
 SUBMIT THE GUEST HOUSE PERMIT APPLICATION TO -
 [email protected]
 PLANS FOR BOTH STRUCTURES WILL REMAIN UNDER 20110110 -
 MAIN HOUSE.
  
 1. PROVIDE A SITE PLAN. DRAINAGE/SURVEY
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
  
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 2. PROVIDE THE FINISHED FLOOR ELEVATION.
  
 FINISH FLOOR ELEVATION ? NON-FLOOD ZONE
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 3. PROVIDE A SOILS REPORT.
  
 GEOTECHNICAL INVESTIGATIONS
 FBC 1803.1 GENERAL. GEOTECHNICAL INVESTIGATIONS SHALL
 BE CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 4.NOTICE ONLY: PALM BEACH COUNTY IMPACT FEES REQUIRED.
 SEE COMMENTS UNDER IMPACT FEE REVIEW.
  
 5. STATE R VALUE OF 3/4" RIGID WALL INSULATION ON PLAN.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 6. PROVIDE AN ENERGY SUBMITTAL.
  
 PROVIDE ENERGY GAUGE FORM R405 PER SECTION R405.2 FBC
 EC.
  
 7. PROVIDE WINDOW AND DOOR SCHEDULES WITH THE FOLLOWING
 INFORMATION:
 7A) WINDOW SCHEDULE -
 1. ITEM NUMBER
 2. LOCATION ON PLAN
 3. TYPE
 4. MFGR.
 5. MATERIAL
 6. GLASS TREATMENT
 7. ROUGH OPENING
 8. IMPACT RESISTANT Y/N
 9. PRODUCT APPROVAL NUMBER
 10. NOA DESIGN PRESSURE RATING
 11. OPENING REQUIRED PRESSURE RATING
 12. EGRESS REQUIRED Y/N
 13. SHUTTER REQUIRED Y/N
 7B) DOOR SCHEDULE
 1. ITEM NUMBER
 2. LOCATION ON PLAN
 3. SIZE
 4. THICKNESS
 5. TYPE
 6. MFGR.
 7. MATERIAL
 8. JAM
 9. ROUGH OPENING
 10. HARDWARE
 11. PRODUCT APPROVAL NUMBER
 12. NOA DESIGN PRESSURE RATING
 13. OPENING REQUIRED PRESSURE RATING
 14. SHUTTER REQUIRED Y/N
  
 8. DESINER SHALL SELECT MODEL OF SGD TO BE INSTALLED.
 NOTICE:
 OPENING PROTECTION REQUIRED IF N0N-IMPACT RATED DOOR
 SELECTED.
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 9. NOTICE ONLY: SUBMIT A ROOFING SUB-PERMIT AND
 REQUIRED PRODUCT APPROVALS OR A PROVISO WILL BE PLACED
 ON THE PLAN "SEPERATE ROOFING PERMIT REQUIRED.".
  
 PERMITS - 105.1 REQUIRED.
  
 PROVISO: PROVIDE ICC-ES REPORT FOR SPRAY FOAM
 INSULATION TO CITY INSPECTOR.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 ***THESE COMMENTS APPLY TO BOTH STRUCTURES AND WILL BE
 TRANSFERRED TO NEW GUEST HOUSE PERMIT***
  
 ***REDLINE ADDRESS PER SH***
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-07 Cont ID  
Sent By equinone Date 2021-06-07 Time 09:06 Rev Time 0.00
Received By equinone Date 2021-06-07 Time 08:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-04-28 Cont ID  
Sent By equinone Date 2021-04-28 Time 10:58 Rev Time 0.00
Received By equinone Date 2021-04-28 Time 09:10 Sent To  
Notes
2021-04-28 10:59:05CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. SEE NEW COMMENTS BELOW
  
 1) THIS PERMIT FALLS UNDER THE FBC 2017 7TH EDITION AND
 NEC 2017. ELECTRICAL DRAWINGS ARE REFERING TO THE NEC
 2011.
 PLEASE UPDATE NOTES TO REFERENCE THE RIGHT CODES. FBC
 107
  
 2) ELECTRICAL DRAWING SHOWS AN EMERGENCY GENERATOR AND
 GENERATOR SWITCH THAT ARE NOT SHOWN ON RISER DIAGRAM.
 PLEASE NOTE THAT THE EMERGENCY GENERATOR REQUIRES A
 SEPARATE SUBMISSION AND SEPARATE ELECTRICAL PERMIT.
 PLEASE ADD NOTE STATING THIS FACT. FBC 107
  
 3) PANELS A AND B ARE NOT LOCATED IN DETACHED
 STRUCTURES. GROUNDING SHALL BE DONE WITH GROUNDING
 EQUIPMENT CONDUCTORS NOT SEPARATE GROUNDING ELECTRODE
 SYSTEMS.
 PLEASE SPECIFY THE SIZE OF THE GROUNDING EQUIPMENT
 CONDUCTORS FOR THOSE FEEDERS. NEC 250
  
 4) DOES THE MDP HAVE A MAIN CIRCUIT BREAKER AND
 BREAKERS FOR FEEDERS TO PANELS A AND B? IF YES, PLEASE
 PROVIDE BREAKER SIZES.
 IF NOT PLEASE CLARIFY HOW FEEDERS TO PANELS A AND B ARE
 PROTECTED? NEC 240
  
 5) GROUNDING NOTES ARE UNREADABLE. PLEASE SUBMIT NEW
 DRAWING WITH READABLE NOTES. FBC 107
  
 6) WHAT IS THE ACTUAL RATING OF THE ELECTRICAL SERVICE?
 THE SERVICE CONDUCTORS SPECIFIED ON RISER DIAGRAM ARE
 FOR A 225 AMPS SERVICE AND MIGHT BE TOO SMALL DEPENDING
 ON THE RATINGS OF THE MDP.
  
 7) SMOKE DETECTORS ARE REQUIRED AS PER FBC RE 2020, 7TH
 EDITION. PLEASE SHOW LOCATION OF ALL SMOKE DETECTORS.
  
 8) PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 ELECTRICAL SERVICE INCLUDING INFORMATION FROM THE POWER
 COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS. NEC 110.9, 110.10; FBC RE E3606.3
  
 9) GFI/WP RECEPTACLES ARE REQUIRED AT FRONT AND BACK OF
 HOUSE. NEC 210.8
  
 10) SEPARATE GFI RECEPTACLE IS REQUIRED IN WASHER/DRYER
 ROOM. NEC 210.8
  
 11) A MINIMUM OF ONE COMMUNICATIONS OUTLET SHALL BE
 PROVIDED AS PER NEC 800.156. PLEASE SHOW LOCATION AND
 ADD TO SYMBOLS.
  
 12) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF
 THE LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL
 HAVE
 AN EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL
 UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAN 65
 LUMENS-PER-WATT?.
 A NOTE WILL SUFFICE. FBC EC R404.1
  
  
 SINCERELY,
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By equinone Date 2020-11-19 Time 15:54 Rev Time 0.00
Received By equinone Date 2020-11-19 Time 15:54 Sent To  
Notes
2020-11-19 15:54:33CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) PLEASE PROVIDE ELECTRICAL DRAWINGS FOR MAIN HOUSE.
 INCLUDE RISER DIAGRAM, PANEL SCHEDULES, POWER AND
 LIGHTING LAYOUT, SYSTEM GROUNDING, SERVICE EQUIPMENT
 AND LOCATION, SMOKE ALARMS, LOAD CALCULATIONS,
 AVAILABLE FAULT CURRENT, NOTES AND SYMBOLS. FBC 107
 2) PLEASE PROVIDE PANEL SCHEDULE FOR GUEST HOUSE. FBC
 107
 3) PLEASE SHOW LOCATION OF DISCONNECTING MEANS FOR
 GUEST HOUSE PANEL.
 4) GUEST HOUSE MUST HAVE GFCI, WP RECEPTACLES ON BACK
 AND FRONT.
 5) FOR MAIN HOUSE PLEASE PROVIDE ARC-FAULT AND GFI
 PROTECTION AS PER FBC RE E3902.
 6) FOR MAIN HOUSE PLEASE PROVIDE TAMPER RESISTANT
 RECEPTACLE AS PER FBC RE E4002.14
 7) PLEASE SHOW WIRING METHOD UTILIZED TO FEED GUEST
 HOUSE. UNDERGROUND INSTALLATION MUST COMPLY WITH NEC
 TABLE 300.5
 8) FOR GUEST HOUSE (DETACHED STRUCTURE) PLEASE SHOW
 COMPLIANCE WITH NEC 250.32
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-11-16 Cont ID  
Sent By lcrespo Date 2020-11-16 Time 16:43 Rev Time 0.00
Received By lcrespo Date 2020-11-16 Time 16:43 Sent To  
Notes
2020-11-16 16:44:06GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-17 Cont ID  
Sent By pvalenti Date 2021-06-17 Time 16:58 Rev Time 0.00
Received By pvalenti Date 2021-06-03 Time 07:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-24 Cont ID  
Sent By ccole Date 2021-05-24 Time 13:00 Rev Time 0.00
Received By ccole Date 2021-04-20 Time 13:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-15 Cont ID  
Sent By lmarchan Date 2020-12-15 Time 08:48 Rev Time 0.00
Received By lmarchan Date 2020-11-05 Time 08:25 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-07-13 Cont ID  
Sent By lmarchan Date 2021-07-13 Time 09:14 Rev Time 0.00
Received By lmarchan Date 2021-06-28 Time 11:19 Sent To  
Notes
2021-07-12 11:19:07RECEIPT - MU-2021-32587 - $546.52 PAID
2021-06-28 15:25:39UPLODED IMPACT FEES QUESTIONNAIRE. EMAILED IMPACT FEE
 OFFICE. CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-18 Cont ID  
Sent By cthroop Date 2020-11-18 Time 09:07 Rev Time 0.00
Received By cthroop Date 2020-11-18 Time 09:06 Sent To  
Notes
2020-11-18 09:07:36IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-06-14 Cont ID  
Sent By medwards Date 2021-06-14 Time 13:33 Rev Time 0.00
Received By medwards Date 2021-06-14 Time 13:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-04-29 Cont ID  
Sent By medwards Date 2021-04-29 Time 14:44 Rev Time 0.00
Received By medwards Date 2021-04-29 Time 13:53 Sent To  
Notes
2021-04-29 14:44:592ND REVIEW FBC-2020 MECHANICAL
 PERMIT-20110110
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS ARE FOR
 201 BLOOMFIELD, THE PERMIT APPLICATION IS FOR 6255
 WASHINGTON RD. PLEASE PRESENT MECHANICAL EQUIPMENT
 SIZING CALCULATIONS THAT HAS THE CORRECT ADDRESS. FBC
 107.2.1
  
 2) PLEASE PROVIDE THE CORRECT ADDRESS ON THE PLANS. FBC
 107.2.1
  
 3) PLEASE SUBMIT MECHANICAL EQUIPMENT SIZING
 CALCULATIONS DESIGNED BY AN ENGINEER OR THE MECHANICAL
 CONTRACTOR THAT HAS OBTAINED THE PERMIT TO INSTALL THIS
 PROJECT.
 A MECHANICAL SUB-PERMIT IS REQUIRED.
 FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
 THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB.
 4) PLEASE SHOW THE DRYER EXHAUST PIPING AND TERMINATION
 LOCATION. FBC RES M1502.3
  
 5) PLEASE SHOW THE CONDENSATION LINES ON THE DRAWINGS
 FOR EACH MECHANICAL SYSTEM AND SHOW THE TERMINATION
 LOCATION. FBC RES M1411.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-07 Cont ID  
Sent By medwards Date 2020-11-07 Time 07:18 Rev Time 0.00
Received By medwards Date 2020-11-07 Time 07:18 Sent To  
Notes
2020-11-07 07:18:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110110
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR BOTH, THE
 MAIN HOUSE AND GUEST HOUSE. FBC EC 101.5.1.1.2
  
 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS IN ACCORDANCE WITH MANUAL J FOR BOTH THE
 MAIN HOUSE AND THE GUEST HOUSE. FBC RES M1401.3
  
 3) PROVIDE CODE COMPLIANT MECHANICAL PLANS FOR BOTH THE
 MAIN HOUSE AND THE GUEST HOUSE. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-04-21 Cont ID  
Sent By lcrespo Date 2021-04-21 Time 14:42 Rev Time 0.00
Received By lcrespo Date 2021-04-21 Time 14:42 Sent To  
Notes
2021-04-21 14:43:2204/21/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-11-16 Cont ID  
Sent By lcrespo Date 2020-11-16 Time 16:42 Rev Time 0.00
Received By lcrespo Date 2020-11-16 Time 16:42 Sent To  
Notes
2020-11-16 16:53:5111/16/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL
 PLUMBING.
  
 3. A GAS RANGE IS SHOWN ON PLANS AND NOT NOTED, A
 SEPARATE GAS PERMIT WILL BE REQUIRED WITH A NARRATIVE
 OF THE SCOPE OF WORK OR PROVIDE AT THIS TIME FOR REVIEW
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THE WASHING MACHINE IS STACKABLE IN THE GUEST HOUSE
 PLEASE SHOW THE LOCATION OF THE VALVE ACCESS, THE
 WASHING MACHINE SHUT OFF VALVES SHALL BE ACCESSIBLE
 WITHOUT MOVING OF THE UNITS AND WITHIN REACH PER THE
 2017 FBC SEC. R 2903.9.3.
  
 5. THE GUEST HOUSE SHOWS A GAS WATER HEATER BUT THE
 MAIN HOUSE DOES NOT SHOW ANY WATER HEATER PLEASE
 CLARIFY IF THERE ARE TWO OR JUST ON THE UNIT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 6. THIS IS MULTI-FAMILY DWELLINGS AND WATER USERS WILL
 BE REQUIRED TO INSTALL A BACKFLOW PREVENTION ASSEMBLY
 AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY
 REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF HAZARD
 POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS CONNECTION CONTROL MANUAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2021-06-21 Cont ID  
Sent By pvalenti Date 2021-06-21 Time 11:20 Rev Time 0.00
Received By pvalenti Date 2021-06-21 Time 11:20 Sent To  
Notes
2021-06-21 11:22:13 
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ROOFING REVIEW APPROVED WITH PROVISO:
  
 A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ROOF WORK.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2021-06-17 Cont ID  
Sent By pvalenti Date 2021-06-17 Time 16:55 Rev Time 0.00
Received By pvalenti Date 2021-06-17 Time 13:59 Sent To  
Notes
2021-06-17 16:57:58****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ROOFING REVIEW DENIED:
  
 FBC B 107, PLEASE PROVIDE ROOFING INFORMATION INCLUDING
 SYSTEM TO BE USED AND MATERIALS TO BE USED (ROOFING
 SUB-PERMIT IS REQUIRED).

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-05-04 Cont ID  
Sent By cthroop Date 2021-05-04 Time 14:25 Rev Time 0.00
Received By cthroop Date 2021-05-03 Time 15:02 Sent To  
Notes
2021-05-04 14:27:26PLAN REVIEW / ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SUBMIT A ROOFING SUB-PERMIT APPLICATION AND PRODUCT
 APPROVALS FOR ROOFING SYSTEM COMPONENTS FOR REVIEW OR A
 PROVISO WILL BE POSTED ON PLANS FOR A SEPERATE ROOFING
 PERMIT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 NEW COMMENT:
  
 2. PRODUCT EVALUATION REPORT FOR ROOF TILE SUBMITTED
 FOR REVIEW. PROVIDE COVER PAGE OF PRODUCT APPROVAL.
 . PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER
 SHEETS FOR FL12328-R9 AND FL16709-R7; THE COVER SHEET
 PROVIDES THE APPROVAL NUMBER, CODE VERSION, AND STATUS,
 FBC R 301.
 (COVER SHEETS ARE NOT REQUIRED FOR MIAMI DADE NOAS.)
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-11-18 Cont ID  
Sent By cthroop Date 2020-11-18 Time 09:09 Rev Time 0.00
Received By cthroop Date 2020-11-18 Time 06:16 Sent To  
Notes
2020-11-18 09:12:58PLAN REVIEW / ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SUBMIT A ROOFING SUB-PERMIT APPLICATION AND PRODUCT
 APPROVALS FOR ROOFING SYSTEM COMPONENTS FOR REVIEW OR A
 PROVISO WILL BE POSTED ON PLANS FOR A SEPERATE ROOFING
 PERMIT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-17 Cont ID  
Sent By pvalenti Date 2021-06-17 Time 16:53 Rev Time 0.00
Received By pvalenti Date 2021-06-17 Time 13:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-04 Cont ID  
Sent By cthroop Date 2021-05-04 Time 14:24 Rev Time 0.00
Received By cthroop Date 2021-05-03 Time 15:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-18 Cont ID  
Sent By cthroop Date 2020-11-18 Time 09:06 Rev Time 0.00
Received By cthroop Date 2020-11-18 Time 06:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-05-21 Cont ID  
Sent By kalexand Date 2021-05-21 Time 10:41 Rev Time 0.00
Received By kalexand Date 2021-05-21 Time 10:41 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-11 Cont ID  
Sent By kalexand Date 2020-12-11 Time 12:30 Rev Time 0.00
Received By kalexand Date 2020-12-11 Time 12:30 Sent To I
Notes
2020-12-11 13:22:51ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ACCESSORY DWELLING UNIT NOT PERMITTED IN
 SINGLE-FAMILY LOW DENSITY (SF7) ZONING DISTRICTS.
 PURSUANT TO ZLDR SEC. 94-303 ACCESSORY APARTMENTS ARE
 ONLY PERMITTED IN SINGLE-FAMILY HIGH-DENSITY (SF14)
 RESIDENTIAL ZONING DISTRICTS.
  
 2. FRONT SETBACK REQUIREMENT NOT MET. PURSUANT TO ZLDR
 ARTICLE XIX LOT DEFINITIONS 4.A. LOT LINE, FRONT, MEANS
 THE LINE SEPARATING A LOT FROM A STREET, ROAD OR OTHER
 PUBLIC OR PRIVATE RIGHT-OF-WAY. AT ALL CORNER LOTS, THE
 FRONT LOT LINE SHALL BE THE PUBLIC STREET RIGHT-OF-WAY
 LINE WHICH POSSESSES THE NARROWEST LENGTH. THE OTHER
 PUBLIC STREET RIGHT-OF-WAY SHALL BE CONSIDERED THE
 CORNER LOT LINE.
  
 3. PROVIDE THE TOTAL HEIGHT OF THE PROPOSED HOME ON AN
 ELEVATION PLAN. PURSUANT TO THE ZLDR ARTICLE XIX HEIGHT
 OF STRUCTURE MEANS THE VERTICAL DISTANCE FROM THE
 AVERAGE ELEVATION OF THE FINISHED GRADE OF THE
 STRUCTURE TO THE HIGHEST PORTION OF THE STRUCTURE,
 SUBJECT TO SPECIFIED HEIGHT REQUIREMENTS OF THIS
 CHAPTER. FOR BUILDINGS, THE HEIGHT SHALL BE MEASURED AS
 THE VERTICAL DISTANCE FROM THE AVERAGE ELEVATION OF THE
 FINISHED GRADE OF THE BUILDING TO THE HIGHEST POINT OF
 THE TOP OF THE STRUCTURE OF A FLAT ROOF, OR TO THE DECK
 LINE OF A MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL
 BETWEEN EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL
 ROOFS.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  