Plan Review Details - Permit 20110059
Plan Review Stops For Permit 20110059
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-10 Cont ID  
Sent By shill Date 2020-12-10 Time 14:58 Rev Time 0.00
Received By shill Date 2020-12-10 Time 14:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-09 Cont ID  
Sent By jwitmer Date 2020-11-09 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2020-11-09 Time 10:46 Sent To  
Notes
2020-11-09 11:35:27WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110059
 ADD: 7176 GRASSY BAY DR.
 CONT: O/B MICHAEL MAHOVCH
 TEL: 561-309-9438
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. NOV. 09TH/2020
 ACTION: DENIED
  
 1) FLOOR PLAN:
 1A) THE SUBMITTED FLOOR PLAN DOES NOT PROVIDE WHO THE
 DESIGNER OF THE FLOOR PLAN IS? OWNER BUILDERS (O/B)
 HAVE THE SAME REQUIREMENTS AS CONTRACTORS WHEN IT COMES
 TO DESIGNING PLANS. PLEASE LIST YOURSELF AS THE PLAN
 DESIGNER, PLEASE PRINT YOUR NAME AND SIGN YOUR NAME AND
 DATE THE PLAN.
 CERTIFICATION BY CONTRACTOR.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 1B) THE FLOOR PLAN DOES PROVIDE THE DISTANCE FROM THE
 CORNER OF BUILDING, AND THE DISTANCE BETWEEN OPENINGS
 AND IDENTIFIES OPENINGS BY NUMBER. WHAT THE PLAN FAILS
 TO PROVIDE IN INFORMATION IS THE TYPE OF OPENING
 (SINGLE HUNG WINDOW / IF ONE OR MORE WINDOWS IN THE
 OPENING), AND THE OVERALL SIZE OF THE OPENING AND IN
 INCHES, WIDTH X HEIGHT.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY AND OR
 QUANTITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL
 CODES.
  
 1C) PLEASE MAKE A NOTE ON YOUR FLOOR PLAN STATING THERE
 IS TO BE A WINDOW BUCK INSPECTION BEFORE YOU INSTALL
 THE REPLACEMENT WINDOWS. YOU MUST SCHEDULE ALL
 INSPECTION OVER THE AUTOMATED SYSTEM ONE DAY IN ADVANCE
 OF THE DAY YOU REQUEST.
  
 2)YOU SHOULD HAVE A SHEET LISTING EACH OPENING,
 IDENTIFICATION OF OPENING, SIZES, AND ASSOCIATED
 PRESSURES. PLEASE LIST THE PRESSURES IN VASD. NO WIND
 DESIGN CRITERIA WERE PROVIDED.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 3) PLEASE NOTE ALL 3 PRODUCT APPROVALS WERE LOADED INTO
 ONE DOCUMENT FOLDER. EACH PRODUCT APPROVAL NEEDS TO BE
 LOADED INTO ITS OWN DOCUMENT FOLDER. PLEASE ALSO NOTE
 THE PRODUCT APPROVAL FOUND ON SHEET 29 OF 46 DOES NOT
 HAVE THE COVERSHEETS IDENTIFYING IT, THE DAME HOLDS
 TRUE FOR THE PRODUCT APPROVAL FOUND ON SHEET 37 OF 46.
 107.2.1.3. QUALITY OF PLANS. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR
 THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 4) IN ALL 3 SUBMITTED PRODUCT APPROVALS NOTHING WAS
 MARKED IDENTIFYING THE PRODUCT TO BE INSTALLED. PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-09 Cont ID  
Sent By jwitmer Date 2020-11-09 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2020-11-06 Time 10:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-12-10 Cont ID  
Sent By shill Date 2020-12-10 Time 14:58 Rev Time 0.00
Received By shill Date 2020-12-10 Time 14:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-09 Cont ID  
Sent By jwitmer Date 2020-11-09 Time 11:42 Rev Time 0.00
Received By jwitmer Date 2020-11-09 Time 10:46 Sent To  
Notes
2020-11-09 11:40:40THE SUBMITTED FLOOR PLAN DOES NOT PROVIDE WHO THE
 DESIGNER OF THE FLOOR PLAN IS? OWNER BUILDERS (O/B)
 HAVE THE SAME REQUIREMENTS AS CONTRACTORS WHEN IT COMES
 TO DESIGNING PLANS. PLEASE LIST YOURSELF AS THE PLAN
 DESIGNER, PLEASE PRINT YOUR NAME AND SIGN YOUR NAME AND
 DATE THE PLAN.
 CERTIFICATION BY CONTRACTOR.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
  