Plan Review Details - Permit 20110051
Plan Review Stops For Permit 20110051
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-02-22 Cont ID  
Sent By ccole Date 2021-02-22 Time 15:19 Rev Time 0.00
Received By ccole Date 2021-02-22 Time 15:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-01-12 Cont ID  
Sent By abelisle Date 2021-01-12 Time 07:10 Rev Time 0.00
Received By abelisle Date 2021-01-12 Time 06:24 Sent To I
Notes
2021-01-12 07:10:053RD REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20110051
 1/12/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR THE FIRE PIT TO VERIFY
 COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2408.1.
 2) THE FIRE PIT SPECS PROVIDED SPECIFY LP GAS ONLY!
 3) 3RD REQUEST-THE $1200.00 VALUE ON THE APPLICATION
 APPEARS TO BE LOW FOR THE SCOPE OF THE PROJECT. PLEASE
 PROVIDE A COPY OF A SIGNED CONTRACT AND/OR ESTIMATES
 AND INVOICES TO VERIFY THE COSTS OF LABOR, MATERIALS,
 EQUIPMENT, APPLIANCES, SITE WORK AND DESIGN FEES-
 SECTION 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-11-19 Cont ID  
Sent By ccole Date 2020-11-19 Time 13:53 Rev Time 0.00
Received By ccole Date 2020-11-19 Time 12:23 Sent To  
Notes
2020-11-19 13:53:502ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20110051
 11/119/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS #2 & 5 FROM THE 1ST REVIEW PRINTED BELOW STILL
 EXIST- PLEASE COMPLY.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GRILL
 AND FIREPIT HIGHLIGHTED OR MARKED UP TO SHOW THE ANSI
 STANDARD LISTINGS, AND THE BTUH LOADS AND INPUT
 PRESSURES- SECTION G2404.3 & G2408.1 FBC RES.
  
 5) THE $1200.00 VALUE ON THE APPLICATION APPEARS TO BE
 LOW FOR THE SCOPE OF THE PROJECT. PLEASE PROVIDE A COPY
 OF A SIGNED CONTRACT AND/OR ESTIMATES AND INVOICES TO
 VERIFY THE COSTS OF LABOR, MATERIALS, EQUIPMENT,
 APPLIANCES, SITE WORK AND DESIGN FEES- SECTION 109.3
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-11-10 Cont ID  
Sent By ccole Date 2020-11-10 Time 16:50 Rev Time 0.00
Received By ccole Date 2020-11-10 Time 12:30 Sent To  
Notes
2020-11-10 16:51:091ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20110051
 11/10/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SURVEY OR SITE PLAN DRAWING SHOWING THE
 LOCATIONS OF THE NEW GRILL AND FIREPIT, AND THE
 REQUIRED INSTALLATION CLEARANCES FROM PROPERTY LINES,
 COMBUSTIBLE CONSTRUCTION, AND AIR INTAKES AND OPENINGS
 INTO THE BUILDING- SECTION 107.2.1 WPB AND SECTION
 R303.5.1 FBC RES.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GRILL
 AND FIREPIT HIGHLIGHTED OR MARKED UP TO SHOW THE ANSI
 STANDARD LISTINGS, AND THE BTUH LOADS AND INPUT
 PRESSURES- SECTION G2404.3 & G2408.1 FBC RES.
  
 3) SUBMIT MARKED UP OR HIGHLIGHTED SPECS FOR THE
 REGULATORS SHOWING THE SELECTED MODELS, THE MAX INLET
 AND OUTLET SIZES AND PRESSURES, SPRING DATA, AND
 ORIFICE SIZES- SECTION G2421.1 & G2421.2 FBC RES.
  
 4) PLEASE LIST THE PIPE SIZING TABLES ON THE RISER-
 SECTION G2413.3 FBC RES.
  
 5) THE $1200.00 VALUE ON THE APPLICATION APPEARS TO BE
 LOW FOR THE SCOPE OF THE PROJECT. PLEASE PROVIDE A COPY
 OF A SIGNED CONTRACT AND/OR ESTIMATES AND INVOICES TO
 VERIFY THE COSTS OF LABOR, MATERIALS, EQUIPMENT,
 APPLIANCES, SITE WORK AND DESIGN FEES- SECTION 109.3
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-02-22 Time   Rev Time 0.00
Received By lmarchan Date 2021-02-15 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-01-26 Time   Rev Time 0.00
Received By ccarvaja Date 2021-01-08 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-11-19 Time   Rev Time 0.00
Received By lmarchan Date 2020-11-18 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-11-10 Time   Rev Time 0.00
Received By lmarchan Date 2020-11-06 Time 16:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status N Date 2021-02-22 Cont ID  
Sent By ccole Date 2021-02-22 Time 15:19 Rev Time 0.00
Received By ccole Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-01-12 Cont ID  
Sent By abelisle Date 2021-01-12 Time 06:29 Rev Time 0.00
Received By abelisle Date 2021-01-12 Time 06:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-11-19 Cont ID  
Sent By ccole Date 2020-11-19 Time 13:46 Rev Time 0.00
Received By ccole Date 2020-11-19 Time 12:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-11-10 Cont ID  
Sent By ccole Date 2020-11-10 Time 16:52 Rev Time 0.00
Received By ccole Date 2020-11-10 Time 12:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-02-22 Cont ID  
Sent By ccole Date 2021-02-22 Time 15:20 Rev Time 0.00
Received By ccole Date 2021-02-22 Time 15:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-26 Cont ID  
Sent By ccole Date 2021-01-26 Time 12:43 Rev Time 0.00
Received By ccole Date 2021-01-26 Time 12:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-10 Cont ID  
Sent By ccole Date 2020-11-10 Time 16:52 Rev Time 0.00
Received By ccole Date 2020-11-10 Time 12:30 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved