Plan Review Details - Permit 20101495
Plan Review Stops For Permit 20101495
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By ppetty Date 2020-12-07 Time 11:20 Rev Time 0.00
Received By ppetty Date 2020-12-07 Time 11:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By ppetty Date 2020-11-19 Time 09:18 Rev Time 0.00
Received By ppetty Date 2020-11-19 Time 09:18 Sent To  
Notes
2020-11-19 09:18:39PLEASE SEE F/D NOTES

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-12-04 Cont ID  
Sent By bdolan Date 2020-12-04 Time 14:01 Rev Time 0.00
Received By bdolan Date 2020-12-04 Time 14:00 Sent To  
Notes
2020-12-04 14:00:58REVISION PASSED BY FD 12-4-20. BD
  
 1. FLOOR PLAN WITH DEVICE LOCATIONS PROVIDED PER
 PLEDUC.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By pleduc Date 2020-11-05 Time   Rev Time 0.00
Received By pleduc Date 2020-11-05 Time 11:40 Sent To  
Notes
2020-11-05 11:43:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE ARE NO INDICATIONS OF WHERE THE
 DEVICES/EQUIPMENT IS LOCATED.
  
 PLEASE PROVIDE A DETAILS FLOOR PLAN INDICATIONG THE
 LOCATION OF EACH DEVICE OR PIECE OF EQUIPMENT.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-07 Cont ID  
Sent By ppetty Date 2020-12-07 Time 11:21 Rev Time 0.00
Received By ppetty Date 2020-12-03 Time 11:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-19 Cont ID  
Sent By ppetty Date 2020-11-19 Time 09:18 Rev Time 0.00
Received By ppetty Date 2020-11-03 Time 08:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By medwards Date 2020-12-07 Time 10:30 Rev Time 0.00
Received By medwards Date 2020-12-07 Time 09:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-04 Cont ID  
Sent By medwards Date 2020-11-04 Time 15:55 Rev Time 0.00
Received By medwards Date 2020-11-04 Time 15:55 Sent To  
Notes
2020-11-04 15:56:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20101495
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE SPECIFICATIONS FOR THE DUCT SMOKE
 DETECTORS. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-07 Cont ID  
Sent By medwards Date 2020-12-07 Time 10:33 Rev Time 0.00
Received By medwards Date 2020-12-07 Time 10:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-04 Cont ID  
Sent By medwards Date 2020-11-04 Time 16:01 Rev Time 0.00
Received By medwards Date 2020-11-04 Time 16:01 Sent To  
Notes
2020-11-04 16:02:46DESIGNER MUST DIGITALLY SIGN AND SEAL THE DRAWINGS. THE
 DIGITAL SIGNATURE AND SEAL APPEARS TO BE A COPY.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  