Plan Review Details - Permit 20101431
Plan Review Stops For Permit 20101431
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-11-30 Cont ID  
Sent By cpuell Date 2020-11-30 Time 15:11 Rev Time 0.00
Received By cpuell Date 2020-11-30 Time 15:11 Sent To  
Notes
2020-11-30 15:12:57NEW BUILDING GIVEN THE ADDRESS OF 345 BANYAN BLVD,
 RETAIL SPACE GIVEN 202 & 208 N DIXIE HWY

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2021-04-22 Cont ID  
Sent By scwelter Date 2021-04-22 Time 10:15 Rev Time 0.00
Received By scwelter Date 2021-08-19 Time 11:06 Sent To  
Notes
2021-04-22 10:27:408.19 PUBLIC ART CONCEPT APPROVED BY CITY COMMISSION
 RESOLUTION NO. 154-21
 HOLD CO UNTIL ARTWORK IS INSTALLED ETA SPRING 2022 AND
 FINAL "WALK THROUGH" REVIEW OF WORK
  
 PUBLIC ART FAILED. SUBJECT TO PUBLIC ART REQUIREMENT.
 DEVELOPER HAS VERBALLY CHOSEN OPTION 1. HOWEVER, THE
 PUBLIC ART ASSESSMENT NEEDS TO BE COMPLETED ALONG WITH
 EVIDENCE OF ESCROW. ON 4/21/21 DEVELOPER RESCHEDULED
 ART COMMITTEE REVIEW FOR JUNE 2, 2021. DEVELOPER HAS
 PUSHED BACK REVIEW FOUR TIMES.
 PER THE CODE DEVELOPER MUST SUBMIT THE APPLICATION AND
 EVIDENCE OF ESCROWED FUNDS DUE AT TIME OF PERMITTING.
 THE ITEMS REQUIRED FOR REVIEW BY COMMITTEE ARE DUE TWO
 WEEKS BEFORE ART COMMITTEE REVIEW.
  
 4.22.2021
  
 PUBLIC ART PASSED: DEVELOPER SUBMITTED COMPLETED ART
 ASSESSMENT APPLICATION AND EVIDENCE OF ESCROW. PASS OF
 PUBLIC ART CONTINGENT ON PUBLIC ART COMMITTEE
 RECOMMENDATION AND FINAL APPROVAL BY CITY COMMISSION.
 DEVELOPER MUST PRESENT TO THE ARTLIFE (PUBLIC ART)
 COMMITTEE WITHIN 30 DAYS AFTER THE ISSUANCE OF FIRST
 BUILDING PERMIT FAILURE TO DO SO WILL RESULT IN FAIL OF
 PUBLIC ART.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-05-12 Cont ID  
Sent By rmcdouga Date 2021-05-12 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2021-05-12 Time 15:14 Sent To  
Notes
2021-05-12 15:44:22****PROVISOS****
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A SEPARATE ROOF SUB-PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT DEFERRED ROOF PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD AND ENGINEERING.
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE
 FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS
 SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR
 PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS,
 STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS
 REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW
 AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION.
  
 COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH
 PRESSURES SHOWN ON SHEET S0.0.5)
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR
 TO C.O.
  
 SHORING/RESHORE ENGINEERING IS REQUIRED TO BE SUBMITTED
 TO THE BUILDING DIVISION FOR REVIEW. THE ENGINEERING IS
 TO BE SUBMITTED, REVIEWED AND ISSUED PRIOR TO CONCRETE
 POUR.
  
 A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS REQUIRED
 TO BE PROVIDED PRIOR TO INSTALLATION.
  
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-04-21 Cont ID  
Sent By rmcdouga Date 2021-04-21 Time 14:20 Rev Time 0.00
Received By rmcdouga Date 2021-04-19 Time 12:27 Sent To  
Notes
2021-04-21 12:47:13PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017) & CITY OF W.P.B.
 CHAPTER 1 AMENDMENTS
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 345 BANYAN BLVD.
 PERMIT #20101431
 170 MPH, EXPOSURE "D"
 FLOOD ZONE "X"
 HIGH-RISE BLDG. PER FBC 403 (15 STORIES, 177'-8" TO TOP
 OF OCCUPIED FLOOR, 188'-0" TO HIGHEST ROOF OF OCCUPIED
 SPACE)
 CONSTRUCTION TYPE: IA (REDUCED TO IB FOR FIRE
 RESISTANCE RATING OF BUILDING MATERIALS PER FBC
 403.2.1.1)
 OCCUPANCY TYPE: (MIXED USE) R-2, S-2, S-1, M, B, A-3
 BLDG. AND GARAGE ARE FULLY SPRINKLERED
 GARAGE IS ENCLOSED
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PARTIALLY RESOLVED. [PLEASE KEEP ALL OF THE
 THRESHOLD DOCUMENTS TOGETHER AND IN THE ORDER OF THE
 THRESHOLD INSPECTION BOOKLET. THE RESUMES, LICENSES AND
 CERTIFICATES CAN BE PUT IN THE BOOKLET BEHIND THE FORM
 FOR THAT SPECIFIC ENTITY. THE SIGNED AND NOTARIZED
 THRESHOLD FORMS FROM THE OWNER, CONTRACTOR AND DELEGATE
 INSPECTOR HAVE NOT BEEN SUBMITTED. THE THRESHOLD
 ENGINEER/SPECIAL INSPECTOR FORM IS NOT COMPLETELY
 FILLED OUT. THE ENGINEER IS REQUIRED TO DIGITALLY SIGN
 ELECTRONICALLY SUBMITTED DOCUMENTS. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE ORIGINAL SIGNED AND SEALED PAPER
 DOCUMENTS TO THE BUILDING DEPARTMENT AFTER THE
 ELECTRONIC VERSION OF THEM ONES HAVE BEEN APPROVED.]
 THIS PROJECT IS A THRESHOLD BUILDING PER FL S. S.
 553.71(7) "THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DEFINED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF
 GREATER THAN 500 PERSONS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 2) TO BE RESOLVED BY MS. SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR AT 822-1515 OR E-MAIL:
 [email protected]
  
 3) RESOLVED.
  
 4) RESOLVED.
  
 5) RESOLVED.
  
 6) RESOLVED.
  
 7) RESOLVED.
  
 8) PARTIALLY RESOLVED. [REVISE THE CODE DATA TABLE FOR
 FIRE SEPARATION DISTANCE ON SHEET ALS.0.1. ADD THE EAST
 WALL TO THE TABLE WITH THE FIRE SEPARATION DISTANCE TO
 REFLECT THE 23'-7" FROM THE EAST WALL TO THE ASSUMED
 PROPERTY LINE BETWEEN THE TWO BUILDINGS ON THE SAME
 LOT. THE EXEMPTION IN TABLE 602 (G) IS FOR NON-LOAD
 BEARING WALLS. THE FIRE RESISTANCE RATING OF EXTERIOR
 WALLS IS STILL REQUIRED TO COMPLY WITH FBC TABLE 601.]
  
 9) RESOLVED.
  
 10) RESOLVED.
  
 11) RESOLVED.
  
 12) RESOLVED.
  
 13) RESOLVED.
  
 14) RESOLVED. [THE BUILDING OFFICIAL AND FIRE MARSHAL
 HAVE ACCEPTED THIS CONDITION.]
  
 15) RESOLVED.
  
 16) RESOLVED.
  
 17) RESOLVED.
  
 18) RESOLVED.
  
 19) RESOLVED.
  
 20) RESOLVED.
  
 21) RESOLVED.
  
 22) RESOLVED.
  
 23) RESOLVED.
  
 24) RESOLVED.
  
 25) RESOLVED.
  
 26) RESOLVED.
  
 27) RESOLVED.
  
 28) RESOLVED.
  
 29) RESOLVED.
  
 30) RESOLVED.
  
 31) RESOLVED.
  
 32) RESOLVED.
  
 33) RESOLVED.
  
 34) RESOLVED.
  
 35) RESOLVED. THE VALUATION HAS BEEN ADJUSTED.
  
 36) RESOLVED. THE VALUATION IS FOR THE BUILDING AND
 MEPS. ITEMS THAT REQUIRE SEPARATE PERMITS AND REVIEWS
 WILL HAVE FEES BASED ON THEIR VALUATIONS FOR THE SCOPE
 OF WORK. ITEMS SUCH AS FIRE ALARM, FIRE SPRINKLER, LOW
 VOLTAGE, LANDSCAPING, IRRIGATION AND ALL ITEMS OTHER
 THAN BUILDING, MECHANICAL, ELECTRIC AND PLUMBING
 REQUIRE SEPARATE PERMITS.
  
 37) RESOLVED.
  
 38) RESOLVED.
  
 39) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 NEW COMMENTS:
  
 40) RESOLVED.
  
 41) RESOLVED.
  
 42) NEW COMMENT. THE FLORIDA ENERGY CODE PERFORMANCE
 BASED COMPLIANCE CERTIFICATE IS REQUIRED TO BE SIGNED
 AND SEALED BY THE PREPARER. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT'S OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT'S OR ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL IS REQUIRED TO BE ON THE DRAWINGS.
 NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & 61G1, FS 471 & 61G15
  
  
 ****PROVISOS****
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A SEPARATE ROOF SUB-PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT DEFERRED ROOF PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD AND ENGINEERING.
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE
 FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS
 SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR
 PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS,
 STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS
 REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW
 AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION.
  
 COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH
 PRESSURES SHOWN ON SHEET S0.0.5)
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR
 TO C.O.
  
 SHORING/RESHORE ENGINEERING IS REQUIRED TO BE SUBMITTED
 TO THE BUILDING DIVISION FOR REVIEW. THE ENGINEERING IS
 TO BE SUBMITTED, REVIEWED AND ISSUED PRIOR TO CONCRETE
 POUR.
  
 A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS REQUIRED
 TO BE PROVIDED PRIOR TO INSTALLATION.
  
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-02-26 Cont ID  
Sent By rmcdouga Date 2021-02-26 Time 09:15 Rev Time 0.00
Received By rmcdouga Date 2021-02-17 Time 12:12 Sent To  
Notes
2021-02-22 15:25:04PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017) & CITY OF W.P.B.
 CHAPTER 1 AMENDMENTS
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 345 BANYAN BLVD.
 PERMIT #20101431
 170 MPH, EXPOSURE "D"
 FLOOD ZONE "X"
 HIGH-RISE BLDG. PER FBC 403 (15 STORIES, 177'-8" TO TOP
 OF OCCUPIED FLOOR, 188'-0" TO HIGHEST ROOF OF OCCUPIED
 SPACE)
 CONSTRUCTION TYPE: IA (REDUCED TO IB FOR FIRE
 RESISTANCE RATING OF BUILDING MATERIALS PER FBC
 403.2.1.1)
 OCCUPANCY TYPE: (MIXED USE) R-2, S-2, S-1, M, B, A-3
 BLDG. AND GARAGE ARE FULLY SPRINKLERED
 GARAGE IS ENCLOSED
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PARTIALLY RESOLVED. [THE SIGNED AND NOTARIZED
 THRESHOLD FORMS FROM THE OWNER, CONTRACTOR, THRESHOLD
 ENGINEER AND DELEGATE INSPECTORS WERE NOT SUBMITTED. NO
 JOB HISTORY FROM THE CONTRACTOR WAS SUBMITTED. PROVIDE
 AN EMAIL ADDRESS AND I WILL SEND YOU THE CURRENT
 THRESHOLD DOCUMENTS AND FORMS.] THIS PROJECT IS A
 THRESHOLD BUILDING PER FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL THRESHOLD BUILDING INSPECTION PLAN IS
 TO PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
 2) NOT RESOLVED. ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR AT
 822-1515 OR E-MAIL: [email protected]
  
 3) NOT RESOLVED. [SUBMIT DIGITALLY SIGNED SOIL REPORT.]
 SUBMIT A SIGNED AND SEALED GEOTECHNICAL REPORT FROM A
 FLORIDA LICENSED ENGINEER WITH THE RECOMMENDED SOIL
 PREPARATION METHOD AND THE SOIL BEARING CAPACITY. FBC
 1801.2
  
 4) NOT RESOLVED. [SUBMIT A MOT PLAN.] SPECIFY HOW
 COMPLIANCE WITH FBC CHAPTER 33 SAFEGUARDS DURING
 CONSTRUCTION FOR THE FOUNDATION PERMIT WILL BE MET.
 PROVIDE A MOT (MANAGEMENT OF TRAFFIC) PLAN. RIGHT OF
 WAY PERMITS WILL BE REQUIRED TO CLOSE SIDEWALKS,
 STREETS, ETC.
  
 5) NOT RESOLVED. [IN ORDER TO AVOID ANY CONFUSION,
 PLEASE IDENTIFY THE VERTICAL DATUM FOR THE ELEVATIONS
 ON THE SITE PLANS. I DID SEE A SMALL NOTE ON THE
 ARCHITECTURAL PLANS THAT ALL ELEVATIONS ARE NAVD. FBC
 107.2.1
  
 6) RESOLVED. THE EXIT PASSAGEWAY AT STAIR 3 IS
 INCORRECTLY LABELED AS AN EGRESS PASSAGEWAY. PLEASE
 CHANGE LABEL TO EXIT PASSAGEWAY AND ADD NOTE THAT
 OPENINGS AND PENETRATIONS INTO IT ARE ONLY ALLOWED FOR
 EXITING PURPOSES AND ITEMS SERVING THE PASSAGEWAY. AN
 EXIT PASSAGEWAY IS AN EXTENSION OF THE ENCLOSED
 INTERIOR EXIT STAIRWAY AND HAS REQUIREMENTS SIMILAR TO
 THE STAIRWAY. SEE FBC 1023.1 AND 1024.
  
 7) NOT RESOLVED. [VERTICAL DATUM WAS NOT PROVIDED ON
 SHEETS SP1.0.1 OR SP1.1.1.] THE EXIT DISCHARGE FROM
 STAIR 3 IS NOT TO A PUBLIC WAY. IT APPEARS THAT THE
 OCCUPANTS WILL NEED TO TRAVEL THROUGH THE ADJACENT
 PROPERTY TO REACH THE PUBLIC WAY. [A] PUBLIC WAY. A
 STREET, ALLEY OR OTHER PARCEL OF LAND OPEN TO THE
 OUTSIDE AIR LEADING TO A STREET, THAT HAS BEEN DEEDED,
 DEDICATED OR OTHERWISE PERMANENTLY APPROPRIATED TO THE
 PUBLIC FOR PUBLIC USE AND WHICH HAS A CLEAR WIDTH AND
 HEIGHT OF NOT LESS THAN 10 FEET (3048 MM). PLEASE
 CLARIFY. FBC 1022
  
 8) NOT RESOLVED. [I DID NOT SEE THE APPROVAL LETTER
 FROM ZONING MENTIONED IN YOUR RESPONCE LETTER. SPECIFY
 THE FIRE SEPARATION DISTANCE BETWEEN THE PROPOSED
 BUILDING AND THE EXISTING BUILDING ON THE LOT. SHOW
 THAT THE AREA OF OPENINGS ON EACH FLOOR OF THE EXISTING
 BUILDING AND THE PROPOSED BUILDING WITH BOTH COMPLY
 WITH FBC 705.8.1.] THE EAST WALL IS NOT LISTED IN THE
 FIRE SEPARATION TABLE 705.8 ON SHEET ALS.0.1. FBC
 107.2.1
  
 9) NOT RESOLVED. [SEE COMMENT NUMBER 8.] THE SITE PLANS
 APPEAR TO SHOW A PORTION OF THE EAST WALL IS ON THE
 PROPERTY LINE. THE DOORS TO THE TRANSFORMER ROOM SWING
 OUT OVER THE PROPERTY LINE WHICH IS NOT ALLOWED. PLEASE
 PROVIDE CLARIFICATION. FBC 107.2.1
  
 10) NOT RESOLVED. [PROVIDE THE REQUESTED CALCULATIONS.]
 THERE ARE MULTIPLE OPENINGS IN THE EAST WALL THAT ARE
 NOT ALLOWED BASED THE FIRE SEPARATION DISTANCE AND
 TABLE 705.8. NO OPENINGS ARE ALLOWED FROM 0<3 FEET AND
 15 PERCENT FROM 3<5 FEET. PROVIDE CALCULATIONS FOR THE
 ALLOWABLE AREA OF OPENINGS ON THE EAST AND NORTH WALLS
 OF THE BUILDING. FBC 107.2.1.2
  
 11) RESOLVED. PLEASE REVISE GENERAL NOTE 21 ON SHEET
 ALS.0.1 TO REFERENCE THE 2017 FBC ACCESSIBILITY RATHER
 THAN THE 2003 IBC FOR ACCESSIBILITY.
  
 12) RESOLVED. PLEASE REVISE THE NOTES ON ALS.0.2 THAT
 REFERENCE THE 2012 N.C. BUILDING CODE TO THE 2017 FBC.
  
 13) RESOLVED. SHOW COMPLIANCE. FBC 3002.4 REQUIRES ANY
 BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET TO
 BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND
 FIRE DEPARTMENT ACCESS TO ALL FLOORS. THE ELEVATOR CAR
 SHALL BE OF A SIZE AND ARRANGEMENT TO ACCOMMODATE AN
 AMBULANCE STRETCHER 24 INCHES BY 76 INCHES WITH NOT
 LESS THAN 5-INCH RADIUS CORNERS, IN THE HORIZONTAL,
 OPEN POSITION AND SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES
 (STAR OF LIFE).
  
 14) RESOLVED. [THE BUILDING OFFICIAL AND FIRE MARSHAL
 HAVE ACCEPTED THIS CONDITION.] THE ELEVATOR LOBBIES
 HAVE DIMENSIONS THAT ARE LESS THAN THE REQUIRED 8 FEET.
 3007.6.4 LOBBY SIZE. REGARDLESS OF THE NUMBER OF FIRE
 SERVICE ACCESS ELEVATORS SERVED BY THE SAME ELEVATOR
 LOBBY, THE ENCLOSED FIRE SERVICE ACCESS ELEVATOR LOBBY
 SHALL BE NOT LESS THAN 150 SQUARE FEET (14 M2) IN AN
 AREA WITH A DIMENSION OF NOT LESS THAN 8 FEET (2440
 MM). SEE SHEET A6.1.2 (PG. 157) AND OTHER SHEETS.
  
 15) RESOLVED. SHOW COMPLIANCE. 403.6.1 FIRE SERVICE
 ACCESS ELEVATOR. IN BUILDINGS WITH AN OCCUPIED FLOOR
 MORE THAN 120 FEET (36 576 MM), MEASURED FROM THE
 ELEVATION OF STREET-LEVEL ACCESS TO THE LEVEL OF THE
 HIGHEST OCCUPIABLE FLOOR, NO FEWER THAN TWO FIRE
 SERVICE ACCESS ELEVATORS SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 3007. ALL REMAINING ELEVATORS,
 IF ANY, SHALL BE PROVIDED WITH PHASE I AND II EMERGENCY
 OPERATION. EACH FIRE SERVICE ACCESS ELEVATOR SHALL HAVE
 A CAPACITY OF NOT LESS THAN 3,500 POUNDS (1588 KG).
  
 16) RESOLVED. ON SHEET ALS.1.1 THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE LOBBY AREA NEEDS TO INCLUDE
 THE MANAGERS OFFICE, WHICH IS PART OF THAT AREA. THE
 LONGEST DIAGONAL SHOULD BE TO THE EXTERIOR WALLS OFNTHE
 AREA FROM THE MANAGER'S OFFICE TO THE SOUTHEAST CORNER
 OF THE LOBBY. FBC 1007.1.1 TWO EXITS OR EXIT ACCESS
 DOORWAYS.
  
 17) RESOLVED. ON SHEET ALS.4.1 THE SEPARATION DISTANCE
 OF THE TWO EXITS FROM UNIT 15 IS SHOWN ON THE PLANS,
 HOWEVER, THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE
 UNIT IS NOT PROVIDED. FBC 107.2.3
  
 18) RESOLVED. ON ALL LIFE SAFETY PLANS, SPECIFY THE
 COMMON PATH OF TRAVEL DISTANCE FROM THE MOST REMOTE
 POINT OF THE BALCONIES IN THE LARGER UNITS AND SHOW THE
 EXIT ACCESS TRAVEL DISTANCE FROM THE MOST REMOTE POINT
 OF THE MOST REMOTE UNIT ON THE FLOOR TO THE NEAREST
 EXIT COMPLIES WITH FBC 1017.
  
 19) RESOLVED. ON ALL LIFE SAFETY PLANS, SPECIFY THE
 EXIT ACCESS TRAVEL DISTANCES IN THE PARKING GARAGE ON
 THE PLANS TO COMPLY WITH FBC 1017.
  
 20) RESOLVED. ON SHEET ALS.6.1, THE EXIT PATH OF TRAVEL
 IS NOT SHOWN FROM THE MOST REMOTE POINT OF THE BALCONY
 IN UNIT 8. FBC 1017
  
 21) RESOLVED. ON SHEET ALS.7.1, THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING AND THE 1/3 DIAGONAL
 EXIT SEPARATION DISTANCE ARE NOT PROVIDED. FBC 107.2.3
  
 22) RESOLVED. ON SHEET ALS.8.1, SPECIFY THE TOTAL
 OCCUPANT LOAD IN THE TABLE. IT APPEARS THAT THE TOTAL
 LOAD IS 94 OCCUPANTS. THE NUMBERS SPECIFIED AT THE EXIT
 STAIRS ARE FOR ONLY 47 OCCUPANTS. PLEASE CORRECT. FBC
 107.2.3
  
 23) RESOLVED. THE MEAN ROOF HEIGHT IS NOT SPECIFIED IN
 THE GN - DESIGNER LOADS TABLE ON SHEET S0.1. (PG 272).
 FBC 107.2.1
  
 24) RESOLVED. ON SHEET S0.1, CONCRETE NOTE #1 NEEDS TO
 BE UPDATED TO THE 2017 FBC. FBC 107
  
 25) RESOLVED. ON SHEET S0.0.5, NOTE #5 IN THE WIND
 DIAGRAM NOTES SPECIFIES THE MEAN ROOF HEIGHT AS 118'-2"
 AND THE PLANS LIST 188'-0" AS THE HIGHEST ROOF OF THE
 OCCUPIED SPACE. PLEASE CLARIFY. FBC 107.2.1
  
 26) RESOLVED. THE WASTE (TRASH) CHUTE IS REQUIRED TO
 HAVE A 2 HOUR FIRE RESISTIVE RATING PER FBC 713.4 AND
 THE CHUTE ACCESS ROOMS ARE REQUIRED TO BE A MINIMUM 1
 HOUR FIRE BARRIER PER FBC 713.13. SOME OF LIFE SAFETY
 PLANS SHEETS DO NOT CLEARLY SHOW THIS. PLEASE CORRECT.
 FBC 107.2.1
  
 27) RESOLVED. SHOW COMPLIANCE WITH FBC 2304.12 FOR
 TERMITE PROTECTION.
  
 28) RESOLVED. VERIFY THE REQUIRED VERTICAL CLEARANCE OF
 98 INCHES FOR THE VAN PARKING SPACE, ACCESS AISLE AND
 VEHICULAR ROUTE SERVING IT AS REQUIRED BY FBC
 ACCESSIBILITY SECTION 502.5. THERE HAVE BEEN ISSUES
 WITH EQUIPMENT OR SYSTEMS INSTALLED BELOW THE REQUIRED
 98" IN THESE AREAS OF PARKING GARAGES. PLEASE PROVIDE
 NOTES ON THE DRAWINGS TO HELP AVOID THIS ISSUE.
  
 29) NOT RESOLVED. [WHERE PROVIDED KITCHEN APPLIANCES
 ARE REQUIRED TO COMPLY WITH FBC ACCESSIBILITY SECTION
 804.6] THE MICROWAVE OVEN IN THE WORK ROOM SHOWN IN
 ELEVATION 6 ON SHEET A9.50.5 DOES NOT APPEAR TO COMPLY
 WITH THE REQUIRED REACH RANGES OF FBC ACCESSIBILITY
 SECTIONS 308, 309.3 AND 804.6.2.
  
 30) RESOLVED. SHOW COMPLIANCE FBC ACCESSIBILITY SECTION
 242 FOR ACCESSIBLE ENTRY INTO THE POOL OR SPECIFY ON
 THE PLANS WHY IT IS NOT REQUIRED. COMMUNITY POOLS THAT
 ARE ASSOCIATED WITH A PRIVATE RESIDENTIAL COMMUNITY
 THAT DO NOT RECEIVE GOVERNMENTAL FINANCIAL ASSISTANCE
 OR SPONSORSHIP AND ARE LIMITED TO THE EXCLUSIVE OF
 RESIDENTS AND THEIR GUESTS ARE NOT COVERED BY THE ADA
 ACCESSIBILITY REQUIREMENTS, INCLUDING PROVISIONS FOR
 POOL LIFTS OR SLOPED ENTRIES. IF A SWIMMING POOL
 LOCATED IN A RESIDENTIAL COMMUNITY IS MADE AVAILABLE TO
 THE PUBLIC FOR RENTAL OR USE IT IS REQUIRED TO COMPLY
 WITH TITLE II OF THE ADA. SPECIFY ON THE PLANS THE
 FORMER OR SHOW COMPLIANCE WITH THE LATTER STATEMENTS.
 SEE DECLARATORY STATEMENT, DS 2013-011. (NOTE: A
 SEPARATE PERMIT WILL BE REQUIRED FOR THE POOL.)
  
 31) RESOLVED. THE MAXIMUM DISTANCE FROM THE WATER'S
 EDGE OF THE SWIMMING POOL TO THE RESTROOMS IS NOT SHOWN
 CORRECTLY ON THE PLAN SHEET ALS.6.1. FBC454.1.6.1 THE
 ENTRY DOORS OF ALL RESTROOMS SHALL BE LOCATED WITHIN A
 200-FOOT (60 960 MM) WALKING DISTANCE OF THE NEAREST
 WATER'S EDGE OF EACH POOL SERVED BY THE FACILITIES.
 PLEASE CORRECT.
  
 32) RESOLVED. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED.
  
 33) RESOLVED. FBC 107.3.4.1 DEFERRED SUBMITTALS. (I
 NOTED THAT THERE IS A LIST OF DEFERRED SUBMITTALS AND
 SEPARATE PERMITS ON SHEET ALS.0.1) FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 34) NOT RESOLVED. [SOUND INSULATION IS REQUIRED FOR
 HARD FLOORING MATERIALS SUCH AS TILE, LAMINATE, WOOD,
 ETC. ADD NOTE TO PLANS. IF YOU WISH TO SUBMIT THE TEST
 REPORTS LATER, ADD TO THE LIST OF DEFERRED ITEMS. SHOW
 COMPLIANCE WITH FBC SECTION 1207 SOUND TRANSMISSION,
 1207.2 AIR-BORNE SOUND AND 1207.3 STRUCTURE-BORNE
 SOUND. TEST REPORTS WILL NEED TO BE SUBMITTED FOR THE
 SOUND INSULATION THAT WILL BE INSTALLED UNDER FINISH
 FLOORING.
  
 35) NOT RESLOVED. [AREA TABULATIONS TO BE PROVIDED BY
 THE DESIGNER.] IN ORDER TO VERIFY THE BUILDING
 VALUATION, PLEASE PROVIDE AREA TABULATIONS FOR THE
 ENTIRE BUILDING. PLEASE SEPARATE AREA TABULATIONS BY
 OCCUPANCY TYPE. FBC 109.3 BUILDING PERMIT VALUATION.
 FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS
 PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL
 BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL.
  
 36) NOT RESOLVED. SEPARATE PERMITS, REVIEWS AND FEES
 ARE REQUIRED FOR SOME ITEMS THAT MAY HAVE BEEN INCLUDED
 IN THE VALUE FOR THIS PROJECT. ITEMS SUCH AS FIRE
 ALARM, FIRE SPRINKLER, LOW VOLTAGE, LANDSCAPING,
 IRRIGATION AND ALL ITEMS OTHER THAN BUILDING,
 MECHANICAL, ELECTRIC AND PLUMBING. PLEASE PROVIDE A
 COST BREAKDOWN SO THAT WE CAN DEDUCT THESE ITEMS FROM
 THE PERMIT VALUE SO THAT YOU WILL NOT BE CHARGED TWICE
 FOR THE SAME ITEM.
  
 37) RESOLVED. [WILL REMAIN AS ONE PARCEL WITH TWO
 BUILDINGS. APPROVAL LETTER FROM ZONING TO BE
 SUBMITTED.] THE P.B.C. PROPERTY APPRAISER SHOWS THIS
 PROJECT IS LOCATED ON A LARGER PARCEL THAN THE SITE
 PLAN AND SURVEY THAT WAS SUBMITTED. IS THIS PARCEL
 BEING SUBDIVIDED OR TO REMAIN AS ONE PARCEL WITH TWO
 BUILDINGS ON IT? PLEASE CLARIFY.
  
 38) NOT RESOLVED. THE ADDRESS OF THE PROJECT HAS BEEN
 CHANGED TO 345 BANYAN BLVD. PLEASE CHANGE THE ADDRESS
 IN THE TITLE BLOCK OF THE PLANS. THE DESCRIPTION OF THE
 PROJECT AS PARKING LOT REDEVELOPEMENT IN THE TITLE
 BLOCK IS NOT SPECIFIC. A MORE ACCURATE DISCRIPTION
 WOULD BE A NEW RESIDENTIAL HIGH RISE BUILDING AND
 PARKING GARAGE. FBC 107.2.1
  
 39) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 NEW COMMENTS:
  
 40) THE ACCESSIBLE ROUTE FROM THE PARKING GARAGE TO
 CORRIDOR 186 APPEARS TO GO THROUGH A WALL. SEE SHEETS
 057-ALS1.1, 070 - A1.1.2B AND 066 - A1.1.1. PLEASE
 CLARIFY. FBC 107.2.1
  
 41) SHOW ACCESS TO THE ELEVATOR MACHINERY THAT WILL BE
 LOCATED ON TOP OF ELEVATORS 2 AND 3. 3005.1 ACCESS. AN
 APPROVED MEANS OF ACCESS SHALL BE PROVIDED TO ELEVATOR
 MACHINE ROOMS, CONTROL ROOMS, CONTROL SPACES AND
 MACHINERY SPACES.
  
 ****PROVISOS****
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE
 FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS
 SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR
 PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS,
 STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS
 REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW
 AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION.
  
 COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH
 PRESSURES SHOWN ON SHEET S0.0.5)
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR
 TO C.O.
  
 SHORING/RESHORE ENGINEERING IS REQUIRED TO BE SUBMITTED
 TO THE BUILDING DIVISION FOR REVIEW. THE ENGINEERING IS
 TO BE SUBMITTED, REVIEWED AND ISSUED PRIOR TO CONCRETE
 POUR.
  
 A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS REQUIRED
 TO BE PROVIDED PRIOR TO INSTALLATION.
  
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By rmcdouga Date 2020-12-07 Time 14:24 Rev Time 0.00
Received By rmcdouga Date 2020-12-07 Time 14:23 Sent To  
Notes
2020-12-04 13:42:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017) & CITY OF W.P.B.
 CHAPTER 1 AMENDMENTS
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 345 BANYAN BLVD.
 PERMIT #20101431
 170 MPH, EXPOSURE "D"
 FLOOD ZONE "X"
 HIGH-RISE BLDG. PER FBC 403 (15 STORIES, 177'-8" TO TOP
 OF OCCUPIED FLOOR, 188'-0" TO HIGHEST ROOF OF OCCUPIED
 SPACE)
 CONSTRUCTION TYPE: IA (REDUCED TO IB FOR FIRE
 RESISTANCE RATING OF BUILDING MATERIALS PER FBC
 403.2.1.1)
 OCCUPANCY TYPE: (MIXED USE) R-2, S-2, S-1, M, B, A-3
 BLDG. AND GARAGE ARE FULLY SPRINKLERED
 GARAGE IS ENCLOSED
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PROJECT IS A THRESHOLD BUILDING PER FL S. S.
 553.71(7) "THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DEFINED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF
 GREATER THAN 500 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL THRESHOLD BUILDING INSPECTION PLAN IS
 TO PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
 2) ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR AT
 822-1515 OR E-MAIL: [email protected]
  
 3) SUBMIT A SIGNED AND SEALED GEOTECHNICAL REPORT FROM
 A FLORIDA LICENSED ENGINEER WITH THE RECOMMENDED SOIL
 PREPARATION METHOD AND THE SOIL BEARING CAPACITY. FBC
 1801.2
  
 4) SPECIFY HOW COMPLIANCE WITH FBC CHAPTER 33
 SAFEGUARDS DURING CONSTRUCTION FOR THE FOUNDATION
 PERMIT WILL BE MET. PROVIDE A MOT (MANAGEMENT OF
 TRAFFIC) PLAN. RIGHT OF WAY PERMITS WILL BE REQUIRED TO
 CLOSE SIDEWALKS, STREETS, ETC.
  
 5) IN ORDER TO AVOID ANY CONFUSION, PLEASE IDENTIFY THE
 VERTICAL DATUM FOR THE ELEVATIONS ON THE SITE PLANS. I
 DID SEE A SMALL NOTE ON THE ARCHITECTURAL PLANS THAT
 ALL ELEVATIONS ARE NAVD. FBC 107.2.1
  
 6) THE EXIT PASSAGEWAY AT STAIR 3 IS INCORRECTLY
 LABELED AS AN EGRESS PASSAGEWAY. PLEASE CHANGE LABEL TO
 EXIT PASSAGEWAY AND ADD NOTE THAT OPENINGS AND
 PENETRATIONS INTO IT ARE ONLY ALLOWED FOR EXITING
 PURPOSES AND ITEMS SERVING THE PASSAGEWAY. AN EXIT
 PASSAGEWAY IS AN EXTENSION OF THE ENCLOSED INTERIOR
 EXIT STAIRWAY AND HAS REQUIREMENTS SIMILAR TO THE
 STAIRWAY. SEE FBC 1023.1 AND 1024.
  
 7) THE EXIT DISCHARGE FROM STAIR 3 IS NOT TO A PUBLIC
 WAY. IT APPEARS THAT THE OCCUPANTS WILL NEED TO TRAVEL
 THROUGH THE ADJACENT PROPERTY TO REACH THE PUBLIC WAY.
 [A] PUBLIC WAY. A STREET, ALLEY OR OTHER PARCEL OF LAND
 OPEN TO THE OUTSIDE AIR LEADING TO A STREET, THAT HAS
 BEEN DEEDED, DEDICATED OR OTHERWISE PERMANENTLY
 APPROPRIATED TO THE PUBLIC FOR PUBLIC USE AND WHICH HAS
 A CLEAR WIDTH AND HEIGHT OF NOT LESS THAN 10 FEET (3048
 MM). PLEASE CLARIFY. FBC 1022
  
 8) THE EAST WALL IS NOT LISTED IN THE FIRE SEPARATION
 TABLE 705.8 ON SHEET ALS.0.1. FBC 107.2.1
  
 9) THE SITE PLANS APPEAR TO SHOW A PORTION OF THE EAST
 WALL IS ON THE PROPERTY LINE. THE DOORS TO THE
 TRANSFORMER ROOM SWING OUT OVER THE PROPERTY LINE WHICH
 IS NOT ALLOWED. PLEASE PROVIDE CLARIFICATION. FBC
 107.2.1
  
 10) THERE ARE MULTIPLE OPENINGS IN THE EAST WALL THAT
 ARE NOT ALLOWED BASED THE FIRE SEPARATION DISTANCE AND
 TABLE 705.8. NO OPENINGS ARE ALLOWED FROM 0<3 FEET AND
 15 PERCENT FROM 3<5 FEET. PROVIDE CALCULATIONS FOR THE
 ALLOWABLE AREA OF OPENINGS ON THE EAST AND NORTH WALLS
 OF THE BUILDING. FBC 107.2.1.2
  
 11) PLEASE REVISE GENERAL NOTE 21 ON SHEET ALS.0.1 TO
 REFERENCE THE 2017 FBC ACCESSIBILITY RATHER THAN THE
 2003 IBC FOR ACCESSIBILITY.
  
 12) PLEASE REVISE THE NOTES ON ALS.0.2 THAT REFERENCE
 THE 2012 N.C. BUILDING CODE TO THE 2017 FBC.
  
 13) SHOW COMPLIANCE. FBC 3002.4 REQUIRES ANY BUILDING
 THAT IS MORE THAN THREE STORIES HIGH OR IN WHICH THE
 VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL LANDING
 AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET TO BE
 CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER ELEVATOR
 THAT IS OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE
 DEPARTMENT ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL
 BE OF A SIZE AND ARRANGEMENT TO ACCOMMODATE AN
 AMBULANCE STRETCHER 24 INCHES BY 76 INCHES WITH NOT
 LESS THAN 5-INCH RADIUS CORNERS, IN THE HORIZONTAL,
 OPEN POSITION AND SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES
 (STAR OF LIFE).
  
 14) THE ELEVATOR LOBBIES HAVE DIMENSIONS THAT ARE LESS
 THAN THE REQUIRED 8 FEET. 3007.6.4 LOBBY SIZE.
 REGARDLESS OF THE NUMBER OF FIRE SERVICE ACCESS
 ELEVATORS SERVED BY THE SAME ELEVATOR LOBBY, THE
 ENCLOSED FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE
 NOT LESS THAN 150 SQUARE FEET (14 M2) IN AN AREA WITH A
 DIMENSION OF NOT LESS THAN 8 FEET (2440 MM). SEE SHEET
 A6.1.2 (PG. 157) AND OTHER SHEETS.
  
 15) SHOW COMPLIANCE. 403.6.1 FIRE SERVICE ACCESS
 ELEVATOR. IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN
 120 FEET (36 576 MM), MEASURED FROM THE ELEVATION OF
 STREET-LEVEL ACCESS TO THE LEVEL OF THE HIGHEST
 OCCUPIABLE FLOOR, NO FEWER THAN TWO FIRE SERVICE ACCESS
 ELEVATORS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 3007. ALL REMAINING ELEVATORS, IF ANY, SHALL BE
 PROVIDED WITH PHASE I AND II EMERGENCY OPERATION. EACH
 FIRE SERVICE ACCESS ELEVATOR SHALL HAVE A CAPACITY OF
 NOT LESS THAN 3,500 POUNDS (1588 KG).
  
 16) ON SHEET ALS.1.1 THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE LOBBY AREA NEEDS TO INCLUDE THE
 MANAGERS OFFICE, WHICH IS PART OF THAT AREA. THE
 LONGEST DIAGONAL SHOULD BE TO THE EXTERIOR WALLS OFNTHE
 AREA FROM THE MANAGER'S OFFICE TO THE SOUTHEAST CORNER
 OF THE LOBBY. FBC 1007.1.1 TWO EXITS OR EXIT ACCESS
 DOORWAYS.
  
 17) ON SHEET ALS.4.1 THE SEPARATION DISTANCE OF THE TWO
 EXITS FROM UNIT 15 IS SHOWN ON THE PLANS, HOWEVER, THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE UNIT IS NOT
 PROVIDED. FBC 107.2.3
  
 18) ON ALL LIFE SAFETY PLANS, SPECIFY THE COMMON PATH
 OF TRAVEL DISTANCE FROM THE MOST REMOTE POINT OF THE
 BALCONIES IN THE LARGER UNITS AND SHOW THE EXIT ACCESS
 TRAVEL DISTANCE FROM THE MOST REMOTE POINT OF THE MOST
 REMOTE UNIT ON THE FLOOR TO THE NEAREST EXIT COMPLIES
 WITH FBC 1017.
  
 19) ON ALL LIFE SAFETY PLANS, SPECIFY THE EXIT ACCESS
 TRAVEL DISTANCES IN THE PARKING GARAGE ON THE PLANS TO
 COMPLY WITH FBC 1017.
  
 20) ON SHEET ALS.6.1, THE EXIT PATH OF TRAVEL IS NOT
 SHOWN FROM THE MOST REMOTE POINT OF THE BALCONY IN UNIT
 8. FBC 1017
  
 21) ON SHEET ALS.7.1, THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE BUILDING AND THE 1/3 DIAGONAL EXIT
 SEPARATION DISTANCE ARE NOT PROVIDED. FBC 107.2.3
  
 22) ON SHEET ALS.8.1, SPECIFY THE TOTAL OCCUPANT LOAD
 IN THE TABLE. IT APPEARS THAT THE TOTAL LOAD IS 94
 OCCUPANTS. THE NUMBERS SPECIFIED AT THE EXIT STAIRS ARE
 FOR ONLY 47 OCCUPANTS. PLEASE CORRECT. FBC 107.2.3
  
 23) THE MEAN ROOF HEIGHT IS NOT SPECIFIED IN THE GN -
 DESIGNER LOADS TABLE ON SHEET S0.1. (PG 272). FBC
 107.2.1
  
 24) ON SHEET S0.1, CONCRETE NOTE #1 NEEDS TO BE UPDATED
 TO THE 2017 FBC. FBC 107
  
 25) ON SHEET S0.0.5, NOTE #5 IN THE WIND DIAGRAM NOTES
 SPECIFIES THE MEAN ROOF HEIGHT AS 118'-2" AND THE PLANS
 LIST 188'-0" AS THE HIGHEST ROOF OF THE OCCUPIED SPACE.
 PLEASE CLARIFY. FBC 107.2.1
  
 26) THE WASTE (TRASH) CHUTE IS REQUIRED TO HAVE A 2
 HOUR FIRE RESISTIVE RATING PER FBC 713.4 AND THE CHUTE
 ACCESS ROOMS ARE REQUIRED TO BE A MINIMUM 1 HOUR FIRE
 BARRIER PER FBC 713.13. SOME OF LIFE SAFETY PLANS
 SHEETS DO NOT CLEARLY SHOW THIS. PLEASE CORRECT. FBC
 107.2.1
  
 27) SHOW COMPLIANCE WITH FBC 2304.12 FOR TERMITE
 PROTECTION.
  
 28) VERIFY THE REQUIRED VERTICAL CLEARANCE OF 98 INCHES
 FOR THE VAN PARKING SPACE, ACCESS AISLE AND VEHICULAR
 ROUTE SERVING IT AS REQUIRED BY FBC ACCESSIBILITY
 SECTION 502.5. THERE HAVE BEEN ISSUES WITH EQUIPMENT OR
 SYSTEMS INSTALLED BELOW THE REQUIRED 98" IN THESE AREAS
 OF PARKING GARAGES. PLEASE PROVIDE NOTES ON THE
 DRAWINGS TO HELP AVOID THIS ISSUE.
  
 29) THE MICROWAVE OVEN IN THE WORK ROOM SHOWN IN
 ELEVATION 6 ON SHEET A9.50.5 DOES NOT APPEAR TO COMPLY
 WITH THE REQUIRED REACH RANGES OF FBC ACCESSIBILITY
 SECTIONS 308, 309.3 AND 804.6.2.
  
 30) SHOW COMPLIANCE FBC ACCESSIBILITY SECTION 242 FOR
 ACCESSIBLE ENTRY INTO THE POOL OR SPECIFY ON THE PLANS
 WHY IT IS NOT REQUIRED. COMMUNITY POOLS THAT ARE
 ASSOCIATED WITH A PRIVATE RESIDENTIAL COMMUNITY THAT DO
 NOT RECEIVE GOVERNMENTAL FINANCIAL ASSISTANCE OR
 SPONSORSHIP AND ARE LIMITED TO THE EXCLUSIVE OF
 RESIDENTS AND THEIR GUESTS ARE NOT COVERED BY THE ADA
 ACCESSIBILITY REQUIREMENTS, INCLUDING PROVISIONS FOR
 POOL LIFTS OR SLOPED ENTRIES. IF A SWIMMING POOL
 LOCATED IN A RESIDENTIAL COMMUNITY IS MADE AVAILABLE TO
 THE PUBLIC FOR RENTAL OR USE IT IS REQUIRED TO COMPLY
 WITH TITLE II OF THE ADA. SPECIFY ON THE PLANS THE
 FORMER OR SHOW COMPLIANCE WITH THE LATTER STATEMENTS.
 SEE DECLARATORY STATEMENT, DS 2013-011. (NOTE: A
 SEPARATE PERMIT WILL BE REQUIRED FOR THE POOL.)
  
 31) THE MAXIMUM DISTANCE FROM THE WATER'S EDGE OF THE
 SWIMMING POOL TO THE RESTROOMS IS NOT SHOWN CORRECTLY
 ON THE PLAN SHEET ALS.6.1. FBC454.1.6.1 THE ENTRY DOORS
 OF ALL RESTROOMS SHALL BE LOCATED WITHIN A 200-FOOT (60
 960 MM) WALKING DISTANCE OF THE NEAREST WATER'S EDGE OF
 EACH POOL SERVED BY THE FACILITIES. PLEASE CORRECT.
  
 32) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED.
  
 33) FBC 107.3.4.1 DEFERRED SUBMITTALS. (I NOTED THAT
 THERE IS A LIST OF DEFERRED SUBMITTALS AND SEPARATE
 PERMITS ON SHEET ALS.0.1) FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 34) SHOW COMPLIANCE WITH FBC SECTION 1207 SOUND
 TRANSMISSION, 1207.2 AIR-BORNE SOUND AND 1207.3
 STRUCTURE-BORNE SOUND. TEST REPORTS WILL NEED TO BE
 SUBMITTED FOR THE SOUND INSULATION THAT WILL BE
 INSTALLED UNDER FINISH FLOORING.
  
 35) IN ORDER TO VERIFY THE BUILDING VALUATION, PLEASE
 PROVIDE AREA TABULATIONS FOR THE ENTIRE BUILDING.
 PLEASE SEPARATE AREA TABULATIONS BY OCCUPANCY TYPE. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 36) SEPARATE PERMITS, REVIEWS AND FEES ARE REQUIRED FOR
 SOME ITEMS THAT MAY HAVE BEEN INCLUDED IN THE VALUE FOR
 THIS PROJECT. ITEMS SUCH AS FIRE ALARM, FIRE SPRINKLER,
 LOW VOLTAGE, LANDSCAPING, IRRIGATION AND ALL ITEMS
 OTHER THAN BUILDING, MECHANICAL, ELECTRIC AND PLUMBING.
 PLEASE PROVIDE A COST BREAKDOWN SO THAT WE CAN DEDUCT
 THESE ITEMS FROM THE PERMIT VALUE SO THAT YOU WILL NOT
 BE CHARGED TWICE FOR THE SAME ITEM.
  
 37) THE P.B.C. PROPERTY APPRAISER SHOWS THIS PROJECT IS
 LOCATED ON A LARGER PARCEL THAN THE SITE PLAN AND
 SURVEY THAT WAS SUBMITTED. IS THIS PARCEL BEING
 SUBDIVIDED OR TO REMAIN AS ONE PARCEL WITH TWO
 BUILDINGS ON IT? PLEASE CLARIFY.
  
 38) THE ADDRESS OF THE PROJECT HAS BEEN CHANGED TO 345
 BANYAN BLVD. PLEASE CHANGE THE ADDRESS IN THE TITLE
 BLOCK OF THE PLANS. THE DESCRIPTION OF THE PROJECT AS
 PARKING LOT REDEVELOPEMENT IN THE TITLE BLOCK IS NOT
 SPECIFIC. A MORE ACCURATE DISCRIPTION WOULD BE A NEW
 RESIDENTIAL HIGH RISE BUILDING AND PARKING GARAGE. FBC
 107.2.1
  
 39) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 ****PROVISOS****
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE
 FOLLOWING LIST (MAY NOT BE A COMPLETE LIST); DOCUMENTS
 SHOWING COMPLIANCE ARE TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL (ARCHITECT OR ENGINEER FOR
 PRODUCT APPROVALS AND OTHER SPECIFICATION DOCUMENTS,
 STRUCTURAL ENGINEER OF RECORD APPROVAL AND REVIEW IS
 REQUIRED FOR DELEGATED ENGINEERING). SUBMITTAL, REVIEW
 AND APPROVAL ARE REQUIRED PRIOR TO INSTALLATION.
  
 COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH
 PRESSURES SHOWN ON SHEET S0.0.5)
  
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A PDF
 VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL.
  
 AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR
 TO C.O.
  
 SHORING/RESHORE ENGINEERING IS REQUIRED TO BE SUBMITTED
 TO THE BUILDING DIVISION FOR REVIEW. THE ENGINEERING IS
 TO BE SUBMITTED, REVIEWED AND ISSUED PRIOR TO CONCRETE
 POUR.
  
 A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS REQUIRED
 TO BE PROVIDED PRIOR TO INSTALLATION.
  
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-04-21 Cont ID  
Sent By jleahy Date 2021-04-21 Time 16:49 Rev Time 0.00
Received By jleahy Date 2021-04-15 Time 16:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-05 Cont ID  
Sent By jleahy Date 2021-02-04 Time 07:52 Rev Time 0.00
Received By jleahy Date 2021-01-29 Time 08:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By jleahy Date 2020-11-19 Time 13:30 Rev Time 0.00
Received By jleahy Date 2020-11-16 Time 17:58 Sent To  
Notes
2020-11-19 16:27:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E02.2A
  
 1) IS PANEL H1 A MAIN?
  
 2) NOT ALL WIRE SIZES SHOWN ON RISER 215.5
  
 3) FAULT CURRENT CALCULATION NEEDED FOR SERVICE TO SHOW
 CORRECT AIC RATING 110.9, 110.10
  
 4) ARC FLSH MITIGATION REQUIRED PER 240.87 FOR MAINS 1
 THRU 4
  
 PAGESE02.1 B AND C
  
 1) NOT ALL WIRE SIZES SHOWN ON RISER 215.5
  
 PAGE E1.81A
  
 OUTLETS ON ROOF TO BE WITHIN 25' OF AC EQUIPMENT 210.63
  
 PAGES E9.1.1 THROUGH E9.1,14
  
 1) SMOKE ALARMS ARE CLOSE TO KITCHEN RANGE NEED TO
 INSTALLED PER NFPA 72 29.8.3.4 (4)
  
 2) SMOKE ALARMS INSTLLED TO CLOSE TO THE BATHROOM DOOR
 SEE NFPA 72 29.8.3.4 (6)
  
 GENERAL NOTE
  
 FOLLOWING REQUIRE SEPARATE PERMITS FIRE ALARM, BDA
 SYSTEM, POOL, GENERATOR, LOW VOLTAGE SYSTEMS, LIGHTNING
 PROTECTION, SITE LIGHTING

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-01-28 Cont ID  
Sent By rrossano Date 2021-01-28 Time   Rev Time 0.00
Received By rrossano Date 2021-01-28 Time   Sent To  
Notes
2021-01-28 08:56:24REVIEWED UNDER FORMAL ENG SUBMITTAL E20070023.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By rrossano Date 2020-11-19 Time   Rev Time  
Received By rrossano Date 2020-11-19 Time   Sent To  
Notes
2020-11-19 23:41:21UNDER REVIEW AS FORMAL ENGINEERING SUBMITTAL E20070023.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-04-19 Cont ID  
Sent By pleduc Date 2021-04-19 Time   Rev Time 0.00
Received By pleduc Date 2021-04-09 Time 12:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-02-03 Cont ID  
Sent By pleduc Date 2021-02-03 Time   Rev Time 0.00
Received By pleduc Date 2021-01-29 Time 11:28 Sent To  
Notes
2021-01-29 11:28:12*********UPDATE:********
  
 2/3/20
  
 SPOKE WITH MR LEBLANC FROM SPINAOROUKE VIA TELEPHONE
 AND HE EXPLAINED HIS COMMENTS. THE BELOW COMMENTS HAS
 BEEN ADDRESSED AND ACCEPTED.
  
  
  
  
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 ***THE FOLLOWING COMMENTS ARE RESUBMITTED FOR
 CLARIFICATIONS:
  
 1) SHEET ALS 6.1 - IT IS NOT CLEAR WHERE THE 2ND EXIT
 OFF THE RECREATIONAL DECK IS LOCATED.
  
 PLEASE REVIEW AND CLEARLY INDICATE AND ACCOUNTING FOR
 THE REQUIRED SEPARATION DISTANCE AND OCCUPANT LOAD.
  
 NEW COMMENT:
  
 *** BASED ON THE RESPONSE PROVIDED OF 532 OCCUPANTS TO
 THE POOL DECK A 3RD EXIT IS REQUIRED
  
 7.4.1.2 THE NUMBER OF MEANS OF EGRESS FROM ANY STORY OR
 PORTION
 THEREOF, OTHER THAN FOR EXISTING BUILDINGS AS PERMITTED
 IN CHAPTERS
 11 THROUGH 43, SHALL BE AS FOLLOWS:
 (1) OCCUPANT LOAD MORE THAN 500 BUT NOT MORE THAN 1000
 ? NOT
 LESS THAN 3
 (2) OCCUPANT LOAD MORE THAN 1000 ? NOT LESS THAN 4
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC FIRE
 CODE REFERENCES.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-12-03 Cont ID  
Sent By pleduc Date 2020-12-03 Time   Rev Time 0.00
Received By pleduc Date 2020-11-19 Time 10:06 Sent To  
Notes
2020-12-02 14:18:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET ALS 6.1 - IT IS NOT CLEAR WHERE THE 2ND EXIT
 OFF THE RECREATIONAL DECK IS LOCATED.
  
 PLEASE REVIEW AND CLEARLY INDICATE AND ACCOUNTING FOR
 THE REQUIRED SEPARATION DISTANCE AND OCCUPANT LOAD.
  
  
 2) SHEET ALS 1.1 - THERE IS AN INDICATION OF AN EGRESS
 PASSAGEWAY AT STAIR # 3. THERE ARE 3 DOORS WITHIN THIS
 EXIT PASSAGEWAY, ONLY 2 ARE ALLOWED.
  
 PER NFPA 101 CH 7 MEANS OF EGRESS
  
 7.2.3.5 DISCHARGE.
 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE
 INTO A PUBLIC
 WAY, INTO A YARD OR COURT HAVING DIRECT ACCESS TO A
 PUBLIC WAY, OR
 INTO AN EXIT PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE
 WITHOUT
 OPENINGS, OTHER THAN THE ENTRANCE TO THE SMOKEPROOF
 ENCLOSURE AND
 THE DOOR OPENING TO THE OUTSIDE YARD, COURT, OR PUBLIC
 WAY. THE EXIT
 PASSAGEWAY SHALL BE SEPARATED FROM THE REMAINDER OF THE
 BUILDING
 BY A 2-HOUR FIRE RESISTANCE RATING.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NAARRATIVE.
  
  
 3) SHEETS P 1.0.1.A & 1.01.B - THERE ARE INDICATIONS OF
 UNDERGROUND FIRE LINES.
  
 ALL UNDERGROUND FIRE LINES SHALL SUBMITTED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS AND PER NFPA 24
 REQUIREMENTS
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGMENT.
  
  
  
 4) SHEET # 6.0.3 - THERE IS AN INDICATION OF A BDA
 SYSTEM.
  
 THE BDA SYSTEM SHALL SUBMITTED UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS AND PER NFPA 72 REQUIREMENTS
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGMENT.
  
  
 5) FIRE ALARM SHEETS - THERE ARE INDICATIONS OF PULL
 STATIONS THROUGHOUT THE OCCUPANCY.
  
 FOR INFORMATIONAL PURPOSES AND TO REDUCE FALSE ALARMS,
 PER NFPA 101, CH 30 & 9 , PULL STATIONS MAY BE
 ELIMINATED OR REDUCED PER THE AHJ.
  
 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 30.3.4.1 GENERAL.
 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR
 WITH MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE
 MEETING THE
 REQUIREMENTS OF 30.3.4.1.2, SHALL BE PROVIDED WITH A
 FIRE ALARM
 SYSTEM IN ACCORDANCE WITH SECTION 9.6, EXCEPT AS
 MODIFIED BY
 30.3.4.2 THROUGH 30.3.4.5.
  
 30.3.4.2 INITIATION.
 30.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM
 SHALL BE BY
 MANUAL MEANS IN ACCORDANCE WITH 9.6.2, UNLESS THE
 BUILDING
 COMPLIES WITH 30.3.4.2.2.
  
 30.3.4.2.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 30.3.5,
 REQUIRED FIRE ALARM SYSTEMS SHALL BE INITIATED UPON
 OPERATION OF
 THE AUTOMATIC SPRINKLER SYSTEM.
  
 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE
 DETECTION OR
 WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM
 SYSTEM IN
 ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN
 ONE MANUAL
 FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY
 HAVING
 JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE
 ALARM SIGNAL.
  
 BELOW IS THE APPENDIX NARRATIVE FOR INFORMATIONAL
 PURPOSES.
  
 A.9.6.2.6 THE MANUAL FIRE ALARM BOX REQUIRED BY 9.6.2.6
 IS INTENDED
 TO PROVIDE A MEANS TO MANUALLY ACTIVATE THE FIRE ALARM
 SYSTEM WHEN THE AUTOMATIC FIRE DETECTION SYSTEM OR
 WATERFLOW DEVICES
 ARE OUT OF SERVICE DUE TO MAINTENANCE OR TESTING, OR
 WHERE
 HUMAN DISCOVERY OF THE FIRE PRECEDES AUTOMATIC
 SPRINKLER SYSTEM
 OR AUTOMATIC DETECTION SYSTEM ACTIVATION. WHERE THE
 FIRE ALARM
 SYSTEM IS CONNECTED TO A MONITORING FACILITY, THE
 MANUAL FIRE
 ALARM BOX REQUIRED BY 9.6.2.6 SHOULD BE CONNECTED TO A
 SEPARATE
 CIRCUIT THAT IS NOT PLACED ?ON TEST? WHEN THE DETECTION
 OR SPRINKLER
 SYSTEM IS PLACED ON TEST. THE MANUAL FIRE ALARM BOX
 SHOULD BE
 LOCATED IN AN AREA THAT IS ACCESSIBLE TO OCCUPANTS OF
 THE BUILDING
 AND SHOULD NOT BE LOCKED.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE TO
 COORDINATE LOCATIONS WITH THE OFFICE OF THE FIRE
 MARSHAL.
  
 SHOULD THE EOR OR OWNER NOT WNAT TO REDUCE LOCATIONS,
 PROVIDE THAT APPLICABLE NOTE.
  
  
 6) FIRE ALARM SHEETS - THERE ARE INDICATIONS OF SMOKE
 DETECTION THROUGHOUT THE OCCUPANCY.
  
 FOR INFORMATIONAL PURPOSES AND TO REDUCE FALSE ALARMS,
 PER NFPA 101, CH 30 & 9 , COMPLETE SMOKE DETECTION IS
 NOT REQUIRED MAY BE ELIMINATED OR REDUCED.
  
 30.3.4.4 DETECTION. (RESERVED)
 30.3.4.5* SMOKE ALARMS. SMOKE ALARMS SHALL BE INSTALLED
 IN
 ACCORDANCE WITH 9.6.2.10 IN EVERY SLEEPING AREA,
 OUTSIDE EVERY
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS, AND ON
 ALL LEVELS OF THE DWELLING UNIT, INCLUDING BASEMENTS.
  
 9.6.2.9 WHERE A TOTAL (COMPLETE) COVERAGE SMOKE
 DETECTION
 SYSTEM IS REQUIRED BY ANOTHER SECTION OF THIS CODE,
 AUTOMATIC
 DETECTION OF SMOKE IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE
 ALARM AND SIGNALING CODE, SHALL BE PROVIDED IN ALL
 OCCUPIABLE
 AREAS IN ENVIRONMENTS THAT ARE SUITABLE FOR PROPER
 SMOKE DETECTOR
 OPERATION
  
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE TO
 COORDINATE LOCATIONS WITH THE OFFICE OF THE FIRE
 MARSHAL.
  
 SHOULD THE EOR OR OWNER NOT WNAT TO REDUCE LOCATIONS,
 PROVIDE THAT APPLICABLE NOTE.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-04-20 Cont ID  
Sent By lcrespo Date 2021-04-20 Time 07:42 Rev Time 0.00
Received By lcrespo Date 2021-04-18 Time 09:24 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-03-12 Cont ID  
Sent By lcrespo Date 2021-03-12 Time 14:29 Rev Time 0.00
Received By lcrespo Date 2021-03-03 Time 09:54 Sent To  
Notes
2021-03-12 14:30:3303/12/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-12-13 Cont ID  
Sent By lcrespo Date 2020-12-13 Time 10:04 Rev Time 0.00
Received By lcrespo Date 2020-12-12 Time 11:44 Sent To  
Notes
2020-12-13 10:04:5812/13/20 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SHOW ON ISOMETRIC DRAWING THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2017 FBC FG SECS. 402.4.1,
 402.4.2. 11.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE SPECIFY THE TYPE OF GAS (LP OR NATURAL) PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 4. THE SHUT-OFF VALVES ON ALL ALLIANCES NEED TO BE
 SHOWN IMMEDIATELY AHEAD OF EACH REGULATOR. 2017 FBC FG
 SEC. 409.4.
  
 5. PLEASE LIST THE TOTAL BTU LOAD OF ALL EQUIPMENT ON
 THE SYSTEM. REFER TO THE 2017 FBC FG SECS. 401.8
 THROUGH 402.6.1 AND TABLES 402.4 (1) THROUGH 402.4
 (37).
  
 6. PLEASE GIVE THE DISTANCE FROM THE POINT OF DELIVERY
 (GAS METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN
 THE BUILDING AND OR SYSTEM PER THE 2017 FBC FG SEC.
 402.4.1.
  
 7. PLEASE SHOW ON ISOMETRIC THE GAS RISER DETAIL 2/P
 0.3.2 NOTES PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FG SEC. 304.1, 614.5 (POOL HEATER).
  A. IF USING COMBUSTION AIR FOR A MECHANICAL COMBUSTION
 AIR SUPPLY SYSTEM, THE PLANS' INFORMATION NEEDS TO
 INDICATE WHERE THIS COMBUSTION AIR IS BEING SUPPLIED
 FROM.
  B. IF USING LOUVERS LOCATION FOR COMBUSTION AIR,
 PLEASE SHOW THE LOUVERS' LOCATION AND SIZE THAT ARE
 BEING INSTALLED F. THE LOUVERS CANNOT BE LOCATED ON AN
 EXTERIOR WALL THAT IS FIRE RATED AS THE WALL'S FIRE
 RATING MUST BE MAINTAINED PER THE WPB AMENDMENTS TO FBC
 SEC.107.2.1. 61.
 9. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER THE 2017 FBC FG SEC. 402.2 OR 2017 FBC
 RES. SEC. G2413.2.
  
 10. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FG SEC.305.1.
  
 11. PLEASE SHOW P 0.3.2 ISOMETRIC RISERS WHERE THE GAS
 PIPE IS COMING OR CONNECTING PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 12. PLEASE PLACE A NOTE ON BOTH SETS OF PLANS LISTING
 THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD
 BEING USED IN THIS SYSTEM'S DESIGN PER THE 2017 FBC FG
 SEC. 402.3.
  
 13. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC FG SEC. 410.1 OR 2017 FBC
 RES. SEC. G2421.1.
  
 14. PLEASE PROVIDE DETAIL OF ALL UNIONS IN FRONT OF
 REGULATOR 1? OF EITHER SIDE, DRIP LEG PER THE 2017 FBC
 RES. SEC G2421.2 OR 2017 FBC FG SEC 410.2.
  
 15. THE CITY OF WEST PALM BEACH WILL REQUIRE THE GAS
 SYSTEM TO BE PURGE AND ADMINISTERED BY A CITY
 INSPECTOR. PLEASE DESCRIBE HOW THE PURGE WILL TAKE
 PLACE BEFORE DOING THIS PROCESS AND WHEN SUBMITTED TO
 THE PLUMBING DEPARTMENT IN ADVANCE. PLEASE PROVIDE A
 NOTE ON PLANS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-05-18 Cont ID  
Sent By lmarchan Date 2021-05-18 Time 11:13 Rev Time 0.00
Received By lmarchan Date 2021-05-18 Time 10:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-14 Cont ID  
Sent By lmarchan Date 2021-05-14 Time 08:04 Rev Time 0.00
Received By lmarchan Date 2021-05-07 Time 13:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-22 Cont ID  
Sent By jleahy Date 2021-04-22 Time 06:11 Rev Time 0.00
Received By jleahy Date 2021-04-07 Time 16:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-12 Cont ID  
Sent By lcrespo Date 2021-03-12 Time 14:30 Rev Time 0.00
Received By lcrespo Date 2021-01-26 Time 08:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-13 Cont ID  
Sent By lcrespo Date 2020-12-13 Time 10:05 Rev Time 0.00
Received By lcrespo Date 2020-11-10 Time 15:58 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-05-14 Cont ID  
Sent By lmarchan Date 2021-05-14 Time 08:04 Rev Time 0.00
Received By lmarchan Date 2021-04-22 Time 09:15 Sent To  
Notes
2021-05-12 15:33:59RECEIPT MU-2021-021788 - $1,431,793.31 - PAID
2021-04-22 09:16:034/22/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-17 Cont ID  
Sent By rmcdouga Date 2020-11-17 Time 15:35 Rev Time 0.00
Received By rmcdouga Date 2020-11-17 Time 15:35 Sent To  
Notes
2020-11-17 15:36:56PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-05-11 Cont ID  
Sent By medwards Date 2021-05-11 Time 14:16 Rev Time 0.00
Received By medwards Date 2021-05-11 Time 13:20 Sent To  
Notes
2021-05-11 14:18:32MECHANICAL IS APPROVED FOR THIS PROJECT WITH A PRIVISO:
 THE DRYER ESHAUST TERMINATIONS WILL BE SUBMITTED AT A
 LATER DATE AND BEFORE ROUGH IN INSPECTIONS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-04-14 Cont ID  
Sent By medwards Date 2021-04-14 Time 13:29 Rev Time 0.00
Received By medwards Date 2021-04-14 Time 09:27 Sent To  
Notes
2021-04-14 13:31:51WE HAVE LOOKED AT THE VENT TERMINATION AGAIN AND WHILE
 IT MEETS FBC M 501.3.2 REQUIREMENTS FOR GENERAL EXHAUST
 VENT TERMINATION WITH THE SCREEN, LOUVER OR GRILLE A
 DRYER VENT TERMINATION HAS SPECIFIC REQUIREMENTS FOR
 THE VENT TERMINATION.
 FBC M 501.3.2EXHAUST OPENING PROTECTION.
 EXHAUST OPENINGS THAT TERMINATE OUTDOORS SHALL BE
 PROTECTED WITH CORROSION-RESISTANT SCREENS, LOUVERS OR
 GRILLES. OPENINGS IN SCREENS, LOUVERS AND GRILLES SHALL
 BE SIZED NOT LESS THAN 1/4 INCH (6.4 MM) AND NOT LARGER
 THAN 1/2 INCH (12.7 MM). OPENINGS SHALL BE PROTECTED
 AGAINST LOCAL WEATHER CONDITIONS. LOUVERS THAT PROTECT
 EXHAUST OPENINGS IN STRUCTURES LOCATED IN
 HURRICANE-PRONE REGIONS, AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING, SHALL COMPLY WITH AMCA
 STANDARD 550. OUTDOOR OPENINGS LOCATED IN EXTERIOR
 WALLS SHALL MEET THE PROVISIONS FOR EXTERIOR WALL
 OPENING PROTECTIVES IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 THE PRODUCT DOES MEET THIS SECTION OF THE CODE FOR
 TYPICAL EXHAUST VENT TERMINATION. THE CODE IS SAYING
 ALL EXHAUST TERMINATION OPENINGS MUST HAVE EITHER A
 SCREEN, LOUVER OR GRILLE.
 DRYER VENT TERMINATIONS HAVE THEIR OWN SET OF RULES
 SPECIFICALLY COVERED IN. FBC M 504.4 EXHAUST
 INSTALLATION.
 DRYER EXHAUST DUCTS FOR CLOTHES DRYERS SHALL TERMINATE
 ON THE OUTSIDE OF THE BUILDING AND SHALL BE EQUIPPED
 WITH A BACKDRAFT DAMPER. SCREENS SHALL NOT BE INSTALLED
 AT THE DUCT TERMINATION. DUCTS SHALL NOT BE CONNECTED
 OR INSTALLED WITH SHEET METAL SCREWS OR OTHER FASTENERS
 THAT WILL OBSTRUCT THE EXHAUST FLOW. CLOTHES DRYER
 EXHAUST DUCTS SHALL NOT BE CONNECTED TO A VENT
 CONNECTOR, VENT OR CHIMNEY. CLOTHES DRYER EXHAUST DUCTS
 SHALL NOT EXTEND INTO OR THROUGH DUCTS OR PLENUMS.
  
 BASED ON THIS CODE SECTION THE INTENT OF THE CODE IS TO
 NOT HAVE ANY RESTRICTIONS BEYOND THE BACKDRAFT DAMPER
 FOR ANY DRYER EXHAUST TERMINATION, THERE SHALL BE NO
 SCREEN, LOUVER OR GRILLE BEYOND THE BACKDRAFT DAMPER OF
 THE DRYER EXHAUST TERMINATION.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-02-16 Cont ID  
Sent By medwards Date 2021-02-16 Time 13:35 Rev Time 0.00
Received By medwards Date 2021-02-16 Time 13:12 Sent To  
Notes
2021-02-16 13:35:142ND REVIEW FBC-2020 MECHANICAL
 PERMIT-20101431
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE HEATING AND COOLING SIZING
 CALCULATIONS, I DO NOT SEE THE CALCULATIONS IN THIS
 SUBMITTAL. FBC EC C403.2.1
  
 2) PLEASE PROVIDE RESPONSE FOR QUESTION NUMBER 4 OF
 FIRST REVIEW. THE ENGINEER MUST ADDRESS THE RESTRICTION
 OF THE XVENT LOUVER FOR DRYER EXHAUST. THE DOCUMENT
 MENTIONED IN RESPONSE LETTER FROM XVENT WAS NOT
 INCLUDED IN THIS SUBMITTAL. FBC M 504.8.5.2
  
 3) SHEET M1.1.1B: PLEASE PROVIDE NOTES FOR EXHAUST FANS
 6 AND 8 SHOWING THEY COMPLY WITH FBC 717.5.4 EXCEPTION
 3.2 AND 3.6.
  
 4) SHEET M1.1.1B: PLEASE PROVIDE NOTES FOR THE FRESH
 AIR DUCT FOR AHU-A7 SHOWING IT COMPLIES WITH FBC
 717.5.4 EXCEPTION 3.2 AND 3.6.
  
 5) SHEET M1.2.1A: PLEASE PROVIDE NOTES FOR EF-1 DUCT
 SHOWING IT WILL COMPLY WITH FBC 717.5.4 EXCEPTION 3.2
 AND 3.6.
  
 6) SHEET M1.2.1B: THERE ARE SEVERAL KEYNOTE NUMBERS ON
 THIS SHEET BUT THERE ARE NO KEYNOTES CORRESPONDING WITH
 THESE NUMBERS. PLEASE ADD THE CORRESPONDING KEYNOTES TO
 THIS SHEET. FBC 107.2.1
  
 7) SHEET M1.3.1A: PLEASE EXPLAIN NOTE 6, IS THIS NOTE
 ONLY FOR THE EXHAUST DUCT FROM ELECTRIC ROOM TO SHAFT?
 HOW ARE YOU PROTECTING THE EXHAUST DUCT FOR THE
 CORRIDOR EXHAUST? IF THE DUCT MEETS 717.5.4 (3) WHY USE
 THE FIRE WRAP? FBC 107.2.1
  
 8) PLEASE PROVIDE A RISER DETAIL DRAWING OF THE
 SUBDUCT AND SHOW SIZE OF DUCT AND EACH FLOOR WITH ALL
 DUCTS. FBC 107.2.1
  
 9) PLEASE SHOW THE EXHAUST DUCT IN THE ELECTRIC ROOMS
 IN THE CORRIDORS DOES NOT STOP AT THE RATED WALL AS
 THIS DOES NOT MEET FBC 717.5.4 (3.5)
  
 10) SHEET M1.3.1B: PLEASE PROVIDE A DETAIL DRAWING OF
 THE GENERATOR EXHAUST FLUE. FBC 107.2.1
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-03 Cont ID  
Sent By medwards Date 2020-12-03 Time 14:39 Rev Time 0.00
Received By medwards Date 2020-11-16 Time 11:22 Sent To  
Notes
2020-12-03 14:40:141ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20101431
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE HEATING AND COOLING SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 2) SHEET M0.3.1- VENTILATION SCHEDULES INDICATES THE
 PUBLIC TOILET ROOMS EXHAUST FANS ARE EXHAUSTING 50 CFM.
 SHEET M0.2.2 FAN SCHEDULE INDICATES EF-1 EXHAUSTS 75
 CFM AND IS INTERLOCKED WITH WALL LIGHT SWITCH. FBC M
 TABLE 403.3.1.1 NOTE E INDICATES THE 50 CFM MUST BE FOR
 CONTINUOUS OPERATION. PLEASE USE THE 75 CFM IN THE
 VENTILATION CALCULATIONS OR REMOVE CONTROL TYPE 2 AND
 MAKE THE EF-1 CONTINUOUSLY OPERATED.
  
  
 3) SHEET M0.4.2- DETAIL 1: 504.8.5 LENGTH
 IDENTIFICATION.
 WHERE THE EXHAUST DUCT EQUIVALENT LENGTH EXCEEDS 35
 FEET (10 668 MM), THE EQUIVALENT LENGTH OF THE EXHAUST
 DUCT SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG.
 THE LABEL OR TAG SHALL BE LOCATED WITHIN 6 FEET (1829
 MM) OF THE EXHAUST DUCT CONNECTION.
  
 4) PLEASE PROVIDE A LETTER FROM THE DRYER MANUFACTURER
 STATING THAT THE X VENT DRYER EXHAUST TERMINATION IS
 ALLOWED WITH EACH SPECIFIC DRYER. THE X VENT IS UNIQUE
 IN THE FACT THAT IT USES BOTH THE BACK-DRAFT DAMPER AND
 THE LOUVER. THE INSTALLATION MANUAL DOES NOT ADDRESS
 THIS KIND OF INSTALLATION. WITH THE X VENT SYSTEM THE
 BOX OF THE X VENT IS MOUNTED INTO THE EXTERIOR OF THE
 WALL AND THE LOUVER IS FLUSH TO THE EXTERIOR WALL. THE
 EXHAUST OF THE DRYER MUST TRAVEL THROUGH THE EXHAUST
 DUCT, OPEN THE BACK-DRAFT DAMPER AND TRAVEL THROUGH THE
 X VENT COVER (LOUVER) BEFORE IT IS EXHAUSTED TO THE
 OUTDOORS. BECAUSE THIS PRODUCT USES BOTH THE BACK-DRAFT
 DAMPER AND THE OUTER COVER OF THE BOX (LOUVER) INSTEAD
 OF EITHER THE BACK-DRAFT DAMPER OR THE LOUVER AS
 TYPICALLY SEEN IN THE MANUFACTURES INSTALLATION MANUAL
 THE OUTER LOUVER IS A RESTRICTION THAT MUST BE
 ADDRESSED. IN LIEU OF THE MANUFACTURES LETTER STATING
 THE MAXIMUM DRYER EXHAUST DUCT TO BE USED WITH THE X
 VENT SYSTEM THE ENGINEER OF RECORD MUST DETERMINE THE
 AMOUNT OF RESTRICTION THIS CREATES AND THE EFFECT TO
 THE DRYER EXHAUST DUCT LENGTH. THE ENGINEER OF RECORD
 MUST SUBMIT THE CALCULATIONS AND PROVIDE MAX. EXHAUST
 DRYER DUCT LENGTHS FOR EACH DRYER USED IN THIS PROJECT.
 FBC M 504.8.4.2
  
 5) SHEET M0.6.1- GARAGE EXHAUST SEQUENCE OF OPERATIONS:
 THE SEQUENCE OF OPERATION MUST ALSO INCLUDE NITROGEN
 DIOXIDE DETECTORS. FBC M 404.1
 404.1ENCLOSED PARKING GARAGES.
 WHERE MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED
 PARKING GARAGES OPERATE INTERMITTENTLY, SUCH OPERATION
 SHALL BE AUTOMATIC BY MEANS OF CARBON MONOXIDE
 DETECTORS APPLIED IN CONJUNCTION WITH NITROGEN DIOXIDE
 DETECTORS. SUCH DETECTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH THEIR MANUFACTURERS? RECOMMENDATIONS.
  
 6) SHEET M1.1.1A: PLEASE SHOW THE DAMPERS AT THE RATED
 WALL AND FLOOR PENETRATIONS FOR THE DUCT WORK GOING UP
 TO AHU-A1 AND AHU-A2. FBC M 607
  
 7) SHEET M1.1.1A: AHU-A2 IS SUPPLYING 1250 CFM?S
 AIRFLOW TO THE LEASING AREA. SHEET M0.2.1 SPLIT SYSTEM
 DX SCHEDULE INDICATES THE AIRFLOW RATE FOR AHU-A2 IS
 700 CFM?S OF AIRFLOW. PLEASE CORRECT THIS. FBC 107.2.1
  
 8) SHEETS M1.1.1A, M1.11.1B, M1.2.1B: AHU-A1 IS
 SUPPLYING 1,800 CFM, SHEET M0.2.1 SPLIT SYSTEM DX
 SCHEDULE INDICATES THAT AHU-A1 IS 1400 CFM?S OF AIR
 FLOW. PLEASE CORRECT THIS. FBC 107.2.1
  
 9) SHEET M1.1.1B: PLEASE MAKE SURE NOTE 8 INCLUDES ALL
 PENETRATIONS IN RATED WALLS. THE WALL SEPARATING THE
 PARKING GARAGE AND THE STORAGE ROOM IS BEING PENETRATED
 BY THE STAIR PRESSURIZATION DUCT WORK.
  
  
 10) SHEET M1.1.1B: THE EF-2 EXHAUST FAN DUCT FOR THE
 GENERATOR ROOM IS PASSING THROUGH SEVERAL 2 HOUR RATED
 WALLS. PLEASE SHOW HOW THE PENETRATIONS IN THESE RATED
 WALLS ARE TO BE PROTECTED. FBC M 607
  
 11) SHEET M1.1.1B: THE GENERATOR EXHAUST PIPE IS
 PENETRATING RATED WALLS AND TRAVELING THROUGH THE
 EGRESS CORRIDOR. PLEASE SHOW HOW THE PENETRATIONS IN
 THE RATED WALLS WILL BE PROTECTED. FBC M607
  
 12) SHEET M1.1.1B: THE GENERATOR EXHAUST PIPE CANNOT
 PASS THROUGH THE EGRESS CORRIDOR. FBC 1024.6
  
 13) SHEET M1.1.1B: EF-6 AND 8; THE DUCTWORK FOR THESE
 EXHAUST FANS ARE PENETRATING SEVERAL RATED WALLS,
 PLEASE SHOW THE RATED DAMPERS AT EACH PENETRATION. FBC
 M607
  
 14) SHEET M1.1.1B:THE FRESH AIR DUCT FOR AHU-A7 IS
 PENETRATING A RATED WALL, PLEASE PROVIDE A RATED DAMPER
 AT THE PENETRATION. FBC M 607
  
 15) SHEET M1.2.1A: EF-1 DUCT WORK IS PENETRATING RATED
 WALLS, PLEASE SHOW RATED DAMPERS AT EACH PENETRATION.
 FBC M 607
  
 16) SHEET M1.2.1A: AHU-3 IS SUPPLYING 2220 CFM?S TO THE
  
 17) SHEET M1.2.1B: THERE ARE NO NOTES ON THIS SHEET.
 NOTE 6 IN THE PARKING GARAGE APPEARS TO BE FOR A
 SENSOR. PLEASE PROVIDE NOTES FOR THIS SHEET. FBC
 107.2.1
  
  
 18) SHEET M1.3.1A: PLEASE SHOW THE DAMPER FOR THE
 ELECTRIC ROOM EXHAUST AT RATED WALL. FBC M 607
  
 19) SHEET M1.4.1A: PLEASE SHOW THE DAMPER FOR THE
 ELECTRIC ROOM EXHAUST AT RATED WALL. FBC M 607
  
 20) SHEET M1.5.1A: PLEASE SHOW THE DAMPER FOR THE
 ELECTRIC ROOM EXHAUST AT RATED WALL. FBC M 607
  
 21) SHEET M1.6.1A: AHU-A4 IS SUPPLYING 2640 CFM TO THE
 FITNESS CENTER AREA, NO CFM?S LABELED FOR THE WOMEN?S
 TOILET ROOM. SHEET M0.2.1 SPLIT SYSTEM DX SCHEDULE
 INDICATES AHU-A4 SUPPLIES 1400CFM?S OF AIR FLOW. PLEASE
 CORRECT THIS. FBC 107.2.1
  
 22) SHEET M1.6.1A: AHU-A5 IS SUPPLYING 1200 CFM TO THE
 EXERCISE ROOM. SHEET M0.2.1 SPLIT SYSTEM DX SCHEDULE
 INDICATES AHU-A5 SUPPLIES 700 CFM TO THE EXERCISE ROOM.
 PLEASE CORRECT THIS. FBC 107.2.1
  
 23) SHEET M1.6.1A: THE OUTDOOR AIR DUCT FOR AHU-A5 FOR
 THE EXERCISE ROOM IS PENETRATING A RATED WALL. PLEASE
 PROVIDE A RATED DAMPER AT THIS PENETRATION. FBC M 607
  
 24) SHEET M1.6.1A: THE OUTDOOR AIR DUCT FOR THE
 VESTIBULE IS PENETRATING A RATED WALL AND APPEARS TO BE
 FLEX DUCT. PLEASE PROVIDE A RATED DAMPER AT THIS
 PENETRATION. FBC M 607
  
 25) SHEET M1.6.1A: PLEASE SHOW THE DAMPER FOR THE
 ELECTRIC ROOM EXHAUST AT RATED WALL. FBC M 607
  
 26) SHEET M1.6.1A: PLEASE IDENTIFY THE EXHAUST FAN FOR
 THE TOILETS IN THE FITNESS CENTER AREA. FBC 107.2.1
  
 27) SHEET M1.6.1A: PLEASE PROVIDE THE CFM?S TO THE
 BATHROOM GRILLE?S PROVIDED BY AHU-A4. FBC M 403.3.1.2
  
 28) SHEET M1.7.1A: PLEASE SHOW THE DAMPER FOR THE
 ELECTRIC ROOM AND STORAGE ROOM EXHAUST AT RATED WALL.
 FBC M 607
  
 29) SHEET M1.8.1A: NOTE 6 DISCUSSES SUPPLY AND EXHAUST
 AIR DUCTWORK SERVING THE DOAS. BUT NOTE 7 LIST THE
 DUCTWORK AS THE RISER FOR THE TRASH ROOM EXHAUST. IT
 APPEARS THAT THIS IS ONE AND THE SAME DUCTWORK. WHY
 WOULD THE TRASH ROOM EXHAUST BE GOING BACK TO THE DOAS
 UNIT? PLEASE MAKE THIS CLEARER FOR THE MECHANICAL
 REVIEWER. FBC 107.2.1
  
 30) SHEET M1.8.1B: NOTE 3 MENTIONS A DUCTLESS AIR
 HANDLER, THE KEYNOTE 3 SYMBOL IS IN THE ELEVATOR LOBBY
 AREA. PLEASE SHOW THE DUCTLESS AIR HANDLER ON THE
 DRAWING AND IDENTIFY IT ON THE SCHEDULES SHEET. FBC
 107.2.1
  
 31) SHEET M1.6.1A: AHU-A4 IS SUPPLYING 2640 CFM TO THE
 FITNESS CENTER AREA, NO CFM?S LABELED FOR THE WOMEN?S
 TOILET ROOM. SHEET M0.2.1 1 SPLIT SYSTEM DX SCHEDULE
 INDICATES AHU_A4 SUPPLIES 1400CFM?S OF AIR FLOW. PLEASE
 CORRECT THIS. FBC 107.2.1
  
 32) SHEET M0.3.1 VENTILATION SCHEDULES: AHU-A1
 INDICATES THAT 210 CFM OF OUTDOOR AIR IS REQUIRED FOR
 THIS AREA OF THE BUILDING. SHEET M0.2.1 SPLIT SYSTEM DX
 SCHEDULE INDICATES AHU-A1 IS SUPPLYING 160 CFM TO THIS
 AREA. PLEASE CORRECT THIS. FBC 107.2.1
  
 33) SHEET M0.3.1 VENTILATION SCHEDULES: AHU-A2
 INDICATES THAT 87 CFM OF OUTDOOR AIR IS REQUIRED FOR
 THIS AREA. SHEET M0.2.1 SPLIT SYSTEM DX SCHEDULE
 INDICATES AHU-A2 IS SUPPLYING 80 CFM TO THIS AREA.
 PLEASE CORRECT THIS. FBC 107.2.1
  
 34) SHEET M0.3.1 VENTILATION SCHEDULES: AHU-A3
 INDICATES THAT 240 CFM OF OUTDOOR AIR IS REQUIRED FOR
 THIS AREA. SHEET M0.2.1 SPLIT SYSTEM DX SCHEDULE
 INDICATES AHU-A3 IS SUPPLYING 125 CFM TO THIS AREA.
 PLEASE CORRECT THIS. FBC 107.2.1
  
 35) SHEET M0.3.1 VENTILATION SCHEDULES: AHU-A4
 INDICATES THAT 385 CFM IS REQUIRED FOR THIS AREA. SHEET
 M0.2.1 SPLIT SYSTEM DX SCHEDULE INDICATES AHU-A4 IS
 SUPPLYING 160 CFM TO THIS AREA. PLEASE CORRECT THIS.
 FBC 107.2.1
  
 36) SHEET M0.2.1 AHU-B INDICATES 750-800 SUPPLY AIR
 FLOW. SHEET M9.1.2 UNIT TYPE 4 INDICATES AHU-B IS
 SUPPLYING 865 CFM FOR THIS UNIT. PLEASE CORRECT THIS.
 FBC EC C403.2.1
  
 37) SHEET M9.1.3: UNIT TYPE 5 SUPPLY DUCT FOR KITCHEN
 AREA IS MISSING THE SUPPLIED CFM?S. PLEASE SHOW THE
 CFM?S FOR THIS AREA. FBC EC C403.2.1
  
 38) SHEET M0.2.1 AHU-B INDICATES 750-800 SUPPLY AIR
 FLOW. SHEET M9.1.8 UNIT TYPE 13 INDICATES 890 CFM BEING
 SUPPLIED TO THIS UNIT. PLEASE CORRECT THIS. FBC EC
 C403.2.1
  
 39) SHEET M0.2.1 AHU-C INDICATES 950-100CFM OF SUPPLY
 AIR FLOW. SHEET M9.1.9 UNIT 15 INDICATES AHU-C IS
 SUPPLYING 1,050 CFM OF AIR FLOW. PLEASE CORRECT. FBC EC
 C403.2.1
  
 40) SHEET M0.2.1 AHU-C INDICATES 950-100 CFM OF SUPPLY
 AIR FLOW. SHEET M9.1.12 UNIT TYPE 17 INDICATES AHU-C IS
 SUPPLYING 1,070 CFM OF AIR FLOW. PLEASE CORRECT. FBC EC
 C403.2.1
  
 41) PLEASE PROVIDE CALCULATIONS FOR THE PARKING GARAGE
 VENTILATION. FBC M 404
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-04-20 Cont ID  
Sent By lcrespo Date 2021-04-20 Time 07:43 Rev Time 0.00
Received By lcrespo Date 2021-04-18 Time 09:24 Sent To  
Notes
2021-04-20 07:44:3504/20/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-03-12 Cont ID  
Sent By lcrespo Date 2021-03-12 Time 13:49 Rev Time 0.00
Received By lcrespo Date 2021-03-03 Time 09:54 Sent To  
Notes
2021-03-12 13:40:0203/12/21 2ND REVIEW PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 PLEASE NOTE THAT WE CAN DO A ZOOM MEETING FOR THIS
 REVIEW TO CLARIFY THE IN-QUESTION COMMENT IF NEEDED.
 YOU MAY CONTACT ME VIA PHONE OR EMAIL TO SET THIS
 MEETING UP AT YOUR CONVENIENCE.
  
 1. THE RESPONSE TO COMMENT NOT FOUND OR NEW DRAWING;
 PLEASE PROVIDE PAGE AND OR DETAIL REFERENCE; SHEET 5 OF
 16 REFERS TO 45,800 CUBIC FOOT TANK STORAGE CHAMBERS.
 SUBMIT A DETAIL OF THIS STORAGE ARRANGEMENT, IT'S
 PURPOSE AND ANY/ ALL ASSOCIATED PIPING, PUMPS AND/OR
 ANY OTHER DETAILS ASSOCIATED WITH THIS SYSTEM. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 2. SHEETS, ALS 0.2, ALS 0.3, ALS 0.4, ALS 0.5, THE
 REFERENCE NOTES HAVE FAIR HOUSING ACT DESIGN MANUAL
 (1998), WHICH IS FINE BUT ALSO NEEDS TO HAVE THE
 REFERENCES TO THE ANSI A117.1 1986, AND THIS IS THE ONE
 THAT SHOULD BE USED IN COMMON AREAS. THE ANSI 2009 WAS
 USED IN SOME COMMENT IN THE LAST REVIEW WHICH DOES NOT
 APPLY AND SHOULD BE NOTED THE SAFE HARBORS IN USE.
 PLEASE MAKE CHANGES PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 A. ON SHEET ALS 0.1, PLEASE PLACE A NOTE THAT THE BUILT
 OUT AREA SHALL BE BUILT TO THE CURRENT FLORIDA BUILDING
 CODE ACCESSIBILITY.
  
 B. A. ON ALL NOTE ON THESE PAGES, A NOTE THAT STATES
 FHA DESIGN MANUAL (1998 ED.) IS FINE, BUT THE PART OF
 ADA FBC 2017 WILL NEED TO BE REMOVED. ANY CODE
 REFERENCE NOTES TO THE ACCESSIBILITY CODE FBC NEED TO
 BE REMOVED AS WELL.
  
 C. ON ALS 0.02, PLEASE PROVIDE THE DISTANCE FROM THE
 WALL ON THE TOILET WHERE IT GIVES THE REAR GRAB OF THE
 BAR OF 1'- 6" ABSOLUTE AND REMOVES THE 16? FROM THE
 COMPARTMENT DRAWING PER THE ANSI 117.1 1886 4.16.2. THE
 GRAB BARS FOR THE SUPPORT NEED TO COMPLY WITH THE ANSI
 117 4.24.3, AND THE BACKING ON THE DETAIL MAY NOT BE
 ENOUGH FOR THE ALLOWABLE STRESS OF 250 LBS. PLEASE
 ADDRESS THE APPLICATION OR INCREASE THE SIZE OF THE
 BACKING; PROVIDE DETAIL IF POSSIBLE. THE HEIGHT OF GRAB
 BARS FOR THE TOILET IS NOT CONSISTENT, AND THEY NEED TO
 MEASURE TO THE CENTER OF THE BAR PER THE ANSI 4.17.6.
 THE GRAB BAR IN A VERTICAL POSITION IS NOT IN ANY OF
 THE STANDARDS REFERENCES, AND THERE ARE NO EXCEPTIONS.
 PLEASE REMOVE ALL DRAWINGS PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 D. ON SHEET ALS.0.4, NO ACTION WAS TAKEN ON THIS
 COMMENT. THERE ARE FHA DETAILS WITH ADA, ACCESSIBLY /
 ICC ANSI A117.1-2009 NOTES; PLEASE CORRECT THEM. PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. PLEASE PROVIDE THE MAXIMUM HEIGHT AND CLEARANCE FOR
 URINAL PARTITIONS PER THE 2017 FBC P 405.3.5 URINAL
 PARTITIONS.
  
 3. HUD RECOGNIZES TEN SAFE HARBORS FOR COMPLIANCE WITH
 THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION
 REQUIREMENTS. THE ICC/ANSI A117.1 - 2009 IS NOT LISTED
 AS A SAFE HARBOR. HUD SAID IN THE INTRODUCTION TO THE
 ACCESSIBILITY GUIDELINES, "BUILDERS AND DEVELOPERS MAY
 CHOOSE TO DEPART FROM THESE GUIDELINES AND SEEK
 ALTERNATE WAYS TO DEMONSTRATE THAT THEY HAVE MET THE
 REQUIREMENTS OF THE FAIR HOUSING ACT." THE STANDARD
 EMPLOYED MUST MEET ALL OF THE DESIGN AND CONSTRUCTION
 REQUIREMENTS SPECIFIED IN THE FAIR HOUSING ACT AND
 HUD'S FAIR HOUSING ACT REGULATIONS, AND PROVIDE THE
 SAME OR A STRICTER DEGREE OF ACCESSIBILITY THAN THE
 RECOGNIZED SAFE HARBORS. FAIR HOUSING ACT DESIGN
 MANUAL, PAGE 13. PREAMBLE TO THE GUIDELINES, 56 FR
 9478-79, MARCH 6, 1991. THE PURPOSE OF THE FAIR HOUSING
 ACT GUIDELINES IS "TO DESCRIBE THE MINIMUM STANDARDS OF
 COMPLIANCE WITH THE SPECIFIC ACCESSIBILITY REQUIREMENTS
 OF THE ACT." PREAMBLE TO THE GUIDELINES, 56 FR 9472,
 9476, MARCH 6, 1991. VERIFICATION MUST BE PROVIDED THAT
 THE 2009 EDITION OF THE ANSI A117.1 PROVIDES THE SAME
 OR A STRICTER DEGREE OF ACCESSIBILITY THE RECOGNIZED
 SAFE HARBORS.
  
 4. DONE.
  
 5. PLEASE ADDRESS COMMENT TWO AND REMOVE ADA FBC 2017
 DETAIL ON TITLE BLOCK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PLEASE REFER TO COMMENT TWO FOR CORRECTIONS; SHEET.
 ALS 0.2 - DRINKING FOUNTAIN DETAILS - THE DETAIL TITLE
 REFERS TO THE ANSI 2009 EDITION BUT NOTE #1 REFERS TO
 THE FLORIDA BUILDING CODE. THE COMMON AREAS SHALL
 COMPLY WITH THE APPLICABLE STANDARD USED FOR FAIR
 HOUSING DESIGN COMPLIANCE. THE FLORIDA BUILDING CODE
 DOES NOT APPLY TO THE COMMON AREAS OF THE BUILDING. THE
 FLORIDA BUILDING CODE WOULD APPLY TO ANY RETAIL OR
 TENANT SPACES THAT DO NOT FALL UNDER FAIR HOUSING
 REQUIREMENTS. THE SAME APPLIES TO THE URINAL DETAIL.
 REVISE THE NOTES.
  
 7. DONE.
  
 8. DONE.
  
 9. DONE.
  
 10. THERE IS NO INFORMATION ON THIS PAGE THAT SEEMS TO
 HAVE TWO-THIRD OF THE DETAILS DELETE. IF THIS IS IN
 ERROR, PLEASE CLARIFY. PLEASE REFER TO COMMENT TWO AND,
 IF NEEDED, PUT BACK INFORMATION THAT WILL BE REQUIRED
 FOR THESE PLANS; SHT. ALS 0.3 - ACCESSIBLE WATER
 CLOSETS DETAIL - SECTION 1003.11.2.4.4 OF THE NOTED
 ANSI STANDARD REQUIRES THE CLEARANCE AT THE WATER
 CLOSET TO BE 66 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL WHEN A LAVATORY IS LOCATED NEXT TO
 THE WATER CLOSET FOR TYPE "A" ACCESSIBLE WATER CLOSETS.
 THE DEPTH OF THE LAVATORY SHALL BE A MAXIMUM OF 24
 INCHES.
  
 11. SOME GRAB BARS ARE 36" TO THE TOP AND OTHERS 36" TO
 THE MIDDLE. ARE THESE FHA OR ACC REFERENCES? SEE
 COMMENT TWO? PLEASE CLARIFY PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 12. THIS COMMENT IS NOT CLEAR ABOUT WHAT WAS CORRECTED
 TO ITS REFERENCE OF THE DETAILS; SHOW THE CLEAR FLOOR
 SPACE DIMENSIONS FOR THE WATER CLOSETS ON ALL THE WATER
 CLOSET DETAILS ON THE FHA DRAWINGS. COMPLY WITH THE
 REQUIREMENTS FROM THE DESIGN STANDARD BEING USED.WPB
 AMEND. TO FBC
 SEC. 107.2.1.
  
 13. ITEM REMOVE.
  
 14. DONE.
  
 15. DONE.
  
 16. DONE.
  
 17. COULD NOT LOCATE THE PAGE REFERENCE GIVEN ALS 6.1.
 NO SUCH PAGE NUMBER. PLEASE CLARIFY.
  
 18. COULD NOT LOCATE THE PAGE REFERENCE GIVEN ALS 6.1.
 NO SUCH PAGE NUMBER. PLEASE CLARIFY.
  
 19. DONE.
  
 20. DONE.
  
 21. DONE.
  
 22. DONE.
  
 23. DONE.
  
 24. THE RESPONSE TO THE COMMENT IS NOT CORRECT; PLEASE
 REFER TO THE DESIGN MANUAL PAGE 7.43 AND FIGURE 7.44;
 THE MAXIMUM DEPTH OF THE LAVATORIES SHALL BE 24 INCHES.
 THE PLANS SHOW SOME OF THE LAVATORIES AS 25 1/2 INCHES
 DEEP. INDICATE ON THE UNIT FLOOR PLANS THAT THE
 LAVATORIES' MAXIMUM DEPTH IS 24 INCHES PER ANSI A117.1.
  
 25. DONE.
  
 26 SECOND REQUEST; SHEET A9.17.1 - UNIT 17 - SHOWS THE
 WATER CLOSET IN THE MASTER BATH LOCATED 2 FEET 5 INCHES
 ( 2'- 5" ) FROM THE ADJACENT WALL TO THE WATER CLOSET'S
 CENTERLINE. THE WATER CLOSET SHALL BE 18 INCHES FROM
 SIDE TO ITS CENTERLINE PER THE FHAGL PAGE 6.5.
  
 27. SHEET A9.20.1 - UNIT 20 ? IS MISSING THE TYPE FOR
 FHA; IS IT AN A OR A B UNIT?? PLEASE PROVIDE PER WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 28. DONE.
  
 29. DONE.
  
 30. DONE.
  
 31. DONE.
  
 32. DONE.
  
 A. DONE.
  
 33. DONE.
  
 34. DONE.
  
 35. PLEASE HAVE ENGINEER ADDRESS SHEET P 1.0.1. THE
 GRID NUMBERS AND LETTERS ARE ON TOP OF EACH OTHER IN
 SOME PLACES, AND PLEASE OFFSET OR MOVE AWAY FOR CLARITY
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. THIS IS TYPICAL
 ON ALL PLUMBING PAGES, SO NOT TO REPEAT EVERY COMMENT;
 IT IS NOTED IN THIS ONE ONLY.
  
 A. DONE.
  
 36. PLUMBING RISERS WILL BE MOVED TO THE INSIDE FACE OF
 THE COLUMN DURING THE SHOP DRAWING COORDINATION TO
 ALLOW THE CONCRETE COLUMN TO PROVIDE PROTECTION. PLEASE
 PLACE A NOTE ON THE PLANS ON THIS COMMENT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 IN ANSWER TO THE RESPONSE, PLEASE NOTE THE REFERENCE
 PAGES; PLUMBING RISERS WILL BE MOVED TO THE INSIDE FACE
 OF THE COLUMN DURING THE SHOP DRAWING COORDINATION TO
 ALLOW THE CONCRETE COLUMN TO PROVIDE PROTECTION.
  
 A. GRIDLINE LETTERS ARE NOT SHOWN. PLEASE MOVE THE
 DRAWING OVER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. DONE.
  
 C. SECOND REQUEST; THE STORAGE ROOM WITH THE LAUNDRY
 TRAY IS NOT LABELED NEXT TO THE ELEVATORS; PLEASE LABEL
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. DONE.
  
 37. DONE.
  
 A. DONE.
  
 38. DONE.
  
 39. DONE.
  
 40 DONE.
  
 41. SECOND REQUEST; SHEET P 1.5.B, IN THE POOL AREA, SO
 MANY MISSING CIRCLES AND LINES INDICATE THAT A PIPE IS
 GOING UP OR DOWN IN THE POOL AREA. PLEASE OVERLAY AND
 MATCH TO P 1.6.B; THERE ARE TOO MANY TO MENTION ON THIS
 PAGE I. E. PD, TD PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 42. DONE.
  
 A. DONE
  
 B. DONE.
  
 43. DONE.
  
 A. SECOND REQUEST, THERE IS ON V.2 FOR P0.2.1, PLEASE
 PROVIDE DETAILS FOR PLANT DRAINS AND PUT A REFERENCE ON
 KEYNOTE LEGEND PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 E. DONE.
  
 44. SECOND REQUEST; SHEET P 1.7.1A, THE GRID LINES ON
 THE LEFT BOTTOM ARE OFF THE PLOTTED DRAWING AND OTHER
 OVERLAPPED (AS MENTION BEFORE, PLEASE CORRECT ALL
 OVERLAPS IN ALL PAGES); PLEASE MOVE OVER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 45. DONE.
  
 A. SECOND REQUEST, PLEASE GIVE THE LOCATION. THERE IS
 NO LAYOUT SHOWING THE RD-1 AND HB-3; PLEASE PROVIDE A
 REFERENCE IF ON ANOTHER PAGE OR GENERATE ONE PLEASE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 46. SECOND REQUEST, THERE IS NO V.2 AVAILABLE; SHEET P
 1.8.1B, THERE IS AN AREA WHERE THE TRENCH DRAINS ARE,
 AND THEY ARE NOT LABELED. PLEASE LABEL PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 A. SECOND REQUEST, THERE IS NO V.2 AVAILABLE; SHEET;
 THERE IS NO LAYOUT SHOWING THE RD-1 AND TD-1; PLEASE
 PROVIDE ON PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 47. SECOND REQUEST; SHEET P 9.0.1, DETAIL 2 FOR THE
 FITNESS CENTER IT HAS A 6" PIPE COMING UP, NOT SIZED
 AND NOT LABELED OR WITH A REFERENCE POINT, ALSO SIZE
 THE HORIZONTAL 4" LINE GOING TO THE MEN'S ROOM, AND THE
 LADIES ROOM DOWNSTREAM HAS A FEW 3" AND 4" NOT SIZED AS
 WELL. PLEASE PROVIDE SIZES PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 A. SECOND REQUEST; ON THAT SAME DETAIL, THERE IS A 4"
 SANITARY LINE WITH NO LABEL AS TO WHERE IT IS GOING.
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. SECOND REQUEST; PLEASE SHOW ALL TRAP PRIMERS ON THE
 FLOOR DRAINS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. SECOND REQUEST; LAVATORIES ON ALL AP-3 NEED TO BE
 SHOWN HORIZONTALLY AS THEY SEEM TO BE IN AN S-TRAP
 POSITION. PLEASE CHANGE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. SECOND REQUEST; THERE ARE THREE 3" SANITARY PIPES
 GOING UP WITH NO DESTINATION VENT. PLEASE LABEL PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 E. SECOND REQUEST; THERE ARE TWO FLOATING FITTING AND A
 PIPE WITH A 90-DEGREE ELBOW GOING DOWN AND A WYE AT THE
 END; IT DOESN'T HAVE A SIZE OR DESTINATION; PLEASE
 REMOVE AND OR GIVE A REFERENCE TO ITS USE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. SECOND REQUEST; ON DETAIL FOUR, PLEASE SHOW SHUTOFF
 VALVES FOR THE RECIRCULATING PUMP AT THE FITNESS ROOM
 AREA WITH AN ACCESS BOX ON BOTH SIDES OF THE
 RECIRCULATING PUMP FOR THE WATER HEATER AND ALL
 FIXTURES PER THE 2017 FBC SEC. P 606.1.
  
 G. SECOND REQUEST; PLEASE SHOW AND LABEL ON ISOMETRIC
 THE HAMMER ARRESTOR FOR THE DRINKING FOUNTAIN AND ALL
 QUICK CLOSING VALVES PER THE 2017 FBC SEC. P 604.9.
  
 H. SECOND REQUEST; PLEASE SHOW AND LABEL CHECK VALVES
 ON THE RECIRCULATING SYSTEM PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 I. SECOND REQUEST; THE RECIRCULATING MANIFOLD TO THE
 HOT WATER LINES MAY NEED TO BE CLOSER TO THE OUTLET
 SOURCE; PLEASE REFER TO THE 2017 FBC ENERGY CODE TABLE
 C404.5.1.
  
 J. DONE.
  
 K. SECOND REQUEST; ON DETAIL ONE, AP-9 IS LABELED AS A
 FLOOR DRAIN; PLEASE MARK AS MOP SINK AND HAVE A NOTE
 THAT SURROUNDING THE WALL SHALL BE NON-ABSORBENT
 SURFACE IN ACCORDANCE WITH THE 2017 FBC BUILDING SEC.
 1210.2.2.
  
 L. SECOND REQUEST; IN THAT SAME DETAIL, THE MOP SINK
 AND DRINKING FOUNTAIN CANNOT DISCHARGE INTO A
 HORIZONTAL WET VENT PER THE 2017 FBC SEC. P 912.1.
  
 M. SECOND REQUEST; IN THAT SAME DETAIL, THE WATER
 CLOSET IS ON A SANITARY TEE ON ITS BACK; A WATER CLOSET
 BEND IS REQUIRED PER THE 2017 FBC SEC. P 420.4.
  
 48. DONE.
  
 A. DONE.
  
 B. DONE.
  
 C. SECOND REQUEST; NOT ALL COMMENTS WERE ADDRESSED. ON
 DETAIL 6/P 9.0.2, THE ARMS FOR THE STACK BY THE
 TWO-FLOOR DRAINS HAVE THE ARMS IN AN S-TRAP. PLEASE
 SHOW IN A HORIZONTAL POSITION. THE FLOOR DRAIN NEXT TO
 AP-10 IS MISSING A TRAP PRIMER #. THE LAVATORY IN THE
 DOG SPA IS NOT SHOWN ON THE ISOMETRIC. PLEASE
 INCORPORATE IT IN THE SYSTEM OF THIS ISOMETRIC PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. DONE.
  
 E. DONE.
  
 F. DONE.
  
 G. DONE.
  
 49. SECOND REQUEST; SHEET P 9.0.3, IN DETAIL 1/P 9.0.3
 AND 2/P 9.0.3, IN THE JANITOR'S ROOM, THE MOP SINK IS
 LABELED AS FD-2, PLEASE CORRECT, PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 A. DONE.
  
 B. DONE.
  
 PLEASE ADD A NOTE THAT A SEPARATE PERMIT IS REQUIRED
 FOR THE GREASE INTERCEPTOR.
  
 C. SECOND REQUEST HERE IS NO NOTE ON TEMPERED WATER
 SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO
 (ASSE 1070 OR CSA B125.3) PER THE 2017 FBC SEC. 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
  
 D. DONE.
  
 E. DONE.
  
 50. DONE.
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 D. DONE.
  
 E. DONE.
  
 F. SECOND REQUEST; ON DETAIL 9/P 9.0.4, PLEASE SHOW
 SHUT-OFF VALVES TO THE MOP SINK, SIZE, AND LABEL THEM
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. DONE.
  
 51. SECOND REQUEST; SHEET P 9.0.5, THE DRAWING HAS
 MISSING DECK DRAINS AND EXTRA ROOF DRAINS, RISERS ARE
 CONNECTING TO DRAINS THAT ARE MISSING FITTINGS, TOO
 MANY TO CALL OUT PLEASE GO BACK AND REFER TO THE FLAT
 DRAWING AND MAKE CORRECTIONS FOR CLARITY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 52. SECOND REQUEST; SHEET P 9.0.6, PLEASE SIZE BOTH,
 PLEASE SHOW CLEAN CLEAN-OUTS ON VERTICALS, AND LABEL
 THE VENTS. THERE IS A 6" 121 GPM PIPE GOING WITH NO DD
 R? UP. WHERE IS THE NEW 3" CD COMING FROM AND PIPES
 GOING NOT SIZED, AND ARE THEY VENTS? PLEASE CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 53. SHEET P 9.0.7, THE DP-8 AND DP-9 SIZES ARE NOT
 LABELED, CD-1 AND CD-2 SIZES ARE NOT LABELED, AND THE
 THREE 1" CONDENSATE TIED TOGETHER IS GOING DOWN THAT IS
 MISSING WHERE IT'S GOING TO AND SIZE, CONDENSATE NUMBER
 DOES NOT CONNECT AT 90 GOING DOWN. PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 54. DONE.
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 55. SHEET P 9.0.9, PLEASE PROVIDE CLEAN-OUT ON THESE
 STORM RISERS PER 2017 FBC SEC. 1101.8 CLEANOUTS
 REQUIRED.
  
 56. SHEET P 9.0.12, NEW COMMENT THERE IS A 12" 45
 MISSINGS ON THE DRAIN AND DIRECTIONAL FITTING UPSTREAM
 OF THAT IS NOT DIRECTIONAL ALSO THE ONE ON BATHROOM
 GROUP IS WRONG, PLEASE CORRECT. S/R-9 IS NOT CONNECTED
 TO THE TRUNK LINE, AND THE TRAP FOR THE LAST FLOOR
 DRAIN WITH A VENT IS DRAWN WRONG. THE 4" FUTURE PIPE
 NUMBER S/R-9 DOES NOT HAVE A DIRECTIONAL FITTING. S/R-3
 PIPE SIZE IS WRONG, AND ALSO UPSTREAM LOOKS OVERSIZED.
 PLEASE FIX ALL SANTEE ON ITS SIDE AND USE WYE FITTINGS
 AND CORRECT ALL DIRECTIONAL FITTINGS. ALL DRAINS FROM
 ELEVATORS REQUIRE A TRAP AND A TRAP PRIMER, AND THE
 PUMP TWO ELEVATOR TRAP HAS NOWHERE TO CONNECT BY
 S/R-11. PIPES ARE FLOATING; PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 A. DONE.
  
 B. STILL NOT ADDRESSED. PLEASE SHOW THE STACK BY THE
 TWO-FLOOR DRAINS WITH THE ARMS IN AN S-TRAP. PLEASE
 SHOW IN A HORIZONTAL POSITION PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. DONE.
  
 D. THE THREE FD-1 NEXT TO STACK S/R-9 NOT DRAWN
 CORRECTLY, PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 57. DONE.
  
 A. DONE.
  
 B. DONE.
  
 C. DONE.
  
 58. DONE.
  
 A. NEW COMMENT; IN DETAIL ELEVEN, THE RIGHT BOTTOM
 CORNER 1/P 0.3.0 HAS A PIPE WITH TWO NINETY DOWN AND NO
 REFERENCE; PLEASE LABEL OR DELETE IF NOT NEEDED PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. DONE.
  
 C. NEW COMMENT; IN DETAIL EIGHT, THE LEFT TOP CORNER
 TWO PIPES ARE FLOATING AND NO REFERENCE POINT OR USE.
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 59. DONE.
  
 60. SHEET P 9.0.16, PLEASE SHOW AND LABEL ALL SHUT-OFF
 VALVES FOR HOSE BIBBS. FOUR RISERS ARE NOT LABELED WITH
 SIZE AND NO REFINANCE POINT NEXT TO THE WATER
 DISTRIBUTION ISOMETRIC VERBIAGE. PLEASE LABEL
 REFERENCES TO WHERE WATER LINES COME FROM AND GO PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 61. SHEET P 9.0.18, IT SEEMS THE PIPES WERE MOVED AND
 FITTING AND PIPES' CONNECTION IS FLOATING IN DRAWING;
 PLEASE CONNECT AND SIZE TO ITS PERSPECTIVE POINTS OF
 CONNECTIONS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 61B. NEW COMMENT ON P 9.0.19; DETAIL TWO HAS GRIDLINE
 NUMBERS OF THE DRAWING; PLEASE LOWER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 62. DONE.
  
 A. DONE.
  
 63. DONE.
  
 64.DONE.
  
 65. IT LOOKS LIKE THE PAGE UPLOADED HAS CHANGED AND
 DOES NOT REFLECT WHAT WAS REQUESTED; PLEASE CORRECT AND
 RESUBMIT. SHEET P 9.1.5, IN DETAIL THREE, 1/2" H & C
 LINES TO THE SHOWER, C WATER CLOSET, AND H & C TO THE
 LAV NOT SIZED OR LABELED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 66. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.6;
 NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 67. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.7;
 NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 68. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.9;
 NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR LABELED
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 A. DONE.
  
 69. SECOND REQUEST; SHEET P 9.1.9, 1/2" H & C TO THE
 WASHING MACHINE, FRIG, LAV, SHOWER, AND WATER CLOSET
 ARE NOT SIZED OR LABELED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 70. SHEET P 9.1.10, 1/2" HOT AND COLD WATER NOT SIZED
 TO THE FRIG AND THE TWO WATER CLOSET AND TUB PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 71. DONE, BUT ISLAND VENT IN QUESTION. SHEET P 9.1.11;
 NEEDS APPROVAL WITH CHIEF PLUMBING INSPECTOR LABELED
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 A. THE RESPONSE TO THIS WILL NOT WORK AS THE SHOWER MAY
 BE OVER 8' IN THE DISTANCE TO UP AND DOWN VENT; PLEASE
 CLARIFY; DETAIL ONE SHOWS WATER CLOSET AND SHOWER NOT
 VENTED; TRAPS REQUIRE A SYSTEM OF VENTING SO THAT A
 PRESSURE DIFFERENTIAL OF NOT MORE THAN 1" FOR EACH PER
 THE 2017 FBC SEC. 901.2.
  
 72. SECOND REQUEST; SHEET P 9.1.12, 1/2" H & C NOT
 LABELED OR SIZED TO BOTH LAVS AND WATER CLOSET PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 73. SECOND REQUEST; SHEET P 9.1.13, 1/2" H & C NOT
 LABELED OR SIZED TO LAVS, TUB, AND WATER CLOSET AND
 1/2" H & C NOT LABELED OR SIZED TO LAV AND WATER CLOSET
 THEN TO SHOWER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 SWIMMING POOL
  
 1. PROVISO FOR THE OPERATING PERMIT STAMPED BY THE
 FLORIDA DEPARTMENT OF HEALTH PER FL. STATUTES 514.03,
 553.79 (11).
  
 2. DONE.
  
 3. ATTACHMENT NOT FOUND OR UPLOADED; SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE POOL SHOWER. THE
 POOL SHOWER SHALL COMPLY WITH THE REQUIREMENTS OF ANSI
 A117.1 FOR COMPLIANCE WITH FAIR HOUSING REQUIREMENTS.
  
 4 DONE.
  
 5. DONE.
  
 6. DONE.
  
 7. DONE.
  
 8. DONE.
  
 9. SECOND REQUEST; SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE POOL HEATER. THE POOL HEATER SHALL HAVE A
 MINIMUM THERMAL EFFICIENCY OF 82% PER 2017 FBC-ENERGY
 TABLE C404.2.
  
 10. DONE.
  
 11. DONE.
  
 12. DONE.
  
 13. PLEASE PLACE A NOTE ON THE PLANS; SHEET. P2.3 -
 THERE IS A NOTE ON THE COLLECTOR TANK DETAIL THAT
 STATES" COLLECTOR TANK PIT DRAINAGE BY G.C." SUBMIT
 DETAILS ON THIS DRAINAGE AND ITS TERMINATION POINT OR
 PROVIDE THE PLAN SHEETS OF THIS PROJECT WHERE THIS
 INFORMATION CAN BE FOUND. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 14. DONE.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-13 Cont ID  
Sent By tklarge Date 2020-12-13 Time 06:26 Rev Time 0.00
Received By tklarge Date 2020-11-23 Time 08:52 Sent To  
Notes
2020-12-12 07:57:051) SHT. 5 OF 16 REFERS TO 45,800 CUBIC FOOT TANK
 STORAGE CHAMBERS. SUBMIT A DETAIL OF THIS STORAGE
 ARRANGEMENT, IT'S PURPOSE AND ANY/ ALL ASSOCIATED
 PIPING, PUMPS AND/OR ANY OTHER DETAILS ASSOCIATED WITH
 THIS SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHEETS ALS 0.1, ALS 0.2, ALS 0..3, ALS 0.4, ALS 0.5
 - THERE ARE REFERENCES IN THE NOTES ON THE FAIR HOUSING
 DETAILS AND ALSO IN THE DETAIL TITLES TO 6 DIFFERENT
 FAIR HOUSING DESIGN STANDARDS AND AT THIS POINT I HAVE
 NO IDEA AS TO WHAT DESIGN STANDARD YOU ARE USING AS A
 SAFE HARBOR FOR COMPLIANCE WITH THE FAIR HOUSING ACT.
 THERE IS ALSO A REFERENCE TO THE NORTH CAROLINA
 BUILDING CODE.THEREFORE, A THOROUGH AND COMPREHENSIVE
 REVIEW COULD NOT BE DONE FOR COMPLIANCE WITH FAIR
 HOUSING REQUIREMENTS. ONE DESIGN STANDARD ONLY MUST BE
 CHOSEN FOR COMPLIANCE WITH FAIR HOUSING REQUIREMENTS.
 REVISE ALL THE AFFECTED NOTES AND DETAIL TITLES ON THE
 FAIR HOUSING DETAIL SHEETS TO REFLECT THE CORRECT
 DESIGN STANDARD TO BE USED FOR COMPLIANCE. WPB AMEND.
 TO FBC SEC. 107..2.1.
 3) HUD RECOGNIZES TEN SAFE HARBORS FOR COMPLIANCE WITH
 THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION
 REQUIREMENTS. THE ICC/ANSI A117.1 - 2009 IS NOT LISTED
 AS A SAFE HARBOR. HUD SAID IN THE INTRODUCTION TO THE
 ACCESSIBILITY GUIDELINES, "BUILDERS AND DEVELOPERS MAY
 CHOOSE TO DEPART FROM THESE GUIDELINES AND SEEK
 ALTERNATE WAYS TO DEMONSTRATE THAT THEY HAVE MET THE
 REQUIREMENTS OF THE FAIR HOUSING ACT." THE STANDARD
 EMPLOYED MUST MEET ALL OF THE DESIGN AND CONSTRUCTION
 REQUIREMENTS SPECIFIED IN THE FAIR HOUSING ACT AND
 HUD'S FAIR HOUSING ACT REGULATIONS, AND PROVIDE THE
 SAME OR A STRICTER DEGREE OF ACCESSIBILITY THAN THE
 RECOGNIZED SAFE HARBORS. FAIR HOUSING ACT DESIGN
 MANUAL, PAGE 13. PREAMBLE TO THE GUIDELINES, 56 FR
 9478-79, MARCH 6, 1991. THE PURPOSE OF THE FAIR HOUSING
 ACT GUIDELINES IS "TO DESCRIBE THE MINIMUM STANDARDS OF
 COMPLIANCE WITH THE SPECIFIC ACCESSIBILITY REQUIREMENTS
 OF THE ACT." PREAMBLE TO THE GUIDELINES, 56 FR 9472,
 9476, MARCH 6, 1991. VERIFICATION MUST BE PROVIDED THAT
 THE 2009 EDITION OF THE ANSI A117.1 PROVIDES THE SAME
 OR A STRICTER DEGREE OF ACCESSIBILITY THE RECOGNIZED
 SAFE HARBORS.
 4) SHEET ALS 0.1 - ITEMS UNDER SEPARATE PERMIT -
 INCLUDE GREASE INTERCEPTOR, GAS, BACKFLOW DEVICES, AND
 IRRIGATION SYSTEMS.
 5) SHT.ALS 0.2 - FHA NOTES - COMMON USE FACILITIES -
 THE NOTE REFERS TO THE ANSI A117.1 - 1988 STANDARD. I
 AM NOT AWARE OF AN 1988 ANSI A117.1 STANDARD. CLARIFY
 AND REVISE THE NOTE TO REFLECT THE DESIGN STANDARD
 BEING USED FOR THIS PROJECT. WPB AMEND. TO FBC SEC.
 107.2.1.
 6) SHT. ALS 0.2 - DRINKING FOUNTAIN DETAILS - THE
 DETAIL TITLE REFERS TO THE ANSI 2009 EDITION BUT NOTE
 #1 REFERS TO THE FLORIDA BUILDING CODE. THE COMMON
 AREAS SHALL COMPLY WITH THE APPLICABLE STANDARD USED
 FOR FAIR HOUSING DESIGN COMPLIANCE. THE FLORIDA UILDING
 CODE DOES NOT APPLY TO THE COMMON AREAS OF THE
 BUILDING. THE FLORIDA BUILDING CODE WOULD APPLY TO ANY
 RETAIL OR TENANT SPACES THAT DO NOT FALL UNDER FAIR
 HOUSING REQUIREMENTS.THE SAME APPLIES TO THE URINAL
 DETAIL.REVISE THE NOTES.
 7) SHT. ALS 0.2 - ROLL- IN SHOWER DETAIL - THE DETAIL
 SHOWS A SEAT IN THE SHOWER. IF A SEAT IS INSTALLED, HOW
 WILL A PERSON ON THE SEAT BE ABLE TO REACH AND USE THE
 CONTROLS? CLARIFY.
 8) THE FAIR HOUSING DETAIL SHEETS HAVE NOTES REFERRING
 TO TYPE "A" AND TYPE "B" PLUMBING FIXTURES AND LAUNDRY
 EQUIPMENT. IF THE INTENT IS TO USE THE 2009 ICC/ANSI
 A117.1 STANDARD AS THE BASIS FOR FAIR HOUSING ACT
 COMPLIANCE, THEN SPECIFY THE TYPE OF UNIT ("A" UNIT OR
 "B" UNIT ) AND ALSO THE OPTION ( OPTION "A" OR "B" )
 BEING USED FROM CHAPTER 10 OF THE 2009 STANDARD.
 9) SHT. ALS 0.2 - WATER CLOSET COMPARTMENT-PUBLIC -
 NOTE #4 - DOOR PULLS SHALL BE LOCATED 34 INCHES MINIMUM
 AND 48 INCHES MAXIMUM ABOVE THE FLOOR. ANSI A117.1
 SEC.404.2.6, 604.9.3.
 10) SHT. ALS 0.3 - ACCESSIBLE WATER CLOSETS DETAIL -
 SECTION 1003.11.2.4.4 OF THE NOTED ANSI STANDARD
 REQUIRES THE CLEARANCE AT THE WATER CLOSET TO BE 66
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL WHEN A LAVATORY IS LOCATED NEXT TO THE WATER
 CLOSET FOR TYPE "A" ACCESSIBLE WATER CLOSETS. THE DEPTH
 OF THE LAVATORY SHALL BE A MAXIMUM OF 24 INCHES.
 11) FHA COMPLIANT WATER CLOSETS DETAILS - SHOW THE
 LENGTH OF ALL THE REINFORCEMENT FOR THE GRAB BARS.
 ALSO, SHOW THE HEIGHT OF THE REINFORCEMENT FROM THE
 FLOOR TO THE BOTTOM OF THE REINFORCEMENT.
 12) SHOW THE CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER
 CLOSETS ON ALL THE WATER CLOSET DETAILS ON THE FHA
 DRAWINGS. COMPLY WITH THE REQUIREMENTS FROM THE DESIGN
 STANDARD BEING USED.WPB AMEND. TO FBC SEC. 107.2.1.
 13) SHT. ALS 0.3 - ACCESSIBLE BATHTUBS W/O PERMANENT
 SEATS - NOTE #1 REFERS TO SEC.1003.11.2.5.1 OF THE ANSI
 STANDARD WHICH REFERS TO SEC. 607 WHICH REQUIRES THE 30
 INCH WIDE CLEAR FLOOR SPACE TO EXTEND THE LENGTH OF THE
 BATHTUB BUT THE DETAIL SHOWS THE LENGTH AS 48
 INCHES.THIS ALSO OCCURS ON SHT. ALS 0.5. CLARIFY.
 14) SHTS. A1.1.1A & A 9.50.1 - TOILET ROOM #104 - THE
 DOOR IS SWINGING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORY.COMPLY WITH ANSI A117.1 SEC. 603.2.2.
 15) SHTS. A1.2.1 & A 9.51.1 - TOILET ROOM #M02 - THE
 DOOR IS SWINGING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORY.COMPLY WITH ANSI A117.1 SEC. 603.2.2.
 16) 5TH FLOOR PLANS - AMENITY & POOL DECK - TOILET
 ROOMS #517 & #521 - TOILET COMPARTMENT DOORS SHALL NOT
 SWING INTO THE REQUIRED MINIMUM AREA OF THE
 COMPARTMENT. SHOW COMPLIANCE WITH ANSI A117.1
 SEC.604.9.3. SEE SHT. A9.52.1.
 17) SHT. A1.6.1 - CLEARLY SHOW THE ACESSIBLE ROUTE FROM
 THE SWIMMING POOL AREA TO THE TOILET FACILITIES. ANSI
 A117.1 SEC. 401.1
 18) THE ENTRY DOORS OF ALL RESTROOMS SHALL BE LOCATED
 WITHIN A 200 - FOOT WALKING DISTANCE OF THE NEAREST
 WATER'S EDGE OF EACH POOL SERVED BY THE FACILITIES.
 2017 FBC SEC.454.1.6.1.
 19) SHTS. A1.8.1, A9.54.1, & A9.54.3 - TOILET ROOMS
 #1601 & #1602 - THE DOOR IS SWINGING INTO THE CLEAR
 FLOOR SPACE FOR THE LAVATORY.COMPLY WITH ANSI A117.1
 SEC. 603.2.2.
 20) THE INTERIOR ELEVATION DRAWINGS FOR THE DWELLING
 UNITS- DETAIL #1 SHOWS THE HEIGHT OF THE KITCHEN SINK
 CABINET AS 36 INCHES IN HEIGHT YET THE FHA DETAIL
 SHEETS SHOW THE SINK HEIGHT AS 34 INCHES. CLARIFY.
 21) INDICATE ON THE FLOOR PLANS OF THE INDIVIDUAL
 DWELLING UNITS WHICH KITCHENS ARE TYPE "A" ACCESSIBLE
 KITCHENS AND WHICH ARE TYPE "B" ACCESSIBLE KITCHENS.
 WPB AMEND. TO FBC SEC.107.2.1.
 22) SHT. A9.8.1 - UNIT 8 - SHOW THE CLEAR FLOOR SPACE
 FOR ALL THE FIXTURES PER ANSI A117.1.
 23) SHT. A9.10.1 - UNIT 10 - DETAIL #2 - THE WATER
 CLOSET IS SHOWN AS 1 FOOT 11 INCHES (1'-11") FROM ITS
 CENTERLINE FROM THE EDGE OF THE LAVATORY AND THE
 WRAPPED EDGE OF THE COLUMN. THE WATER CLOSET SHALLL BE
 16-18 INCHES TO ITS CENTERLINE PER ANSI A117.1
 SEC.1003.11.2.4.
 24) THE MAXIMUM DEPTH OF THE LAVATORIES SHALL BE 24
 INCHES. THE PLANS SHOW SOME OF THE LAVATORIES AS 25 1/2
 INCHES DEEP. INDICATE ON THE UNIT FLOOR PLANS THAT THE
 MAXIMUM DEPTH OF THE LAVATORIES IS 24 INCHES PER ANSI
 A117.1.
 25) SHT. A9.16.1 - UNIT 16 - SHOWS THE WATER CLOSET IN
 THE MASTER BATH LOCATED 1 FOOT 10 INCHES (1'-10" ) FROM
 THE EDGE OF THE LAVATORY AND THE ADJACENT WALL TO THE
 CENTERLINE OF THE WATER CLOSET. THE WATER CLOSET SHALLL
 BE 16-18 INCHES TO ITS CENTERLINE PER ANSI A117.1
 SEC.1004.11..3.2.2
 26) SHT. A9.17.1 - UNIT 17 - SHOWS THE WATER CLOSET IN
 THE MASTER BATH LOCATED 2 FEET 5 INCHES ( 2'- 5" ) FROM
 THE ADJACENT WALL TO THE CENTERLINE OF THE WATER
 CLOSET. THE WATER CLOSET SHALLL BE 16-18 INCHES TO ITS
 CENTERLINE PER ANSI A117.1 SEC.1004.11.3.2.2.
 27) SHT. A9.20.1 - UNIT 20 - INDICATE ON THE PLAN THE
 UNIT TYPE BATHROOM AND OPTION TYPE ON THE PLAN PER ANSI
 A117.1. THE CENTERLINE OF THE WATER CLOSET FROM THE
 EDGE OF THE LAVATORY IS SHOWN AS 1 FOOT 9 INCHES (1'-
 9" ). CLARIFY.
 28) SHT. A9.52.3 - IDENTIFY THE WALL FINISH AROUND THE
 JANITOR SINK. COMPLY WITH FBC-BUILDING SEC.1210.2.2.
 29) SHT. A9.52.4 - SHOW THE INSIDE CLEAR DIMENSIONS (L
 X W) FOR THE TOILET STALLS IN THE WOMEN'S RESTROOM.
 COMPLY WITH FBC-PLUMBING SEC. 405.3.1.
 30) SHT. A9.54.1 - SHOW THE WIDTH DIMENSION BETWEEN THE
 SINK AND THE GRILL AND THE REQUIRED CLEAR FLOOR SPACES
 FOR EACH PER ANSI A117.1 SEC. 305.
 31) SHT. A9.54.1 - SHOW THE WIDTH OF TOILET ROOM #1602
 ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1, ANSI
 A117.1 SEC. 604.
 32) SHEET P 0.3.0, ON THE TYPICAL KITCHEN, A SANITARY
 RISER WITH AN AIR ADMITTANCE VALVE IS RESTRICTED ON THE
 HIGH RISE DUE TO THE HYDRAULIC JUMP CAUSED IN A STACK
 THAT WITHSTANDS LIMITED POSITIVE PRESSURES. BECAUSE
 EXTREME PRESSURES MAY DAMAGE THE DEVICES, THE AIR
 ADMITTANCE VALVES MAY BE USED IN THE BUILDING'S TOP 4
 STORIES. PLEASE REFER TO THE CODE SECTION, WHICH
 REQUIRES RELIEF VENTS PER THE 2017 FBC SEC. P 918.3.1.
 A) ON THE TYPICAL CONDENSATE LINE, THE FLOOR HAS A
 KEYNOTE SIX, WHICH REFERS TO AN AUTOMATIC AIR VENT
 TYPE. PLEASE GIVE DETAIL OF A STANDARD FOR THIS TYPE OF
 VALVE. THIS NOTED IT MIGHT NOT BE IN A CAVITY WALL AS
 THERE IS NO NEGATIVE OR POSITIVE PRESSURE. YOU MAY
 OFFSET IT IN AN A/C CLOSET, AND IT SHALL BE
 NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF
 NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 50 PER THE 2017 FBC SEC M 602.2.1.
 33) SHEET P 0.3.1, NOTE FIVE HAS THE LAST FEW WORDS ON
 TOP OF EACH OTHER. ON DETAIL ONE, PLEASE LABEL THE
 RE-VENT OF THE WASHING MACHINE. THE RE-VENT SIZE FROM
 SECOND TO THIRD LOOKS LIKE IT SHOULD BE 2" SO THE 3"
 SHOULD BE MOVED UP TO THE FOURTH FLOOR. DO THE SAME FOR
 THE 6TH FLOOR ON THE SECOND RISER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 34) SHEET P 0.3.2, RISER ONE THE MOP SINK HAS ONLY ONE
 SHUT OFF VALVE ON THE COLD, BUT IT REQUIRES A SHUT OFF
 AT EACH ENTRY FOR HOT AND COLD ALONG WITH THE PRV; A
 VALVE MAY BE NEEDED ON THE HOT SIDE OF THE HEATER FOR
 SERVICE, PLEASE SHOW AND LABEL PER THE 2017 FBC SEC. P
 606.1(2).
 35) SHEET P 1.0.1, THE GRID NUMBERS AND LETTERS ARE ON
 TOP OF EACH OTHER IN SOME PLACES, AND PLEASE OFFSET OR
 MOVE AWAY FOR CLARITY PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 THIS IS TYPICAL ON ALL PLUMBING PAGES, SO NOT TO REPEAT
 EVERY COMMENT; IT IS NOTED IN THIS ONE ONLY.
 A) THE FIRE ROOM HAS THREE-FLOOR DRAINS, THE TRASH ROOM
 HAS ONE, AND THE ELEVATOR HAS A FUNNEL DRAIN WITHOUT
 TRAP SEAL PROTECTION. PLEASE SHOW TRAP PRIMER AND GIVE
 DETAIL OR SPECIFICATION, ALSO WHERE THE SOURCE OF WATER
 IS COMING FROM IF APPLICABLE PER THE 2017 FBC SEC.
 1002.4.1. IF AN APPROVED TRAP SEAL IS USED THAT
 CONFORMS TO ASSE 1044 IN SOME AREAS, THE AHJ MAY NOT
 APPROVE THE DUE TO DEBRIS. PLEASE PROVIDE DETAILS OF
 THE SANITARY ISOMETRIC ON P 9.0.4 FOR THESE DRAINS,
 CLOUDS, OR BOXES AND GIVE REFERENCE NUMBERS; THESE
 TRAPS IN THESE AREAS ARE MISSING VENT PER THE 2017 FBC
 SEC. 1002.1.
 36) SHEET P 1.0.1B, PLEASE PROVIDE DETAIL OR SHOW HOW
 PIPES WILL BE PROTECTED FROM VEHICULAR TRAFFIC PER THE
 2017 FBC SEC. P 305.7. THIS IS TYPICAL ON ALL PLUMBING
 PAGES, SO NOT TO REPEAT EVERY COMMENT; IT IS NOTED IN
 THIS ONE ONLY.
 A) GRIDLINE LETTERS ARE NOT SHOWN. PLEASE MOVE THE
 DRAWING OVER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B) IN THE MAINTENANCE ROOM AND THE DOG SPA, THEY BOTH
 HAVE A FLOOR DRAIN, AND BEHIND THE TWO ELEVATORS, IT
 HAS A FUNNEL DRAIN WITHOUT TRAP SEAL PROTECTION. PLEASE
 SHOW THE TRAP PRIMER AND GIVE DETAIL AND OR
 SPECIFICATION, ALSO WHERE THE SOURCE OF WATER IS COMING
 FROM IF APPLICABLE PER THE 2017 FBC SEC. 1002.4.1. IF
 AN APPROVED TRAP SEAL IS USED THAT CONFORMS TO ASSE
 1044 IN SOME AREAS, THE AHJ MAY NOT APPROVE THE DUE TO
 DEBRIS. PLEASE PROVIDE DETAIL OF THE SANITARY ISOMETRIC
 ON P 9.0.4 FOR THESE DRAINS, CLOUDS, OR BOXES AND GIVE
 REFERENCE NUMBERS.
 C) THE STORAGE ROOM WITH THE LAUNDRY TRAY IS NOT
 LABELED NEXT TO THE ELEVATORS; PLEASE LABEL PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS
 D) THE TRAPS IN THESE AREAS ARE MISSING A VENT PER THE
 2017 FBC SEC. 1002.1.
 37) SHEET P 1.1.1A, THE BOOSTER PUMPS IN THE FIRE ROOM
 HAS NO BYPASS OR SHUT OFF VALVES FOR MAINTENANCE
 PURPOSES. PLEASE SHOW PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 A) TRASH ROOM HAS NO HOSE BIBB, AND IT IS STRONGLY
 SUGGESTED BUT NOT ENFORCED. THE TRASH SHOOT MAY HAVE A
 SANITIZER IN MOST CASES, BUT NO WATER IS SHOWN OR
 DETAILS FOR IT; IF APPLICABLE, PLEASE GIVE A POINT AND
 REFERENCE TO THE PAGE THAT WILL BE USED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 38) SHEET P 1.1.1B, THE MAINTENANCE ROOM, DOES NOT HAVE
 ANY DETAILS; PLEASE ADD A DETAIL P 9.0.2 SINCE THEY ARE
 NEXT TO EACH OTHER AND REFERENCE IT ON THIS PAGE. IT
 WILL NEED TO SHOW TRAP PRIMER, FLOOR DRAIN, AND VENT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 39) SHEET P 1.3.1A, THE MECHANICAL ROOM, AND BIKE ROOM
 ARE NOT LABELED; PLEASE LABEL PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 40) SHEET P 1.4.1A, THE MECHANICAL ROOM REQUIRES A TRAP
 PRIMER AND WATER ALONG WITH A VENT: IF USING A TRAP
 PRIMER THAT INVOLVES WATER, PLEASE SHOW THE SOURCE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 41) SHEET P 1.5.B, IN THE POOL AREA, THERE ARE MANY
 MISSING CIRCLES WHICH INDICATE THAT A PIPE IS GOING UP
 OR DOWN. PLEASE OVERLAY AND MATCH TO P 1.6.B; THERE ARE
 TOO MANY TO MENTION ON THIS PAGE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 42) SHEET P 1.6.1A, PLEASE REFER TO GRID LINES
 B-B.5/2-2.3; THE 4" DD IS A DECK DRAIN AS A ROOF DRAIN
 ON TOP; PLEASE REMOVE FOR CLARITY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) ON-GRID LINES 4.6-.5/A.1-B, THE PD IS NOT LABELED OR
 HAS SF SIZE FOR IT; PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 B) ON-GRID LINES 4-5/D-E THE BATHROOMS HAVE TOO MANY
 WATER LINES AND LABELS, MAKING IT HARD TO SEE OTHER
 DETAILS; PLEASE LIGHTEN THE OR REMOVE FOR CLARITY PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 43) SHEET P 1.6.1B, PLEASE GIVE DETAILS OR PROVIDE THE
 SPECIFICATION FOR THE GAS SOLENOID VALVE PANIC SHUT OFF
 AND PRESSURE REDUCING VALVES, LABEL THEM TO WHERE THEY
 ARE REFERENCED AT, IF A PAGE OF DETAIL IS AVAILABLE FOR
 THEM, PLEASE NOTE ON KEYNOTE LEGEND PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) PLEASE PROVIDE DETAILS FOR PLANT DRAINS AND PUT A
 REFERENCE ON KEYNOTE LEGEND PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 B) ON-GRID LINES 8-8.78 AND B-B.5, THERE IS A TRENCH
 DRAIN BUT LOOKS TO BE A PLANT DRAIN NEXT TO THE POOL,
 AND ON TOP, THERE IS ANOTHER PLANT DRAIN, AND IT HAS NO
 LABEL OR SIZE; PLEASE CLARIFY PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 C) ON-GRID LINES 8-8.78 AND D-D,8, THERE IS A 4" PLANT
 DRAIN LABELED -SF ON THE POOL DECK; DOES IT BELONG
 THERE, OR IS IT IN THE WRONG LOCATION? PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 D) ON-GRID LINES 7.2-8/D.8-F THERE IS A PLANT DRAIN
 SHOWN, BUT IT'S LABELED 4" DD (123). PLEASE CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 E) IN THE POOL EQUIPMENT ROOM, THERE IS A 4" FLOOR
 DRAIN THAT REQUIRES A VENT, PRIMER, SOURCE OF WATER,
 AND DETAIL WITH A REFERENCE NUMBER; ON THE FLOOR BELOW,
 IT SAYS 4" S UP ONLY. PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 44) SHEET P 1.7.1A, THE GRID LINES ON THE LEFT BOTTOM
 ARE OFF THE PLOTTED DRAWING AND OTHER OVERLAPPED (AS
 MENTION BEFORE, PLEASE CORRECT ALL OVERLAPS IN ALL
 PAGES); PLEASE MOVE OVER PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 45) SHEET P 1.8.1A, WHERE THE TWO RESTROOMS ARE, THE
 ROOM BEHIND THEM HAS NO LABEL; PLEASE LABEL ALL PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A)THERE IS NO LAYOUT SHOWING THE RD-1 AND HB-3; PLEASE
 PROVIDE A REFERENCE IF ON ANOTHER PAGE OR GENERATE ONE
 PLEASE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 46) SHEET P 1.8.1B, THERE IS AN AREA WHERE THE TRENCH
 DRAINS ARE, AND THEY ARE NOT LABELED. PLEASE LABEL PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 A) THERE IS NO LAYOUT SHOWING THE RD-1 AND TD-1; PLEASE
 PROVIDE ON PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 47) SHEET P 9.0.1, DETAIL 2 FOR THE FITNESS CENTER IT
 HAS A 6? PIPE COMING UP, NOT SIZED AND NOT LABELED OR
 WITH A REFERENCE POINT, ALSO SIZE THE HORIZONTAL 4?
 LINE GOING TO THE MEN'S ROOM, AND THE LADIES ROOM
 DOWNSTREAM HAS A FEW 3? AND 4? NOT SIZED AS WELL.
 PLEASE PROVIDE SIZES PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 A) ON THAT SAME DETAIL, THERE IS A 4" SANITARY LINE
 THAT HAS NO LABEL TO WHERE IT IS GOING. PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B) PLEASE SHOW ALL TRAP PRIMERS ON THE FLOOR DRAINS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 C) LAVATORIES ON ALL AP-3 NEED TO BE SHOWN HORIZONTALLY
 AS THEY SEEM TO BE IN AN S-TRAP POSITION. PLEASE CHANGE
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 D) THERE ARE THREE 3" SANITARY PIPES GOING UP WITH NO
 DESTINATION VENT AS WELL, PLEASE LABEL PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 E) THERE ARE TWO FLOATING FITTING AND A PIPE WITH A
 90-DEGREE ELBOW GOING DOWN AND A WYE AT THE END; IT
 DOESN?T HAVE A SIZE OR DESTINATION; PLEASE REMOVE AND
 OR GIVE A REFERENCE TO ITS USE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 F) ON DETAIL FOUR, PLEASE SHOW SHUTOFF VALVES FOR THE
 RECIRCULATING PUMP AT THE FITNESS ROOM AREA WITH AN
 ACCESS BOX ON BOTH SIDES OF THE RECIRCULATING PUMP FOR
 THE WATER HEATER, AND ALL FIXTURES PER THE 2017 FBC
 SEC. P 606.1.
 G) PLEASE SHOW AND LABEL THE HAMMER ARRESTOR FOR THE
 DRINKING FOUNTAIN AND ALL QUICK CLOSING VALVES PER THE
 2017 FBC SEC. P 604.9.
 H) PLEASE SHOW AND LABEL CHECK VALVES ON THE
 RECIRCULATING SYSTEM PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 I) THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES
 MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE
 REFER TO THE 2017 FBC ENERGY CODE TABLE C404.5.1.
 J) ON DETAIL SIX, PLEASE SHOW A BYPASS FOR THE BOOSTER
 PUMPS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 K) ON DETAIL ONE, AP-9 IS LABELED AS A FLOOR DRAIN;
 PLEASE MARK AS MOP SINK AND HAVE A NOTE THAT
 SURROUNDING THE WALL SHALL BE NON-ABSORBENT SURFACE IN
 ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2.
 L) IN THAT SAME DETAIL, THE MOP SINK, AND DRINKING
 FOUNTAIN CANNOT DISCHARGE INTO A HORIZONTAL WET VENT
 PER THE 2017 FBC SEC. P 912.1.
 M) IN THAT SAME DETAIL, THE WATER CLOSET IS ON A
 SANITARY TEE ON ITS BACK; A WATER CLOSET BEND IS
 REQUIRED PER THE 2017 FBC SEC. P 420.4.
 48) SHEET P 9.0.2, ON DETAIL 2/P 9.0.2, PLEASE SHOW
 LABELING ON THE SANITARY DOWN FROM WHERE IT'S COMING
 FROM AND WHERE IT IS GOING TO PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 A. ON DETAIL 4/P 9.0.2, PLEASE SHOW LABELING ON THE
 SANITARY DOWN FROM WHERE IT'S COMING FROM AND GOING TO
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B. ON DETAIL 5/P 9.0.2, IT SHOWS TWO DOG SPAS, ARE
 THESE STAND-ALONE UNITS AND IF SO, PLEASE PROVIDE
 MANUFACTURES SPECIFICATION TO SEE IF THEY REQUIRE A
 BACKFLOW DEVICE. THE DOG SPA SHOWS A LAV THAT IS NOT
 LABELED, AND IT IS MISSING WATER, VALVES, AND SANITARY
 DRAINAGE TO IT; PLEASE GIVE DETAIL. PLEASE SHOW THE
 FLOOR DRAIN IN THE DOG SPA PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 C. ON DETAIL 6/P 9.0.2, THE ARMS FOR THE STACK BY THE
 TWO-FLOOR DRAINS HAVE THE ARMS IN AN S-TRAP, PLEASE
 SHOW IN A HORIZONTAL POSITION. THE FLOOR DRAIN IS
 MISSING A TRAP PRIMER ALONG WITH A SOURCE OF WATER TO
 PRIME. THERE IS A SECOND-FLOOR DRAIN IN THE ROOM NEXT
 TO IT AND NOT SHOWN, AND IT MAY NEED TO BE VENTED IN
 THIS SYSTEM. THE LAVATORY IS NOT SHOWN ON THE
 ISOMETRIC, AND PLEASE INCORPORATE IT IN THE SYSTEM OF
 THIS ISOMETRIC. PLEASE SHOW WHERE AND SIZE OF THE MAIN
 TRUNK LINE IS COMING AND HEADS TO PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 D. ON DETAIL 7/P 9.0.2, THE TOILET ROOM SHALL HAVE
 TEMPERED WATER. IT SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2017 FBC
 SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 E. ON THAT SAME DETAIL, IT SHOWS A COFFEE STATION ON
 THE MEZZ NEXT TO THE TOILET ROOM; IS THIS A UNIT THAT
 REQUIRES WATER TO IT. IF SO, IT MUST BE EQUIPPED WITH
 AN INLINE VACUUM BREAKER THAT CONFORMS TO ASSE 1024 PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 F. ON DETAIL 8/P 9.0.2, PLEASE SHOW THE SHUT-OFF VALVE
 A LITTLE LARGER AND VALVES ON EACH FIXTURE; IF AN
 ACCESS BOX IS REQUIRED, PLEASE SHOW IT AS WELL PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 G. ON DETAILS 11 AND 12/P 9.0.2, PLEASE SHOW THE
 SHUT-OFF VALVES FOR THE WATER HEATER, DOG SPA, AND LAV.
 PLEASE SHOW A DRAIN PAN FOR THE WATER HEATER AND THE
 LOCATION WHERE IT WILL DISCHARGE PER THE 2017 FBC SEC.
 P 504.7.2.
 49) SHEET P 9.0.3, IN DETAIL 1/P 9.0.3 AND 2/P 9.0.3,
 IN THE JANITOR'S ROOM THE MOP SINK IS LABELED AS FD-2,
 PLEASE CORRECT, PLEASE SHOW HOT AND COLD WATER LINE TO
 THE MOP SINK AND SHUT OFF VALVES PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 A) ON DETAIL 4/P 9.0.3, IT DOES NOT SHOW WHERE 4"
 SANITARY DOWN IS COMING FROM, AND THERE IS NO VENT
 TYING TO THE OUTSIDE AS IT IS LOOPED TO ITSELF; PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B) ON DETAIL 5, 6, 7, AND 8/P 9.0.3, IT SHOWS A UNIT
 UNDER THE CABINET LABELED G-1, AND ON THE DESCRIPTION,
 IT IS CALLING A GRILLE; IS THIS A GREASE INTERCEPTOR.
 IF THIS IS A GREASE INTERCEPTOR, PLEASE PROVIDE THE
 FOLLOWING;
 PLEASE SHOW HOW YOU DETERMINE THE SIZE OF THE GREASE
 TRAP PRESUMING YOU ARE USING 14 LB. GREASE CAPACITY,
 (7) GALLONS PER MINUTE RATE FLOW; THIS UNIT SHALL BE
 SIZED IN ACCORDANCE WITH THE SIZING REQUIREMENTS PER
 THE 2017 FBC SEC P 1003.3.4 AND TABLE 1003.3.4.1. 10.
 PROVIDE CALCULATIONS USED IN THE SIZING OF A GREASE
 INTERCEPTOR, AND PLEASE PROVIDE MANUFACTURER
 SPECIFICATION PER THE WPB FBC 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
 C) ON DETAIL 11/P 9.0.3, THE TOILET ROOM SHALL HAVE
 TEMPERED WATER. IT SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2017 FBC
 SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 D) ON DETAIL 12/P 9.0.3, PLEASE PROVIDE A SHUT-OFF
 VALVE FOR EACH FIXTURE AND THE TOILET ROOM AND DRINKING
 FOUNTAIN AREA. PLEASE PROVIDE A HAMMER ARRESTOR FOR THE
 ELECTRIC WATER COOLER PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 E) ON DETAIL 1/P 9.0.3, FOR THE MOP SINK, THE
 SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE IN
 ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2 AND
 2017 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS
 SHEET.
 50) SHEET P 9.0.4, ON DETAIL P 9.0.4 IS LABELED AS AN
 FD-2, AND IT SHOULD BE A MOP SINK; PLEASE LABEL
 ACCORDINGLY FOR CLARITY IN THE FIELD PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) ON DETAIL 2/P 9.0.4, PLEASE SHOW REFERENCE, WHERE
 THE 4" SANITARY IS COMING FROM AND, WHERE THE VENT IS
 CONNECTING TO, ALSO SHOW WHERE THE 3? SANITARY IS GOING
 TO. PLEASE SIZE THAT SAME RISER GOING UP PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 B) ON DETAIL 3/P 9.0.4, FOR THE MOP SINK, THE
 SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE IN
 ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2 AND
 2017 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS
 SHEET.
 C) ON DETAIL 5/P 9.0.4, IT SHOWS A COFFEE STATION ON
 THE GROUND FLOOR; IS THIS A UNIT THAT REQUIRES WATER TO
 IT. IF SO, IT MUST BE EQUIPPED WITH AN INLINE VACUUM
 BREAKER THAT CONFORMS TO ASSE 1024 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 D) ON DETAIL 6/P 9.0.4, PLEASE SHOW A TEMPERING DEVICE
 FOR THE ACCESSIBLE LAV THAT COMPLIES WITH ASSE 1070 OR
 GIVES DETAIL ON ANOTHER PAGE AND REFERENCES THAT DETAIL
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 E) ON DETAIL 7/P 9.0.4, PLEASE PROVIDE A SHUT-OFF VALVE
 FOR EACH FIXTURE AND THE MANAGER'S AREA. PLEASE PROVIDE
 A HAMMER ARRESTOR FOR THE ELECTRIC WATER COOLER PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 F.)ON DETAIL 9/P 9.0.4, PLEASE PROVIDE SHUT-OFF VALVES
 TO THE MOP SINK, SIZE, AND LABEL THEM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 G) ON THE SAME DETAIL ABOVE, IT HAS A DOG SPA; IS THIS
 A MANUFACTURED UNIT? WHICH MAY REQUIRE A VACUUM BREAKER
 OR BACKFLOW DEVICE. PLEASE CLARIFY AND ADD MORE
 INFORMATION PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 51) SHEET P 9.0.5, THE DRAWING HAS MISSING DECK DRAINS,
 AND EXTRA ROOF DRAINS, RISERS ARE CONNECTING TO DRAINS
 THAT ARE MISSING FITTINGS, TOO MANY TO CALL OUT PLEASE
 GO BACK AND REFER TO THE FLAT DRAWING AND MAKE
 CORRECTIONS FOR CLARITY PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 52) SHEET P 9.0.6, PLEASE SIZE BOTH, CLEAN-OUTS AND
 LABEL THE ONE OUTSIDE AND DELETE TWO FLOATING FITTINGS
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 53) SHEET P 9.0.7, THE DP-8 AND DP-9 SIZES ARE NOT
 LABELED, CD-1 AND CD-2 SIZES ARE NOT LABELED, AND THE
 THREE 1? CONDENSATE TIED TOGETHER IS GOING DOWN THAT IS
 MISSING WHERE IT?S GOING TO AND SIZE. PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 54) SHEET P 9.0.8, CONDENSATE NUMBER 16, HAS NO LABEL
 AS TO WHERE IT IS GOING; PLEASE PROVIDE INFORMATION
 LIKE OTHER STACKS PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 A) PLEASE LABEL ALL CLEAN-OUTS, IT SHOWS CLEAN-OUTS AT
 ALL BASE OF STACKS IN THE DETAILS ON 2/P 0.3.0, BUT
 NONE IS SHOWN ON THIS PAGE; PLEASE ADD TO COINCIDE WITH
 BOTH DRAWINGS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B) THERE ARE THREE FITTING FLOATINGS IN THIS DRAWING (
 TWO DRAINS AND ONE COMBO); PLEASE REMOVE THEM TO
 PREVENT CONFUSION PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 C) PAN DRAINS ARE TERMINATING IS IN THE PARKING DECK,
 AND THEY MUST GO TO THE EXTERIOR OF THE BUILDING TO
 COMPLY WITH THE 2017 FBC SEC. P 507.7.2.
 55) SHEET P 9.0.9, PLEASE REFER TO P 1.6.1 FOR OVERLAYS
 AND CORRECTIONS OF ALL THE ROOF, TRENCH, AND PLANT
 DRAINS TO COINCIDE WITH EACH OTHER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 56) SHEET P 9.0.12, PLEASE LABEL CHECK VALVES AND
 SHUTOFF VALVES FOR BOTH ELEVATOR PUMPS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) PLEASE SHOW TRAP PRIMERS, SOURCE OF WATER, AND VENT
 ALL FLOOR DRAINS PROPERLY, TYPES 1 AND 2 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 B) THE STACK BY THE TWO-FLOOR DRAINS THAT HAVE THE ARMS
 IN AN S-TRAP, PLEASE SHOW IN A HORIZONTAL POSITION PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 C) ALL THE PIPES GOING UP, SANITARY AND VENTS, PLEASE
 GIVE A REFERENCE POINT OF CONNECTION AND PLEASE LABEL
 AND SIZE THE CLEAN-OUT UPSTREAM OF THE 8" BY 6" WYE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 D) THE THREE FD-1 NEXT TO STACK S/R-9 ARE NOT LABELED;
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 57) SHEET P 9.0.13, IN DETAIL THREE, LEFT-RIGHT CORNER,
 1/P 0.3.0 (22 DFU) SHOULD BE 4", AND THE P 0.3.1 (66
 DFU) THEY ARE CROSSED, PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) IN DETAIL FIVE IN THE LOWER-LEFT CORNER, AS NOTED ON
 COMMENT 17 LETTER B, I, M, AND N. PLEASE FIX TO MATCH P
 9.0.1 ON THE ISOMETRIC, PLEASE SIZE RIGHT SIDE ON
 DOUBLE 6? WYE AND UPSTREAM OF THAT IS 4/P 0.3.0 (4 DFU)
 THAT IS MISSING A PIPE SIZE AND ALL OTHER BRANCHES IN
 BOTH BATHROOM GROUPS ARE MISSING SIZES, PLEASE SIZE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 B) IN DETAIL SIX, THE MIDDLE BOTTOM TWO 1/P 0.3.0 (60
 DFU) AND 4/ P 0..3.0 (20 DFU) ARE MISSING SIZES. THERE
 IS A 2" SANITARY THAT IS NOT LABELED TO WHERE IT IS
 GOING. PLEASE LABEL PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 C) IN DETAIL SEVEN, THE RIGHT BOTTOM CORNER, 2/P 0.3.0
 IS REFERENCED AS A SANITARY BUT IS A DETAIL FOR
 CONDENSATE; PLEASE CORRECT PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 58) SHEET P 9.0.14, IN DETAIL TEN IN THE LEFT CORNER,
 THE 4" S (84) DFU HAS NO LABEL FOR A RISER. PLEASE
 LABEL PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 A) IN DETAIL ELEVEN, THE RIGHT BOTTOM CORNER 1/P 0.3.0
 (84 DFU) HAS NO SIZE ON THE HORIZONTAL PIPE. PLEASE
 SIZE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 B) IN DETAIL NINE, THE TOP RIGHT CORNER 4/P 0.3.0 (28
 DFU) IS SIZED AS 4" BUT NEEDS TO BE 3" ALSO, IN THE
 SAME RUN DOWNSTREAM SIZE, THE 6" SANITARY IS MISSING;
 DOWNSTREAM FROM THE WYE, THERE IS 1/P 0.3.0 (84) THAT
 IS MISSING A SIZE. ON THE OTHER SIDE OF THAT BRANCH,
 TWO 1/P 0.3.0 (84 DFU) ARE MISSING THEIR SIZES, AND
 UPSTREAM OF THAT, 1/P0.3.1 IS MISSING A SIZE AS WELL.
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 C) IN DETAIL EIGHT, THE LEFT TOP CORNER OF THE LAST
 RISER IS MISSING THE SIZE AND DFU, AND THE 1/P 0.3.0 IS
 NOT POINTING TO IT. PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 59) SHEET P 9.0.15, PLEASE SHOW BYPASS AND SHUTOFF
 VALVES ON BOOSTER PUMPS, PLEASE LABEL ALL SHUT OFF
 VALVED AND ACCESS PANELS, 6? WATER MAIN, PLEASE LABEL
 WHERE IT'S COMING FROM, PLEASE LABEL ALL WATER GOING UP
 TO WHERE IT CONTINUES PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 60) SHEET P 9.0.16, PLEASE LABEL ALL SHUT OFF VALVED
 AND ACCESS PANELS; PLEASE SHOW A SHUTOFF VALVE FOR ALL
 HB-3 ON THE ROOF; AP-5 HAS NO REFERENCE POINT TO WHAT
 IT SERVES. PLEASE LABEL REFERENCES TO WHERE WATER LINES
 COME FROM AND GO PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 61) SHEET P 9.0.18, IN THE FIRST AREA DRAIN NEXT TO THE
 TRENCH DRAIN, AN AD-1 IS NOT LABELED OR SIZED PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 62) SHEET P 9.1.2, IN DETAIL TWO, 3/4" H & C LINES FROM
 WATER HEATER NOT SIZED OR LABELED AND 1/2" H & C TO THE
 TUB'S LINES ARE NOT LABELED, PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) IN DETAIL TWO, THE DISTANCE FROM THE STACK TO THE
 SHOWER SHALL NOT EXCEED 8 FEET PER THE 2017 FBC SEC.
 TABLE P 909.1
 63) SHEET P 9.1.3, IN DETAIL TWO, 3/4" H & C LINES FROM
 WATER HEATER NOT SIZED OR LABELED, 1/2" H & C TO THE
 LINES TO THE TUB, WATER CLOSET, LAVE AND SHOWER NOT
 SIZED AND LABELED THE PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 64) SHEET P 9.1.4, IN DETAIL ONE, H & C WATER LINES
 COMING OUT OF THE HEATER NOT SIZED OR LABELED / ALSO IN
 DETAIL THREE, 1/2" H & C LINES TO THE WASHING MACHINE
 AND THE KITCHEN NOT SIZED OR LABELED PER THE PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 65) SHEET P 9.1.5, IN DETAIL THREE, 1/2" H & C LINES TO
 THE SHOWER, C WATER CLOSET, AND H & C TO THE LAV NOT
 SIZED OR LABELED PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 66) SHEET P 9.1.6, IN DETAIL TWO, 3/4" HOT ON WATER
 HEATER NOT SIZED OR LABELED, IN DETAIL FOUR, 1/2" H & C
 TO THE LINES TO THE KITCHEN AND FRIG NOT SIZED OR
 LABELED PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 67) SHEET P 9.1.7, IN DETAIL ONE, 3/4" H & C LINES FROM
 WATER HEATER NOT SIZED OR LABELED, IN DETAIL TWO 1/2" H
 & C TO THE LAV NOT SIZED OR LABELED PER THE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 68) SHEET P 9.1.8, 1/2" H & C TO THE TUB LINES ON TUB
 AND WATER CLOSET NOT SIZED OR LABELED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) THE LAVATORY ARM SHOWS A HORIZONTAL SANITARY TEE ON
 A DOUBLE LAVATORY WHICH IS NOT PERMITTED PER THE 2017
 FBC TABLE P 706.3.
 69) SHEET P 9.1.9, 1/2" H & C TO THE WASHING MACHINE,
 FRIG, LAV, AND WATER CLOSET ARE NOT SIZED OR LABELED
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 70) SHEET P 9.1.10, 3/4" HOT COMING OUT THE WATER
 HEATER NOT LABELED OR SIZED, 1/2" H & C LINES NOT
 LABELED OR SIZE ON THE WATER TO THE FRIG AND THE TWO
 WATER CLOSET AND TUB PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 71) SHEET P 9.1.11, 1/2" H & C LAV NOT SIZED OR LABELED
 AND H & C TO THE KITCHEN NOT SIZED OR LABELED PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 A) DETAIL ONE SHOWS WATER CLOSET AND SHOWER NOT VENTED;
 TRAPS REQUIRE A SYSTEM OF VENTING SO THAT A PRESSURE
 DIFFERENTIAL OF NOT MORE THAN 1? FOR EACH PER THE 2017
 FBC SEC. 901.2.
 72) SHEET P 9.1.12, 1/2" H & C NOT LABELED OR SIZED TO
 BOTH LAVS AND WATER CLOSET PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 73) SHEET P 9.1.13, 1/2" H & C NOT LABELED OR SIZED TO
 LAVS, TUB, AND WATER CLOSET AND 1/2" H & C NOT LABELED
 OR SIZED TO LAV AND WATER CLOSET THEN TO SHOWER PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 SWIMMING POOL
 1) SUBMIT A COPY OF THE APPLICATION FOR THE OPERATING
 PERMIT STAMPED BY THE FLORIDA DEPARTMENT OF HEALTH PER
 FL. STATUTES 514.03, 553.79 (11).
 2) SHT. P1.1 -THE PLAN SHOWS THE DISTANCE TO THE
 SANITARY FACILITIES AS 184 FEET THAT TRAVERSES A SET OF
 STAIRS. WHAT IS THE DISTANCE OF THE ACCESSIBLE ROUTE
 FROM THE NEAREST WATER'S EDGE TO THE ENTRY DOORS OF THE
 RESTROOMS? THIS MUST BE TTAKEN INTO CONSIDERATION.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 SHOWER. THE POOL SHOWER SHALL COMPLY WITH THE
 REQUIREMENTS OF ANSI A117.1 FOR COMPLIANCE WITH FAIR
 HOUSING REQUIREMENTS.
 4) SHT. P2.0 - THERE IS A NOTE UNDER THE FRICTION LOSS
 TABLE THAT REFERS TO THE BENDING OF PVC PIPING WITH
 HEAT. APPROVAL OF THIS PROCESS WILL BE BASED ON
 DOCUMENTATION FROM THE MANUFACTURER THAT SPECIFICALLY
 ALLOWS THIS PRROCESS.
 5) FBC-BUILDING SEC.454.1.1.1 STATES THE FILTRATION
 SYSTEM SHALL BE CAPABLE OF PROVIDING A FLOW RATE OF AT
 LEAST .75 GPMM FOR EACH LIVING UNIT AT NONTRANSIENT
 FACILITIES WHICH WOULD BE 174.75 GPM BUT THE DESIGN
 FLOW RATE OR THIS POOL IS 170 GPM. CLARIFY.
 6) FBC-BUILDING SEC. 454.1.6.1.2 - DOORS TO THE
 RESTROOMS SHALL BE WITHIN 50 FEET OF THE BUILDING'S
 EXTERIOR DOOR. INDICATE THIS ON THE SHT. P1.1.
 7) SHOW THE SPACING OF THE WALL INLETS ON SHT. P2.0.
 COMPLY WITH FBC-BULDING SEC. 454.1.6.5.9.1.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAINS. THE MAIN DRAIN COVERS SHALL COMPLY WITH
 ANSI/APSP/ICC 7 - 2013 SEC.4.3.1.1.
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 HEATER. THE POOL HEATER SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82% PER 2017 FBC-ENERGY TABLE C404.2.
 10) OUTDOOR HEATED SWIMMING POOLS SHALL BE EQUIPPED
 WITH A VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE
 OR A LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT
 LOSS. SHOW HOW THIS WILL BE ACHIEVEDFBC-ENERGY SEC.
 C404.9.3.
 11) SHOW THE TEMINATION OF THE POOL WASTE LINE ON THE
 PLANS. THE WASTE LLINE SHALL NOT DISCHARGE TO THE STORM
 OR SANITARY SYSTEM PER CITY OF WEST PALM BEACH CODE OF
 ORDINANCES ARTICLE III, SEC. 90-126 (B) (5) (SANITARY
 SEWERS), AND ARTICLE IV, SEC. 90-203 (A). CONTACT MANNY
 GONZALEZ IN THE CITY OF WEST PALM BEACH ENGINEERING
 DEPARTMENT AT 561-494-1040 FOR FURTHER INFORMATION.
 12) SHT. P2.3 SHOWS A FLOOR DRAIN IN THE POOL EQUIPMENT
 ROOM DISCHARGING TO THE STORM SEWER. THIS FLOOR DRAIN
 SHALL DISCHARGE TO THE SANITARY SEWER AND WILL REQUIRE
 A NEUTRALIZATION TANK DUE TO THE CHEMICALS LLOCATED IN
 THIS ROOM PER FBC-PLUMBING SEC. 803.1,,
 13) SHT. P2.3 - THERE IS A NOTE ON THE COLLECTOR TANK
 DETAIL THAT STATES" COLLLECTOR TANK PIT DRAINAGE BY
 G.C." SUBMIT DETAILS ON THIS DRAINAGE AND IT'S
 TERMINATION POINT OR PROVIDE THE PLAN SHEETS OF THIS
 PROJECT WHHERE THIS INORMATION CAN BE FOUND. WPB AMEND.
 TO FBC SEC. 107.2.1.
 14) SHT. P2.4 - POOL EQUIPMENT PLUMBING DIAGRAM - THERE
 IS AN ITEM LOCATED NEXT TO ITEM PH ON THE DIAGRAM THAT
 IS LABELED AS "PI". PI IS FOR THE COLLECTOR TANK.
 CORRECTLY IDENTIFY THIS ITEM. WPB AMENND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2021-02-23 Cont ID  
Sent By rmcdouga Date 2021-02-23 Time 07:26 Rev Time 0.00
Received By rmcdouga Date 2021-02-23 Time 07:26 Sent To  
Notes
2021-02-23 07:27:48ROOFING SUBMITTALS FOR TPO ROOF TO BE DEFERRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-11-18 Cont ID  
Sent By rmcdouga Date 2020-11-18 Time 12:38 Rev Time 0.00
Received By rmcdouga Date 2020-11-18 Time 12:38 Sent To  
Notes
2020-11-18 12:40:50NO PRODUCT APPROVALS WERE SUBMITTED FOR THE ROOF
 COVERING MATERIALS.
 PLANS SHOW TPO OVER LIGHT WEIGHT CONCRETE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-05-12 Cont ID  
Sent By rmcdouga Date 2021-05-12 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2021-05-12 Time 15:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-21 Cont ID  
Sent By jleahy Date 2021-04-21 Time 16:50 Rev Time 0.00
Received By jleahy Date 2021-04-21 Time 16:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-16 Cont ID  
Sent By medwards Date 2021-02-16 Time 15:16 Rev Time 0.00
Received By medwards Date 2021-02-16 Time 15:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-15 Cont ID  
Sent By medwards Date 2020-12-03 Time 15:40 Rev Time  
Received By medwards Date   Time   Sent To  
Notes
2020-12-03 15:41:38THE CITY OF WEST PALM BEACH DOES ALLOW 1 TIME FOR THE
 ENGINEER TO SELF CERTIFY. SEE BELOW
 SHEETS 004-019 ENGINEER CANNOT SELF CERTIFY.
 61G15?23.004 F.A.C.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS: (A) UNIQUE TO THE PERSON USING IT; (B) CAPABLE OF
 VERIFICATION; AS OF NOVEMBER 16, 2020 63 (C) UNDER THE
 SOLE CONTROL OF THE PERSON USING IT; AND, (D) LINKED TO
 A DOCUMENT IN SUCH A MANNER THAT THE DIGITAL SIGNATURE
 AND CORRESPONDINGLY THE DOCUMENT IS INVALIDATED IF ANY
 DATA IN THE DOCUMENT IS CHANGED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 5 Status P Date 2021-05-18 Cont ID  
Sent By rmcdouga Date 2021-05-18 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2021-05-18 Time 09:50 Sent To  
Notes
2021-05-18 10:20:38THE PAPER VERSION OF THE THRESHOLD FORMS WERE SUBMITTED
 AND THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND
 SEAL WERE VERIFIED BY SAMANTHA HILL ON 5/18/2021.
  
 THRESHOLD INSPECTIONS:
 INTERTEK-PSI
 JAMES R. HILL III, PE, SI 81087
 TULIO PIERO CASARETO, BN 8034

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status F Date 2021-05-12 Cont ID  
Sent By rmcdouga Date 2021-05-12 Time 15:53 Rev Time 0.00
Received By rmcdouga Date 2021-05-12 Time 15:53 Sent To  
Notes
2021-05-12 15:53:05THERE ARE ISSUES WITH THE THRESHOLD INSPECTION
 DOCUMENTS IN YOUR EMAIL ATTACHMENT.
 THERE IS NO FORM WITH A NOTARIZED SIGNATURE FOR THE 468
 LICENSED INSPECTOR, TULIO CASARETO.
 THE REGISTRATION NUMBER FOR THE CONTRACTOR IS NOT
 FILLED IN.
 THE OWNER?S SIGNATURE IS NOT NOTARIZED.
 IF THERE WILL BE MORE THAN THE ONE 468 LICENSED
 INDIVIDUAL PERFORMING THE THRESHOLD INSPECTIONS, THERE
 INFORMATION NEEDS TO BE PROVIDED.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2021-04-21 Cont ID  
Sent By rmcdouga Date 2021-04-21 Time 14:20 Rev Time 0.00
Received By rmcdouga Date 2021-04-21 Time 14:20 Sent To  
Notes
2021-04-21 14:21:58THE DOCUMENTS THAT WERE SUBMITTED ARE INCOMPLETE. SEE
 BUILDING REVIEW COMMENT #1.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2021-02-23 Cont ID  
Sent By rmcdouga Date 2021-02-23 Time 07:28 Rev Time 0.00
Received By rmcdouga Date 2021-02-23 Time 07:28 Sent To  
Notes
2021-02-23 07:30:09THE DOCUMENTS THAT WERE SUBMITTED ARE INCOMPLETE. SEE
 BUILDING REVIEW COMMENT #1.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2020-12-02 Cont ID  
Sent By rmcdouga Date 2020-12-02 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2020-12-02 Time 10:45 Sent To  
Notes
2020-12-02 10:46:20THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE OCTOBER 2018
 GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-04-20 Cont ID  
Sent By aaponte Date 2021-04-20 Time 11:18 Rev Time 0.00
Received By aaponte Date 2021-04-20 Time 11:18 Sent To  
Notes
2021-04-20 11:28:23PROVISO:
 1. A SEPARATE ELECTRIC PERMIT SHALL BE SUBMITTED FOR
 THE DECORATIVE STREET LIGHTS TO BE LOCATED ALONG THE
 STREET. THIS PERMIT DOES NOT INCLUDE STREETLIGHTS.
 2. A SEPARATE DIRECTIONAL SIGN PERMIT SHALL BE
 SUBMITTED FOR THE APPROVAL OF THE PEDESTRIAN WARNING
 SIGN AT THE EXIT OF THE DIXIE HIGHWAY GARAGE.

Review Stop Z ZONING
Rev No 2 Status F Date 2021-02-26 Cont ID  
Sent By aaponte Date 2021-02-26 Time 18:19 Rev Time 0.00
Received By aaponte Date 2021-01-26 Time 18:19 Sent To  
Notes
2021-02-26 14:05:021. NOT SATISFIED. THE PERMIT SET NEEDS TO INCLUDE THE
 PROJECT DATA INFORMATION AS ORIGINALLY PRESENTED FOR
 SITE PLAN OR SIMILAR. PREVIOUS COMMENT:PLEASE INCLUDE
 THE SITE DATA INFORMATION AS INCLUDED IN THE APPROVED
 SITE PLAN SET SHEET SP-1.
 2.PARTIALLY SATISFIED. PLEASE INCLUDE IN THE SITE PLAN
 THE SAME NOTE INCLUDED IN THE APPROVED SITE PLAN THAT
 STATES THAT "8 EXSTING ANGLES PARKING SPACES TO REMAIN.
 NOT INCLUDED IN OVERALL SITE PARKING PROVIDED. PREVIOUS
 COMMENT:SP1.01 PARKING COUNT SHALL REFLECT THE NUMBER
 OF SURFACE PARKING SPACES EXISTING ALONG THE NORTH
 PROPERTY LINE.
 3. SATISFIED-FIRST PARKING SPACE ON THE RIGHT SIDE FROM
 THE GROUND FLOOR UP THE RAMP CAN BE DIMENSIONED AS
 8?-6? AS IT IS NOT A COMPACT SPACE.
 4. NOT SATISFIED.PROJECT IS REQUIRED TO PROVIDE 12
 GUEST PARKING SPACES AND 7 RETAIL SPACES. SHEED SP1.1.1
 INDICATES ONLY 14 SPACES LISTED FOR RETAIL AND LEASING,
 BUT DOES NOT INDICATE SPACES FOR GUEST. PLEASE ADJUST
 TO DEMONSTRATE COMPLIANCE. PREVIOUS COMMENT:PLEASE
 INDICATE THE LOCATION OF GUEST AND RETAIL PARKING AND
 SHOW THE MARKINGS PROPOSED.
 5. SATISFIED.PLEASE MARK THE TURN AROUND SPACE AS NO
 PARKING.
 6. SATISFIED.PLEASE ADJUST THE PARKING TABLE IN SHEET
 SP1.01 TO REFLECT THAT THE GARAGE HAS ONLY 323 PARKING
 SPACES AND NOT 324 PARKING SPACES.
 7. SATISFIED.PLEASE CONFIRM THE SIDEWALKS WILL MEET THE
 MAXIMUM 2% CROSS SLOPE AND MEET THE CURB ELEVATION.
 8. SATISFIED.PLEASE CONFIRM THE PROPOSED DCDA EQUIPMENT
 AT THE EAST SIDE OF THE PUBLIC OPEN SPACE CAN BE
 SCREENED WITH LANDSCAPE AND MEET UTILITY REQUIREMENTS.
 9. SATISFIED. AN AERIAL ENCROACHMENT WILL BE NEEDED FOR
 ANY PORTION OF THE CANOPIES OVER THE ROW.PREVIOUS
 COMMENT:PLEASE CALL OUT THE CANOPY/EYEBROW THAT GOES
 OVER THE PEDESTRIAN ENTRANCE AND GARAGE, AND GENERALLY
 ABOVE THE FIRST FLOOR LINE.
 10. ACKNOWLEDGED.SIGN REQUIRED A SEPARATE PERMIT AND IT
 IS NOT INCLUDED IN THIS PERMIT.
 11. SATISFIED.PLEASE PROVIDE INFORMATION TO CONFIRM
 THAT ALL MECHANICAL EQUIPMENT IS SCREENED WITH A LOUVER
 OR PARAPET WALL AS TALL AS THE EQUIPMENT.
 12. SATISFIED.TREATMENT OF GARAGE EAST FA?ADE IS
 MISSING SOME ADDITIONAL PAINT VARIATIONS PROPOSED UNDER
 THE WINDOWS.
 13. PARTIALLY SATISFIED. PLEASE CONFIRM THE SLIPFITTER
 FOR THE PROPOSED STREETLIGHT FIXTURE IS THE SFX
 APPROVED FOR DOWNTOWN, AND THE POLE IS 13 IN HEIGHT.
 PREVIOUS COMMENT:PLEASE PROVIDE PHOTOMETRICS FOR THE
 STREETSCAPE AND INCLUDE A DETAIL OF THE DECORATIVE
 STREETLIGHT TO BE INSTALLED WITHIN IN THE PUBLIC REALM
 TO CONFIRM COMPLIANCE WITH CITY STANDARDS.
 14. SATISFIED.PLEASE PROVIDE THE BIKE RACK DETAIL WITH
 PLACEMENT DIMENSIONS.
 15. SATISFIED.IS ANY OF THE GARAGE LIGHTING VISIBLE
 FROM THE PUBLIC SIDEWALK AND STREET? OR IS THE GARAGE
 FULLY ENCLOSED?
 16. SATISFIED.PLEASE INCLUDE A NOTE IN THE CIVIL
 DRAWING SPECIFYING THAT THE SIDEWALK ELEVATION SHALL BE
 MAINTAINED ACROSS THE ALL DRIVEWAY ENTRANCES.
 17. ACKNOWLEDGED.PLEASE IDENTIFY THE LOCATION OF THE
 ART IN PUBLIC PLACES COMPONENT.
 18.NOT SATISFIED.SPECIFICATION SHEET LISTED IN RESPONSE
 LETTER NOT FOUND. PLEASE INCLUDE DETAILS TO CONFIRM
 COMPLIANCE WITH DAC REQUIREMENT FOR THE INSTALLATION OF
 A PEDESTRIAN WARNING SMART SIGN OUTSIDE THE DIXIE HWAY
 DRIVEWAY.
 ADDITIONAL COMMENTS:
 19. PLEASE CONFIRM THE SECTIONS PROVIDED IN THE CIVIL
 SHEET 7 MATCH THE PROPOSED HARDSCAPE, INCLUDING PAVER
 BRICKS.
 20. AS THE LANDSCAPE AND HARDSCAPE ARE PROCESSED UNDER
 A SEPARATE PERMIT, PLEASE INCLUDE IN THIS PERMIT AN
 EXHIBIT LISTING THE AMOUNT OF PRIVATE AND PUBLIC OPEN
 SPACE REQUIRED AND PROVIDED.
 FOR RESUBMITTAL PLEASE INCLUDE A RESPONSE LETTER
 INDICATING IN WHICH PAGE IS THE RESPONSE TO THE COMMENT
 PROVIDED. FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA
 MARIA APONTE AT 561-822-1439.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-10 Cont ID  
Sent By aaponte Date 2020-12-10 Time 15:08 Rev Time 0.00
Received By aaponte Date 2020-12-10 Time 15:08 Sent To  
Notes
2020-12-10 17:11:091. PLEASE INCLUDE THE SITE DATA INFORMATION AS INCLUDED
 IN THE APPROVED SITE PLAN SET SHEET SP-1.
 2.SP1.01 PARKING COUNT SHALL REFLECT THE NUMBER OF
 SURFACE PARKING SPACES EXISTING ALONG THE NORTH
 PROPERTY LINE.
 3. FIRST PARKING SPACE ON THE RIGHT SIDE FROM THE
 GROUND FLOOR UP THE RAMP CAN BE DIMENSIONED AS 8?-6? AS
 IT IS NOT A COMPACT SPACE.
 4. PLEASE INDICATE THE LOCATION OF GUEST AND RETAIL
 PARKING AND SHOW THE MARKINGS PROPOSED.
 5. PLEASE MARK THE TURN AROUND SPACE AS NO PARKING.
 6. PLEASE ADJUST THE PARKING TABLE IN SHEET SP1.01 TO
 REFLECT THAT THE GARAGE HAS ONLY 323 PARKING SPACES AND
 NOT 324 PARKING SPACES.
 7. PLEASE CONFIRM THE SIDEWALKS WILL MEET THE MAXIMUM
 2% CROSS SLOPE AND MEET THE CURB ELEVATION.
 8. PLEASE CONFIRM THE PROPOSED DCDA EQUIPMENT AT THE
 EAST SIDE OF THE PUBLIC OPEN SPACE CAN BE SCREENED WITH
 LANDSCAPE AND MEET UTILITY REQUIREMENTS.
 9. PLEASE CALL OUT THE CANOPY/EYEBROW THAT GOES OVER
 THE PEDESTRIAN ENTRANCE AND GARAGE, AND GENERALLY ABOVE
 THE FIRST FLOOR LINE.
 10. SIGN REQUIRED A SEPARATE PERMIT AND IT IS NOT
 INCLUDED IN THIS PERMIT.
 11. PLEASE PROVIDE INFORMATION TO CONFIRM THAT ALL
 MECHANICAL EQUIPMENT IS SCREENED WITH A LOUVER OR
 PARAPET WALL AS TALL AS THE EQUIPMENT.
 12. TREATMENT OF GARAGE EAST FA?ADE IS MISSING SOME
 ADDITIONAL PAINT VARIATIONS PROPOSED UNDER THE WINDOWS.
 13. PLEASE PROVIDE PHOTOMETRICS FOR THE STREETSCAPE AND
 INCLUDE A DETAIL OF THE DECORATIVE STREETLIGHT TO BE
 INSTALLED WITHIN IN THE PUBLIC REALM TO CONFIRM
 COMPLIANCE WITH CITY STANDARDS.
 14. PLEASE PROVIDE THE BIKE RACK DETAIL WITH PLACEMENT
 DIMENSIONS.
 15. IS ANY OF THE GARAGE LIGHTING VISIBLE FROM THE
 PUBLIC SIDEWALK AND STREET? OR IS THE GARAGE FULLY
 ENCLOSED?
 16. PLEASE INCLUDE A NOTE IN THE CIVIL DRAWING
 SPECIFYING THAT THE SIDEWALK ELEVATION SHALL BE
 MAINTAINED ACROSS THE ALL DRIVEWAY ENTRANCES.
 17. PLEASE IDENTIFY THE LOCATION OF THE ART IN PUBLIC
 PLACES COMPONENT.
 18.PLEASE INCLUDE DETAILS TO CONFIRM COMPLIANCE WITH
 DAC REQUIREMENT FOR THE INSTALLATION OF A PEDESTRIAN
 WARNING SMART SIGN OUTSIDE THE DIXIE HWAY DRIVEWAY.
 FOR RESUBMITTAL PLEASE INCLUDE A RESPONSE LETTER
 INDICATING IN WHICH PAGE IS THE RESPONSE TO THE COMMENT
 PROVIDED.
  