Plan Review Details - Permit 20101376
Plan Review Stops For Permit 20101376
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-12-03 Cont ID  
Sent By cpuell Date 2020-12-03 Time 17:42 Rev Time 0.00
Received By cpuell Date 2020-12-03 Time 17:42 Sent To  
Notes
2020-12-03 17:42:45CHANGE DESCRIPTION TO REFLECT WHERE WORK IS BEING DONE

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-12-07 Cont ID  
Sent By jwitmer Date 2020-12-07 Time 14:31 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-12-07 14:31:27THIS IS A 18 STORY BUSINESS HIGHRISE STILL UNDER
 CONSTRUCTION, SHELL BUILDING (18090469. THE 8 TH FLOOR
 TENANT BUILD-OUT IS STILL CONSIDERED NEW WORK AND DOES
 NOT REQUIRE ASBESTOS SURVEY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-04-06 Cont ID  
Sent By jwitmer Date 2022-04-06 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2022-04-06 Time 06:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-27 Cont ID  
Sent By jwitmer Date 2021-05-27 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2021-05-27 Time 11:14 Sent To  
Notes
2021-05-27 12:22:26WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101376
 ADD: 360 S. ROSEMARY AVE. 8TH FLOOR PARKING 64 GARAGE
 CAR LIFTS.
 CONT: PARK PLUS FL INC.
 TEL: 954-929-7511
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. MAY 27TH/ 2021
 ACTION: DENIED
  
 NOTE, THE RESPONSE SHEET APPEARS TO BE FROM THE
 CONTRACTOR AND NOT THE DESIGN PROFESSIONAL VIRAPHPNH
 SOUKAMNEUTH THE P. E. FOR THIS PROJECT. THE RESPONSE
 COMMENTS 3-5 STATE REFER TO THE ATTACHED ADDENDUM.
 THERE WAS NO ADDENDUM IN THE 2ND SUBMITTAL.
  
 1-2) COMPLIED.
  
 3) 2ND REQUEST. SHEET MP1.0 SHOWS THE 64 CAR LIFTS.
 WHEN VIEWING THE LIFTS APPROXIMATELY 53 & 54 IT APPEARS
 THESE ARE DOUBLE LIFTS JUST LIKE THE REMAINDER OF THE
 LIFTS. WHEN YOU REFER BACK TO THE MASTER PERMIT
 18090469-PAGE AE4.08 THE ENLARGED 8TH FLOOR PLAN
 DIRECTLY ACROSS FROM THE ELEVATOR BANK THE MASTER
 PERMIT SHOWS (2) ACCESSIBLE PARKING SPACES WITH ACCESS
 AISLES. IT WOULD APPEAR THAT THE 2 ACCESSIBLE PARKING
 SPACES AND ACCESS AISLES NEEDS TO BE UPDATED AND SHOWN
 ON THE LIFT PLAN AS WELL. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED, DISCREPANCY IN THE PLANS.
  
 4) 2ND REQUEST. UNDER THE MASTER BUILDING PERMIT FOR
 THIS BUILDING (18090469) THE PARKING SPACES 626-629 ARE
 SET UP FOR ELECTRIC CAR PARKING, DOES THIS MEAN THAT
 FOR THESE SAME PARKING SPACES THERE WILL BE CHARGING
 STATIONS FOR BOTH THE UPPER AND LOWER
 PARKING SPACES THAT WAS PROVIDED BY THE LIFT. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) 2ND REQUEST. SHEET AE4.08 SHOWS THE WEST PALM BEACH
 CITY STANDARD (MARKING WITH DOUBLE LINE) PARKING
 SPACES, WILL THIS FLOOR COMPLY WITH THE CITY STANDARD
 PARKING SPACE AND ACCESSIBLE PARKING SPACES? ACCESSIBLE
 PARKING SPACE / STALL PAINTING.
 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE SPACES.
 EACH PARKING SPACE MUST BE AT LEAST 12 FEET WIDE, SHALL
 BE MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN
 ADJACENT ACCESS AISLE COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
 6) COMPLIED
  
 7) 2ND REQUEST. PLEASE PROVIDE TO WHAT STANDARD THE CAR
 LIFTS HAVE TO MEET. CAR LIFTS DO NOT NEED TO MEET THE
 DEFINITION OF ELEVATORS AND MEET THE EXCEPTION FOUND
 UNDER SECTION 3001.6 EXCEPTION 19. OF THE 2017 FBC-B.
 THIS INFORMATION NEEDS TO SHOW ON THE PLANS.
  
 8) SEMI- COMPLIED, WITH MSDS SHEETS. SHEET MP0.0 DOES
 HAVE A NEW HYDRAULIC POWER PACK BUT THE RESPONSE LETTER
 DOES NOT ANSWER THE QUESTIONS THAT WERE PRESENTED.
 PLEASE PROVIDE THE MSDS SHEETS FOR THE HYDRAULIC FLUID
 THAT APPEARS TO HAVE A COMMON PUMP. PLEASE ALSO SHOW
 THE TOTAL GALLONS OF HYDRAULIC FLUID THAT IT TAKES FOR
 THE WHOLE SYSTEM AND BEING STORED IN A CLOSED SYSTEM.
 2017 FBC-B TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITIES
 PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A
 PHYSICAL HAZARD. ALSO SEE 307.1.1(3). THIS INFORMATION
 NEEDS TO SHOW ON THE PLANS.
  
 9) 2ND REQUEST. THE PLAN SHEET MP2.0 DETAIL 4 INDICATES
 THE USE OF SILKA ANCHORFIX EPOXY ADHESIVE TO THE
 UNDERSIDE OF THE LEG. SEE NOTES FOR APPLICATION
 INSTRUCTIONS. FURTHER DOWN THE PAGE THERE ARE TO ANCHOR
 NOTES:
 NOTE 1. USE ADHESIVE FOR POST TENSION SLAB (DETAIL 3.
 NOTE 2. USE POST INSTALLED ANCHOR FOR REINFORCED
 CONCRETE SLAB. DETAIL 3A.
 PLEASE NOTE DETAIL 3 ONLY STATES SEE ASD REACTIONS @
 TABLE 2.0 (END LEGS). THERE IS NO ADDITIONAL
 INFORMATION BEEN SUBMITTED ON THE ADHESIVE, WHERE IT IS
 SUPPOSED TO BE APPLIED, WHAT SURFACE AREA IT IS TO BE
 SUPPLIED AND THE HOLDING POWER OF THE ADHESIVE WHEN
 CURED. THERE IS NO INFORMATION ON THE PRODUCT SILKA
 ANCHORFIX EPOXY NOR IS THERE EVIDENCE IT HAS BEEN
 REVIEWED BY THE DESIGNER OF RECORD WITH THEIR APPROVAL
 OF A SHOP DRAWING STAMP OF APPROVAL BEFORE BEING
 SUBMITTED TO THE BUILDING DEPARTMENT.
  
 SHEET MP0.0 UNDER THE HEADING MECHANICAL FASTENERS ARE
 REQUIRED STATES ABOUT (3) HILTI KWIKBOLTS 5/8 INCH DIA.
 AND EMBEDMENT OF 4 INCHES. PLANS ARE TO BE SPECIFIC IN
 NATURE.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2020 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1ST ROUND OF COMMENTS. THE PLANS INDICATE THAT
 4-INCH-DEEP HOLES ARE TO BE DRILLED INTO THE POST
 STRESSED DECK. PLEASE PROVIDE HOW WILL THE LOCATION OF
 THE TENDONS IN THE SLAB BE FOUND? IF A TENDON IS NICKED
 WHAT IS THE REPAIR? 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By jwitmer Date 2020-12-07 Time 16:02 Rev Time 0.00
Received By jwitmer Date 2020-12-07 Time 14:00 Sent To  
Notes
2020-12-07 16:02:31WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101376
 ADD: 360 S. ROSEMARY AVE. 8TH FLOOR PARKING 64 GARAGE
 CAR LIFTS.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] CONTACT: DARA NUNEZ
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 07TH/ 2020
 ACTION: DENIED
  
 1) PLEASE NOTE THIS BUILDING IS A 18 STORY OFFICE
 BUILDING WHICH IS CURRENTLY UNDER CONSTRUCTION. TO DATE
 NO CERTIFICATE OF OCCUPANCY NOR CERTIFICATE OF
 COMPLETION HAS BEEN ISSUED. THIS 8TH FLOOR INSTALLATION
 OF 64 PARKING STACKERS FOR 128 CARS LOCATED ON THE 8TH
 FLOOR, CURRENTLY IS A TBD/ TO BE DETERMINED/ O
 CONTRACTOR ASSIGNED TO THIS PROJECT. IF AT TIME THE
 TIME OF PERMIT TO BE ISSUED AND O CERTIFICATE OF
 OCCUPANCY OR COMPLETION HAS BEEN ISSUED THEN WE WILL
 NEED NOTARIZED LETTERS FROM THE SHELL CONTRACTOR (MOSS)
 AND THE TBD CONTRACTOR THAT THEY BOTH WILL WORK TOWARDS
 CODE COMPLIANCE WITHOUT INTERFERENCE OF THE OTHER
 CONTRACTOR OR MATERIALS DISTURBED.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 2) BEFORE PERMIT ISSUANCE AND THE CONTRACTOR IS SIGNED
 ON THE BUILDING PLANS EXAMINER NEEDS TO REVIEW THE
 VALUE OF THE PERMIT THAT THE GENERAL CONTRACTOR HAS
 DECLARED. VALUES MAY NEED TO BE INCREASED. 2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATIVE CODE SECTION 109.3 BUILDING
 PERMIT VALUATION.
  
 3) SHEET MP1.0 SHOWS THE 64 CAR LIFTS. WHEN VIEWING THE
 LIFTS APPROXIMATELY 53 & 54 IT APPEARS THESE ARE DOUBLE
 LIFTS JUST LIKE THE REMAINDER OF THE LIFTS. WHEN YOU
 REFER BACK TO THE MASTER PERMIT 18090469-PAGE AE4.08
 THE ENLARGED 8TH FLOOR PLAN DIRECTLY ACROSS FROM THE
 ELEVATOR BANK THE MASTER PERMIT SHOWS (2) ACCESSIBLE
 PARKING SPACES WITH ACCESS AISLES. IT WOULD APPEAR THAT
 THE 2 ACCESSIBLE PARKING SPACES AND ACCESS AISLES NEEDS
 TO BE UPDATED AND SHOWN ON THE LIFT PLAN AS WELL.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED,
 DISCREPANCY IN THE PLANS.
  
 4) UNDER THE MASTER BUILDING PERMIT FOR THIS BUILDING
 (18090469) THE PARKING SPACES 626-629 ARE SET UP FOR
 ELECTRIC CAR PARKING, DOES THIS MEAN THAT FOR THESE
 SAME PARKING SPACES THERE WILL BE CHARGING STATIONS FOR
 BOTH THE UPPER AND LOWER
 PARKING SPACES THAT WAS PROVIDED BY THE LIFT. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) SHEET AE4.08 SHOWS THE WEST PALM BEACH CITY STANDARD
 (MARKING WITH DOUBLE LINE) PARKING SPACES, WILL THIS
 FLOOR COMPLY WITH THE CITY STANDARD PARKING SPACE AND
 ACCESSIBLE PARKING SPACES? ACCESSIBLE PARKING SPACE /
 STALL PAINTING.
 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE SPACES.
 EACH PARKING SPACE MUST BE AT LEAST 12 FEET WIDE, SHALL
 BE MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN
 ADJACENT ACCESS AISLE COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
 6) SHEET MP2.0 SHOWS THE RECOMMENDED CLEARANCES FOR
 DP003 CAR LIFT. AY WHERE FROM 10FEET 6 INCHES FOR SEDAN
 & SEDAN TO 14 FEET REQUIRED FOR A SUV AND SUV. THE
 SUBMITTED SET OF PLANS DOES NOT PROVIDE WHAT THE CLEAR
 HEIGHT IS FOR THE 8TH FLOOR. IN THE MATER PLANS
 18090469 SHEETS AE3.17 & AE3.18 THESE SHEETS SHOW CUT
 THROUGH SECTIONS SHOW A SUBSTANTIAL AMOUNT OF WHAT
 APPEARS TO BE DECK DRAINAGE PIPES. PLEASE PROVIDE WHAT
 THE CLEAR HEIGHTS ARE FOR THE VARIOUS AREAS.
  
 7) PLEASE PROVIDE TO WHAT STANDARD THE CAR LIFTS HAVE
 TO MEET. CAR LIFTS DO NOT NEED TO MEET THE DEFINITION
 OF ELEVATORS AND MEET THE EXCEPTION FOUND UNDER SECTION
 3001.6 EXCEPTION 19. OF THE 2017 FBC-B. THIS
 INFORMATION NEEDS TO SHOW ON THE PLANS.
  
 8) PLEASE PROVIDE THE MSDS SHEETS FOR THE HYDRAULIC
 FLUID THAT APPEARS TO HAVE A COMMON PUMP. PLEASE ALSO
 SHOW THE TOTAL GALLONS OF HYDRAULIC FLUID THAT IT TAKES
 FOR THE WHOLE SYSTEM AND BEING STORED IN A CLOSED
 SYSTEM. 2017 FBC-B TABLE 307.1(1) MAXIMUM ALLOWABLE
 QUANTITIES PER CONTROL AREA OF HAZARDOUS MATERIALS
 POSING A PHYSICAL HAZARD. ALSO SEE 307.1.1(3). THIS
 INFORMATION NEEDS TO SHOW ON THE PLANS.
  
 9) THE PLANS INDICATE THAT 4-INCH-DEEP HOLES ARE TO BE
 DRILLED INTO THE POST STRESSED DECK. PLEASE PROVIDE HOW
 WILL THE LOCATION OF THE TENDONS IN THE SLAB BE FOUND?
 IF A TENDON IS NICKED WHAT IS THE REPAIR? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-06-29 Cont ID  
Sent By jleahy Date 2022-06-29 Time 16:06 Rev Time 0.00
Received By jleahy Date 2022-06-29 Time 15:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-04-26 Cont ID  
Sent By mpeterso Date 2022-04-26 Time 09:10 Rev Time 0.00
Received By mpeterso Date 2022-04-25 Time 12:35 Sent To  
Notes
2022-04-26 09:17:27ELECTRIC REVIEW FAILED
 1) PREVIOUS COMMENTS NOT ADDRESSED,PLEASE PROVIDE PANEL
 SCHEDULE OR LOAD CALCULATION FOR PANEL PL6 AND UPSTREAM
 PANELS, WIRE SIZES FOR EQUIPMENT DISCONNECTS, WHICH
 CARSTACKERS ARE SERVED BY EACH DISCONNECT AND OTHER
 RELEVANT INFORMATION TO CONVEY THE EXACT SCOPE OF THE
 PROJECT. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-06-01 Cont ID  
Sent By jleahy Date 2021-06-01 Time 14:49 Rev Time 0.00
Received By jleahy Date 2021-06-01 Time 14:45 Sent To  
Notes
2021-06-01 14:51:23ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN, PLEASE INCLUDE THE BRANCH CIRCUIT
 SIZES AND WHERE POWER IS COMING FROM ALONG WITH A LOAD
 CALCULATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-05 Cont ID  
Sent By jleahy Date 2021-01-05 Time 16:52 Rev Time 0.00
Received By jleahy Date 2021-01-05 Time 15:32 Sent To  
Notes
2021-01-05 16:56:46 
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 NEED TO SHOW WHERE POWER COMES FROM AND THE LOAD
 CALCULATION FOR THE ADDITIONAL LOADS.
  
 NEED TO SHOW BRANCH CIRCUI SIZE OF WIRE AND OCP.
  
 JAKE LEAHY BN,
 BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-06-03 Cont ID  
Sent By pleduc Date 2022-06-03 Time   Rev Time 0.00
Received By pleduc Date 2022-06-03 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-03-28 Cont ID  
Sent By pleduc Date 2022-03-28 Time   Rev Time 0.00
Received By pleduc Date 2022-03-28 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-05-27 Cont ID  
Sent By pleduc Date 2021-05-27 Time   Rev Time 0.00
Received By pleduc Date 2021-05-27 Time 15:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-12-04 Cont ID  
Sent By pleduc Date 2020-12-04 Time   Rev Time 0.00
Received By pleduc Date 2020-12-04 Time 14:42 Sent To  
Notes
2020-12-04 14:46:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PROPOSED LIFTS WERE NOT INCLUDED IN THE MASTER
 PERMIT FIRE PROTECTION PLAN; 18090469, NOR FIRE
 SPRINKLER SHOP DRAWINGS; 20020533.
  
 PLEASE PROVIDE AN APPLICABLE EOR REVIEW OF THE PROPOSED
 AND THE TYPE OF FIRE PROTECTION THAT WILL BE PROVIDED.
  
  
  
 2) THE MASTER PERMIT AND/OR THE SHOP DRAWINGS SHALL BE
 REVISED WITH ALL APPLICABLE HYDRAULIC CALCULATIONS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-06-29 Cont ID  
Sent By jleahy Date 2022-06-29 Time 16:32 Rev Time 0.00
Received By jleahy Date 2022-06-01 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-05-27 Cont ID  
Sent By lmarchan Date 2022-05-27 Time 09:09 Rev Time 0.00
Received By lmarchan Date 2022-05-25 Time 08:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-26 Cont ID  
Sent By mpeterso Date 2022-04-26 Time 09:30 Rev Time 0.00
Received By mpeterso Date 2022-03-25 Time 08:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2021-06-01 Cont ID  
Sent By jleahy Date 2021-06-01 Time 14:51 Rev Time 0.00
Received By jleahy Date 2021-05-26 Time 10:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-05 Cont ID  
Sent By jleahy Date 2021-01-05 Time 16:57 Rev Time 0.00
Received By jleahy Date 2020-12-03 Time 16:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-19 Cont ID  
Sent By medwards Date 2022-04-15 Time 15:16 Rev Time 0.00
Received By medwards Date 2022-04-15 Time 15:16 Sent To  
Notes
2022-04-15 15:17:06 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-12-19 Cont ID  
Sent By medwards Date 2020-12-19 Time 06:23 Rev Time 0.00
Received By medwards Date 2020-12-19 Time 06:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-06-29 Cont ID  
Sent By jleahy Date 2022-06-29 Time 16:32 Rev Time 0.00
Received By jleahy Date 2022-06-29 Time 16:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-04-26 Cont ID  
Sent By mpeterso Date 2022-04-26 Time 09:26 Rev Time 0.00
Received By mpeterso Date 2022-04-26 Time 09:26 Sent To  
Notes
2022-04-26 09:29:58SIGNATURE REVIEW FAILED
 1) SHEETS 1-47-10, 13,14,20,22 IN DRAWING FOLDER APPEAR
 THEY DO NOT HAVE THE REWEQUIRED SIGNATURE AND SEAL AS
 REQUIRED BY THE DESIGNER OF RECORD
  
 PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED
 AND SEALED BY THE ENGINEER OF RECORD. PLEASE FOLLOW THE
 DIRECTIONS OUTLINED BELOW TO CORRECT THIS ISSUE.
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING
 DEPARTMENT.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
 PLEASE EMAIL [email protected] AND CC TO
 [email protected] WITH ANY QUESTIONS
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-27 Cont ID  
Sent By jwitmer Date 2021-05-27 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2021-05-27 Time 11:16 Sent To  
Notes
2021-05-27 12:24:57FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-19 Cont ID  
Sent By medwards Date 2020-12-19 Time 06:25 Rev Time 0.00
Received By medwards Date 2020-12-19 Time 06:24 Sent To  
Notes
2020-12-19 06:26:31PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-04 Cont ID  
Sent By ckimmerl Date 2022-04-04 Time 09:51 Rev Time 0.00
Received By ckimmerl Date 2022-04-04 Time 09:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-12-21 Cont ID  
Sent By aaponte Date 2020-12-21 Time 16:20 Rev Time 0.00
Received By aaponte Date 2020-12-21 Time 16:20 Sent To  
Notes
***NONE***