Plan Review Details - Permit 20101364
Plan Review Stops For Permit 20101364
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-12-02 Cont ID  
Sent By cpuell Date 2020-12-02 Time 12:39 Rev Time 0.00
Received By cpuell Date 2020-12-02 Time 12:39 Sent To  
Notes
2020-12-02 12:39:4512/2/20 ADDRESS CHANGED TO 518@ 40TH ST TO REFLECT
 LOCATION OF WORK TO BE DONE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-12-08 Cont ID  
Sent By fgiaquin Date 2021-12-08 Time 11:32 Rev Time 0.00
Received By fgiaquin Date 2021-12-08 Time 11:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-08-26 Cont ID  
Sent By jleahy Date 2021-08-26 Time 11:38 Rev Time 0.00
Received By jleahy Date 2021-08-26 Time 11:24 Sent To  
Notes
2021-08-26 11:39:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SHOW LOCATION OF PANEL AND METER.
  
 IF INSIDE POLE PLEASE SHOW HOW INSTALLTION CONFORMS
 WITH 110.26 FOR WORKING CLEARANCES.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-08-26 Cont ID  
Sent By equinone Date 2021-03-02 Time 10:15 Rev Time 0.00
Received By jleahy Date 2021-03-02 Time 10:15 Sent To  
Notes
2021-08-26 11:38:09ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SHOW LOCATION OF PANEL AND METER.
  
 IF INSIDE POLE PLEASE SHOW HOW INSTALLTION CONFORMS
 WITH 110.26 FOR WORKING CLEARANCES.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-17 Cont ID  
Sent By equinone Date 2020-11-17 Time 15:28 Rev Time 0.00
Received By equinone Date 2020-11-17 Time 15:16 Sent To  
Notes
2020-11-17 15:28:24ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT
 CONSIDERED AN ORIGINAL. FS471, FS481,
  
 EITHER UPLOAD DIGITALLY OR ELECTRONICALLY SIGNED PLANS
 OR YOU CAN SUBMIT SIGNED AND SEALED PAPER ORIGINALS
 WITH A WET SIGNATURE.
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-07-05 Cont ID  
Sent By gpatrie Date 2021-07-05 Time 16:34 Rev Time 0.00
Received By shill Date 2021-07-05 Time 16:34 Sent To  
Notes
2021-07-05 16:34:43PROVISO - CONTACT CITY OF WEST PALM BEACH ENGINEERING
 DEPARTMENT TO DETERMINE IF A RIGHT OF WAY PERMIT IS
 REQUIRED, OBTAIN THAT PERMIT IF REQUIRED
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By rrossano Date 2020-11-19 Time   Rev Time 0.00
Received By rrossano Date 2020-11-19 Time   Sent To  
Notes
2020-11-19 23:56:44PLEASE ADDRESS G. PATRIE COMMENT DATED 11/5/20.

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 3 Status P Date 2021-07-05 Cont ID  
Sent By shill Date 2021-07-05 Time 16:38 Rev Time 0.00
Received By shill Date 2021-07-05 Time 16:38 Sent To  
Notes
2021-07-05 16:39:13PROVISO - CONTACT CITY OF WEST PALM ENGINEERING
 DEPARTMENT, OBTAIN A RIGHT OF WAY PERMIT IF REQUIRED
  

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 2 Status F Date 2021-05-05 Cont ID  
Sent By gpatrie Date 2021-05-05 Time 07:50 Rev Time 0.00
Received By gpatrie Date 2021-05-05 Time 07:50 Sent To  
Notes
2021-06-11 07:01:041. POLE DOES NOT MEET CITY STANDARDS, NON STEALTH.
 2. LAT & LONG LOCATIONS REQUIRED FOR POLE & ALL HAND
 HOLES.
  
 CONTACT: [email protected]
2021-05-05 07:50:33SEE PREVIOUS COMMENTS.

Review Stop ENG-P ENGINEERING PLANNING REVIEW
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By gpatrie Date 2020-11-05 Time 09:14 Rev Time 0.00
Received By gpatrie Date 2020-11-05 Time 09:12 Sent To  
Notes
2020-11-05 09:14:52POLE DESIGN IS UNACCEPTABLE, STEALTH POLE DESIGN IS
 REQUIRED.
  
 A RIGHT-OF-WAY PERMIT IS REQUIRED FOR BORE ALONG 40TH
 ST AND IN ALLEY.
  
 CONTACT: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-12-08 Cont ID  
Sent By fgiaquin Date 2021-12-08 Time 11:33 Rev Time 0.00
Received By fgiaquin Date 2021-12-03 Time 08:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-02 Cont ID  
Sent By lmarchan Date 2021-12-02 Time 08:24 Rev Time 0.00
Received By lmarchan Date 2021-08-10 Time 11:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-05 Cont ID  
Sent By shill Date 2021-07-05 Time 16:39 Rev Time 0.00
Received By shill Date 2021-02-25 Time 06:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-22 Cont ID  
Sent By ccarvaja Date 2020-12-22 Time 12:05 Rev Time 0.00
Received By ccarvaja Date 2020-11-02 Time 11:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-12-08 Cont ID  
Sent By fgiaquin Date 2021-12-08 Time 11:33 Rev Time 0.00
Received By fgiaquin Date 2021-12-08 Time 11:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-02 Cont ID  
Sent By equinone Date 2021-03-02 Time 10:16 Rev Time 0.00
Received By equinone Date 2021-03-02 Time 10:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-17 Cont ID  
Sent By equinone Date 2020-11-17 Time 15:28 Rev Time 0.00
Received By equinone Date 2020-11-17 Time 15:28 Sent To  
Notes
2020-11-17 15:28:56ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT
 CONSIDERED AN ORIGINAL. FS471, FS481,
  
 EITHER UPLOAD DIGITALLY OR ELECTRONICALLY SIGNED PLANS
 OR YOU CAN SUBMIT SIGNED AND SEALED PAPER ORIGINALS
 WITH A WET SIGNATURE.
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-12-01 Cont ID  
Sent By eschneid Date 2021-12-01 Time 18:52 Rev Time 0.25
Received By eschneid Date 2021-09-20 Time 08:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2021-03-15 Cont ID  
Sent By eschneid Date 2021-03-15 Time 16:59 Rev Time 0.25
Received By eschneid Date 2021-03-15 Time 16:38 Sent To  
Notes
2021-03-15 16:59:34FAILED
  
 1) UPDATED COMMENT: THE PLANS SHOW POWER BEING RUN FROM
 AN FPL POLE TO THE 40TH STREET RIGHT-OF-WAY. PROVIDE A
 SURVEY, PREPARED BY A FLORIDA LICENSED SURVEYOR,
 CLEARLY SHOWING THAT THIS WORK IS BEING DONE IN A
 GENERAL UTILITY EASEMENT OR IN THE ALLEY ADJACENT TO
 THE PARCEL. THE SURVEY THAT WAS PROVIDED DOES NOT SHOW
 THE LOCATION OF THE FPL POLE, SO STAFF IS UNABLE TO
 VERIFY THAT THE POLE IS IN THE ALLEY AS SHOWN ON THE
 ENGINEERING PLAN. IF THE POLE (AND THUS THE POWER RUN)
 IT IS NOT IN THE ALLEY, OR AN EASEMENT CLEARLY SHOWN ON
 THE SURVEY, THEN IT MAY NOT BE INSTALLED IN THE
 LOCATION SHOWN.
  
 2) UPDATED COMMENT: IF THE POWER RUN INSTALLATION IS
 SHOWN BY THE SURVEY TO BE IN THE ALLEY, THEN YOU MUST
 SUBMIT AND HAVE APPROVED A COMMUNICATIONS FACILITIES
 PLACEMENT PERMIT APPLICATION FOR CITY RIGHTS-OF-WAY FOR
 THE FIBER INSTALLATION IN BOTH THE ALLEY AND THE 40TH
 STREET RIGHT-OF-WAY. ANY PORTION OF THE POWER RUN ON
 PRIVATE PROPERTY WITHIN AN EASEMENT IS NOT REQUIRED TO
 BE PART OF THE COMMUNICATIONS FACILITIES PLACEMENT
 PERMIT APPLICATION FOR CITY RIGHTS-OF-WAY EXCEPT FOR
 INFORMATIONAL PURPOSES.
  
 3) REPEAT COMMENT: PROVIDE A COPY OF THE FDOT APPROVAL
 FOR THE WORK WITHIN THE BROADWAY AVENUE RIGHT-OF-WAY.
  
 4) REPEAT COMMENT: THE PROPOSED WIRELESS FACILITY (POLE
 WITH EXTERIOR MOUNTED EQUIPMENT) DOES NOT MEET THE CITY
 OF WEST PALM BEACH CONCEALMENT (STEALTH), STYLE
 REQUIREMENTS LISTED IN SECTIONS 78-411(E), 78-411(F)
 AND 78-411(G) OF THE CITY CODE. PROVIDE A POLE THAT
 MEETS THE CITY CODE REQUIREMENTS. NOTE: VERIZON HAS
 SHOWN POLES ON OTHER APPLICATIONS FOR OTHER LOCATIONS
 WITHIN THE CITY THAT MEET THE CITY CODE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-21 Cont ID  
Sent By eschneid Date 2020-12-21 Time 13:46 Rev Time 0.50
Received By eschneid Date 2020-12-21 Time 11:53 Sent To  
Notes
2020-12-21 13:46:06FAILED
  
 1) THE PLANS SHOW POWER BEING RUN UNDER PRIVATE
 PROPERTY FROM THE FPL POLE TO THE 40TH STREET
 RIGHT-OF-WAY. PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, CLEARLY SHOWING THAT THIS WORK IS
 BEING DONE IN A GENERAL UTILITY EASEMENT OR IN THE
 ALLEY ADJACENT TO THE PARCEL. IF IT IS NOT IN AN
 EASEMENT OR THE ALLEY, THEN IT MAY NOT BE INSTALLED IN
 THE LOCATION SHOWN.
  
 2) IF THE INSTALLATION IS SHOWN BY THE SURVEY TO BE IN
 THE ALLEY, THEN YOU MUST SUBMIT AND HAVE APPROVED A
 COMMUNICATIONS FACILITIES PLACEMENT PERMIT APPLICATION
 FOR CITY RIGHTS-OF-WAY FOR THE FIBER INSTALLATION IN
 BOTH THE ALLEY AND THE 40TH STREET RIGHT-OF-WAY. THE
 SURVEY WOULD ALSO NEED TO INCLUDE THE 40TH STREET
 RIGHT-OF-WAY LINE AND THE SIDEWALK LOCATION SO THAT
 STAFF CAN VERIFY THAT THE FIBER INSTALL IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY AS WELL AS THE
 UTILITY LOCATES AND TREES.
  
 3) PROVIDE A COPY OF THE FDOT APPROVAL FOR THE WORK
 WITHIN THE BROADWAY AVENUE RIGHT-OF-WAY.
  
 4) THE PROPOSED WIRELESS FACILITY (POLE WITH EXTERIOR
 MOUNTED EQUIPMENT) DOES NOT MEET THE CITY OF WEST PALM
 BEACH CONCEALMENT (STEALTH), STYLE OR HEIGHT
 REQUIREMENTS LISTED IN SECTIONS 78-411(E), 78-411(F)
 AND 78-411(G) OF THE CITY CODE. PROVIDE A POLE THAT
 MEETS THE CITY CODE REQUIREMENTS. NOTE: VERIZON HAS
 SHOWN POLES ON OTHER APPLICATIONS FOR OTHER LOCATIONS
 WITHIN THE CITY THAT MEET THE CITY CODE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  