| 2020-11-02 15:13:42 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20101341 |
| | 11/2/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED GAS RISER DRAWING DOES NOT APPEAR TO |
| | MATCH THE APPROVED GAS RISER UNDER PERMIT 13080706. THE |
| | APPROVED RISER SHOWS TWO 199,000 BTUH WATER HEATERS AND |
| | SIX 24,0000 BTUH DRYERS- TOTAL LOAD OF 542,000 BTUH AT |
| | 154 FT. TOTAL DEVELOPED LENGTH. THE APPROVED RISER ALSO |
| | SHOWS A 2 IN. GALVANIZED METALLIC BRANCH PIPE TO THE |
| | WATER HEATERS- THE SUBMITTED RISER SHOWS A 1 IN. PIPE. |
| | PLEASE CORRECT THE DRAWING TO MATCH THE EXISTING- |
| | SECTION 402.1 FBC FG, AND SECTION 107.2.1 WPB. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| | WATER HEATER HIGHLIGHTED TO SHOW THE BTUH LOAD AND THE |
| | GAS INPUT PRESSURE- SECTION 624.1 FBC FG. SHOW A NEW |
| | REGULATOR AT THE WATER HEATER IF PRESSURE IS REQUIRED |
| | TO BE DROPPED PER THE SPECS- SECTIONS 410.1 & 410.2 FBC |
| | FG. |
| | |
| | 3) PLEASE CLARIFY IF THE EXISTING VENT SYSTEM IS TO BE |
| | RE-USED OR IF A NEW SYSTEM IS TO BE INSTALLED- SECTION |
| | 107.2.1 WPB. NEW VENT SYSTEMS SHALL BE IN ACCORDANCE |
| | WITH THE MANUFACTURER'S SPECIFICATIONS, AND SECTIONS |
| | 502.1 & 503.1 FBC FG. |
| | |
| | 4) THE $700.00 VALUE ON THE GAS PERMIT APPLICATION |
| | APPEARS LOW. PLEASE NOTE THAT PERMIT VALUE IS BASED ON |
| | LABOR, MATERIAL, EQUIPMENT, APPLIANCES ETC. INCLUDING |
| | THE WATER HEATER- SECTION 109.3 WPB. |
| | |
| | 5) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |