Plan Review Details - Permit 20101339
Plan Review Stops For Permit 20101339
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date   Cont ID  
Sent By jwitmer Date 2021-01-27 Time 10:14 Rev Time 0.00
Received By jwitmer Date 2021-01-27 Time 09:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-11 Cont ID  
Sent By jwitmer Date 2021-01-11 Time 11:13 Rev Time 0.00
Received By jwitmer Date 2021-01-11 Time 09:59 Sent To  
Notes
2021-01-11 11:08:45WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101339
 ADD:7459 RIVERWALK CIR. BLDG.# 205
 CONT: PALM BEACH COUNTY CONTRACTOR CORP.
 TEL: 561-257-3706
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JAN. 11TH/ 2021
 ACTION: DENIED
  
 1) SHEET A-1: UNDER THE HEADING PROJECT DATA THE PLANS
 INDICATE THIS ADDITION IS CONSTRUCTION TYPE 5B,
 UNPROTECTED, UNSPRINKLERED.
 1A) 2ND REQUEST. THE MAXIMUM DEAD END IS GIVEN= W/
 SPRINKLERS 25 FEET. STATED ABOVE A NON-SPRINKLERED
 BUILDING. FBC SECTION 1020.4 STATES NON-SPRINKLERED
 BUILDINGS THE DEAD END MAXIMUM DISTANCE IS 20 FEET.
 107.2.1.2 ADDITIONAL INFORMATION REQUIRED, DISCREPANCY.
  
 1B) COMPLIED.
  
 1C) 2ND REQUEST. THE PLAN STATES LEVEL 2.. PLEASE NOTE
 THE SUBMITTED PLAN SHOULD BE DESIGNED UNDER THE 2017
 FBC-EXISTING BUILDING CODE CHAPTER 11 ADDITIONS.
  
 2) SHEET A-1 TOILET ROOM ELEVATIONS AND EXIST. TOILET
 ROOM ACCESSORY SCHEDULE. THIS IS A NEW ADDITION WHY
 WOULD THE TOILET ACCESSORIES BE EXISTING? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2A) 2ND REQUEST. CHANGE DETAILS. IN BOTH THE ELEVATIONS
 AND ACCESSORY SCHEDULE THE SIDE AND BACK GRAB BAR ARE
 SHOWN MEASURED FROM FLOOR TO THE CENTERLINE OF THE GRAB
 BAR. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION
 OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 2B) 2ND REQUEST. CHANGE DETAILS. THE TOILET PAPER
 DISPENSER IS MEASURED FROM THE BACK WALL TO CENTER LINE
 OF THE DISPENSER MAX. 3 FEET. PLEASE SHOW COMPLIANCE
 WITH THE 2017 ACCESS. CODE SECTION TOILET PAPER
 DISPENSERS. 604.7. THE TOILET PAPER DISPENSER SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM TO 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 2C) THE PLANS ARE SILENT AS TO THE PROTECTION OF THE
 WATER SUPPLY AND DRAINAGE PIPE UNDER THE LAV. 2017
 FBC-ACCESS. CODE 606.5 EXPOSED PIPES AND SURFACES.
 WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT.
  
 3) 2ND REQUEST. SHEET A-1: UNDER THE HEADING OF WALL
 FINISHES THE PLANS INDICATE GYPSUM BOARD. 2017 FBC-B
 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A RESULT
 OF THE BUILDING OFFICIAL INTERPRETATION. IN RESTROOMS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
 2017 FBC-B 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET
 WALLS SHALL COMPLY WITH 1210.2.
 2017 FBC-B 1210.2. FINISH MATERIALS. WALLS, BASE,
 FLOORS AND PARTITIONS IN TOILET AND BATHROOMS SHALL
 COMPLY WITH SECTIONS 1210.1 THROUGH 1210.4.
  
 4-6) COMPLIED.
  
 7) 2ND REQUEST. PLEASE NOTE 3 PRODUCT APPROVALS WERE
 SUBMITTED FOR THE ROOFING MATERIALS. NONE OF THE 3
 ROOFING PRODUCT APPROVALS WERE HIGHLIGHTED/ CIRCLED AS
 FAR AS TYPE OF MATERIALS, TYPE OF FASTENER AND
 ALLOWABLE UPLIFT. 2017 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE
 CODE 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, VENTING, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE.
 NOA # 18-0509.18 EAGLE ROOFING MEDIUM PROFILE CONCRETE
 TILE.
 FL6332-R8 ICP ADHESIVES AND SEALANT,
 FL5259 POLY ROOF UNDERLAYMENT. DOES THIS PRODUCT ALLOW
 DIRECT DECK ATTACHMENT?
  
 8A)COMPLIED EXTERIOR DOOR PRODUCT APPROVAL
  
 8B) SEMI-COMPLIED, DESIGNER OF RECORD NOR CONTRACTOR
 HAS NOT SHOWN COMPLIANCE WITH COMMENT # 7. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 PRODUCT APPROVALS, SHOP DRAWINGS ETC.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-04 Cont ID  
Sent By jwitmer Date 2020-11-04 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2020-11-04 Time 12:16 Sent To  
Notes
2020-11-04 14:11:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101339
 ADD:7459 RIVERWALK CIR. BLDG.# 205
 CONT: PALM BEACH COUNTY CONTRACTOR CORP.
 TEL: 561-257-3706
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 04TH/2020
 ACTION: DENIED
  
 1) SHEET A-1: UNDER THE HEADING PROJECT DATA THE PLANS
 INDICATE THIS ADDITION IS CONSTRUCTION TYPE 5B,
 UNPROTECTED, UNSPRINKLERED.
 1A) THE MAXIMUM DEAD END IS GIVEN= W/ SPRINKLERS 25
 FEET. STATED ABOVE A NON-SPRINKLERED BUILDING.
 107.2.1.2 ADDITIONAL INFORMATION REQUIRED, DISCREPANCY.
  
 1B) THE MAXIMUM TRAVEL = W SPRINKLERS 150 FEET PER
 TABLE 1006. PLEASE NOTE THE TABLES 1006 ALL (3) ARE
 COMMON PATH OF TRAVEL, TABLE 1006.2.1 IS FOR THE 1ST
 FLOOR STORAGE OCCUPANCY < THAN OR EQUAL TO 30 100 FEET
 GREATER OCCUPANT LOAD THAN 30 THEN 75 FEET.
  
 1C) THE PLAN ALSO STATES THAT IT WAS DEVELOPED IN
 COMPLIANCE WITH THE PRESCRIPTIVE COMPLIANCE METHOD.
 LEVEL 2. PLEASE NOTE THE PRESCRIPTIVE COMPLIANCE METHOD
 IS ONE OF 3 COMPLIANCE METHODS. THE WORK AREA METHOD
 (LEVEL 1, 2 & 3) AND THE PERFORMANCE COMPLIANCE METHOD.
 PLEASE NOTE THE SUBMITTED PLAN SHOULD BE DESIGNED UNDER
 THE 2017 FBC-EXISTING BUILDING CODE CHAPTER 11
 ADDITIONS.
  
 2) SHEET A-1 TOILET ROOM ELEVATIONS AND EXIST. TOILET
 ROOM ACCESSORY SCHEDULE. THIS IS A NEW ADDITION WHY
 WOULD THE TOILET ACCESSORIES BE EXISTING? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2A) IN BOTH THE ELEVATIONS AND ACCESSORY SCHEDULE THE
 SIDE AND BACK GRAB BAR ARE SHOWN MEASURED FROM FLOOR TO
 THE CENTERLINE OF THE GRAB BAR. 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 2B) THE TOILET PAPER DISPENSER IS MEASURED FROM THE
 BACK WALL TO CENTER LINE OF THE DISPENSER MAX. 3 FEET.
 PLEASE SHOW COMPLIANCE WITH THE 2017 ACCESS. CODE
 SECTION TOILET PAPER DISPENSERS. 604.7. THE TOILET
 PAPER DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 2C) THE PLANS ARE SILENT AS TO THE PROTECTION OF THE
 WATER SUPPLY AND DRAINAGE PIPE UNDER THE LAV. 2017
 FBC-ACCESS. CODE 606.5 EXPOSED PIPES AND SURFACES.
 WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT.
  
 3) SHEET A-1: UNDER THE HEADING OF WALL FINISHES THE
 PLANS INDICATE GYPSUM BOARD. 2017 FBC-B 1210.2.2. WALLS
 & PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO
 LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
 2017 FBC-B 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET
 WALLS SHALL COMPLY WITH 1210.2.
 2017 FBC-B 1210.2. FINISH MATERIALS. WALLS, BASE,
 FLOORS AND PARTITIONS IN TOILET AND BATHROOMS SHALL
 COMPLY WITH SECTIONS 1210.1 THROUGH 1210.4.
  
 4) SHEET A-1 UNDER THE FOUNDATION LEGEND INDICATES NEW
 8-INCH CMU WALL FILLED CELLS AT 48 INCHES ON CENTER.
 THE SIZE OF THE VERTICAL BARS IS NOT SPECIFIED. THE
 NOTE IS FOR THE BOND BEAM AND DOES NOT MENTION THE
 REBAR FOR THE BOND BEAM? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. SHEET A-2 SHOWS LINTEL
 SCHEDULES.
  
 5) SHEET A-2 PROVIDES THE ROOF PRESSURES FOR ZONES 1-3
 BUT DOES NOT PROVIDE THE WIND DESIGN CRITERIA. NOR ARE
 THE PERUSES GIVEN FOR THE WALL OPENINGS (DOORS).
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 6) THE PLANS ARE SILENT AS TO ATTIC ACCESS. WITH A 4/12
 PITCH AND 20 SPAN, 10 FEET TO CENTERLINE OR 40-INCH
 RISE IN ROOF HEIGHT. PLEASE HOW COMPLIANCE WITH ATTIC
 ACCESS 1209.2 OF THE 2017 FBC-B.
  
 7) PLEASE NOTE 3 PRODUCT APPROVALS WERE SUBMITTED FOR
 THE ROOFING MATERIALS. NONE OF THE 3 ROOFING PRODUCT
 APPROVALS WERE HIGHLIGHTED/ CIRCLED AS FAR AS TYPE OF
 MATERIALS, TYPE OF FASTENER AND ALLOWABLE UPLIFT. 2017
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, VENTING, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE.
 NOA # 18-0509.18 EAGLE ROOFING MEDIUM PROFILE CONCRETE
 TILE.
 FL6332-R8 ICP ADHESIVES AND SEALANT,
 FL5259 POLY ROOF UNDERLAYMENT. DOES THIS PRODUCT ALLOW
 DIRECT DECK ATTACHMENT?
  
 8A) PLEASE NOTE NO PRODUCT APPROVAL WAS SUBMITTED FOR
 THE NEW EXTERIOR RESTROOM DOORS.
 COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS.
  
 8B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-12-02 Cont ID  
Sent By equinone Date 2020-12-02 Time 12:01 Rev Time 0.00
Received By equinone Date 2020-12-02 Time 12:01 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2020-11-05 Cont ID  
Sent By rrossano Date 2020-11-05 Time   Rev Time  
Received By rrossano Date 2020-11-05 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-11-05 Cont ID  
Sent By pleduc Date 2020-11-05 Time   Rev Time 0.00
Received By pleduc Date 2020-11-05 Time 11:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-29 Cont ID  
Sent By lmarchan Date 2021-01-29 Time 10:11 Rev Time 0.00
Received By lmarchan Date 2021-01-26 Time 11:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-12 Cont ID  
Sent By lmarchan Date 2021-01-12 Time 13:34 Rev Time 0.00
Received By lmarchan Date 2021-01-08 Time 11:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-08 Cont ID  
Sent By cpuell Date 2021-01-08 Time 11:24 Rev Time 0.00
Received By lmarchan Date 2020-10-29 Time 09:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-11-04 Cont ID  
Sent By jwitmer Date 2020-11-04 Time 12:25 Rev Time 0.00
Received By jwitmer Date 2020-11-04 Time 12:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-11-10 Cont ID  
Sent By medwards Date 2020-11-10 Time 15:21 Rev Time 0.00
Received By medwards Date 2020-11-10 Time 15:05 Sent To  
Notes
2020-11-10 15:22:28APPROVED WITH PRIVISO: THE BATH EXHAUST FANS MUST BE A
 MINIMUM OF 70 CFM'S BASED ON THE FAN IS BEING
 CONTROLLED BY A SWITCH. FBC M TABLE 4.3.3.1.1 NOTE E

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-11-04 Cont ID  
Sent By lcrespo Date 2020-11-04 Time 16:43 Rev Time 0.00
Received By lcrespo Date 2020-11-04 Time 16:43 Sent To  
Notes
2020-11-04 16:43:5111/04/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date   Cont ID  
Sent By jwitmer Date 2021-01-27 Time 10:14 Rev Time 0.00
Received By jwitmer Date 2021-01-27 Time 09:14 Sent To  
Notes
2021-01-27 10:10:43ROOFING PRODUCT APPROVALS APPROVED UNDEER BUILDING
 PERMIT. J .WITMER 01/27/2021.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-01-11 Cont ID  
Sent By jwitmer Date 2021-01-11 Time 11:05 Rev Time 0.00
Received By jwitmer Date 2021-01-11 Time 11:05 Sent To  
Notes
2021-01-11 11:05:33PLEASE NOTE 3 PRODUCT APPROVALS WERE SUBMITTED FOR THE
 ROOFING MATERIALS. NONE OF THE 3 ROOFING PRODUCT
 APPROVALS WERE HIGHLIGHTED/ CIRCLED AS FAR AS TYPE OF
 MATERIALS, TYPE OF FASTENER AND ALLOWABLE UPLIFT. 2017
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, VENTING, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE.
 NOA # 18-0509.18 EAGLE ROOFING MEDIUM PROFILE CONCRETE
 TILE.
 FL6332-R8 ICP ADHESIVES AND SEALANT,
 FL5259 POLY ROOF UNDERLAYMENT. DOES THIS PRODUCT ALLOW
 DIRECT DECK ATTACHMENT?
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-01-11 Cont ID  
Sent By jwitmer Date 2021-01-11 Time 11:04 Rev Time 0.00
Received By jwitmer Date 2021-01-11 Time 10:00 Sent To  
Notes
2021-01-11 11:04:14ROOFING. PLEASE NOTE 3 PRODUCT APPROVALS WERE SUBMITTED
 FOR THE ROOFING MATERIALS. NONE OF THE 3 ROOFING
 PRODUCT APPROVALS WERE HIGHLIGHTED/ CIRCLED AS FAR AS
 TYPE OF MATERIALS, TYPE OF FASTENER AND ALLOWABLE
 UPLIFT. 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE 107.2.1.2
 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
 NOA # 18-0509.18 EAGLE ROOFING MEDIUM PROFILE CONCRETE
 TILE.
 FL6332-R8 ICP ADHESIVES AND SEALANT,
 FL5259 POLY ROOF UNDERLAYMENT. DOES THIS PRODUCT ALLOW
 DIRECT DECK ATTACHMENT?
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2021-01-27 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2021-01-27 Time 09:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-11 Cont ID  
Sent By jwitmer Date 2021-01-11 Time 11:12 Rev Time 0.00
Received By jwitmer Date 2021-01-11 Time 10:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-10 Cont ID  
Sent By medwards Date 2020-11-10 Time 15:26 Rev Time 0.00
Received By medwards Date 2020-11-10 Time 15:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-01-29 Cont ID  
Sent By llouie Date 2021-01-29 Time   Rev Time 0.00
Received By llouie Date 2021-01-29 Time   Sent To  
Notes
2021-01-29 09:12:39REFERENCE: PB CASE NO. 1100DD.

Review Stop Z ZONING
Rev No 2 Status F Date 2021-01-12 Cont ID  
Sent By llouie Date 2021-01-12 Time   Rev Time 0.00
Received By llouie Date 2021-01-12 Time   Sent To  
Notes
2021-01-12 12:32:39** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) EXPANSION OF THE EXISTING MAINTENANCE BUILDING TO
 INCORPORATE TWO (2) RESTROOMS REQUIRES A MINOR
 AMENDMENT TO THE RIVERWALK RESIDENTIAL PLANNED
 DEVELOPMENT (RPD). PLEASE CONTACT PLANNING AND ZONING
 STAFF FOR ADDITIONAL INFORMATION ON THE APPLICATION
 PROCESS. PLEASE NOTE THAT THE MINOR PLANNED DEVELOPMENT
 (PD) PROCESS IS A SEPARATE PROCESS FROM THE BUILDING
 PERMIT PROCESS AND MUST BE APPROVED BY THE PLANNING AND
 ZONING DIVISION PRIOR TO ZONING SIGN-OFF FOR THE
 BUILDING PERMIT.
  
 [11/6/2020 REPEAT COMMENT: NO RECORD OF A MINOR PD
 AMENDMENT SUBMISSION. STAFF HAS YET TO RECEIVE THE
 MINOR PD AMENDMENT APPLICATION.]
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: RIVERWALK RPD
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-11-06 Cont ID  
Sent By llouie Date 2020-11-06 Time   Rev Time  
Received By llouie Date 2020-11-06 Time   Sent To  
Notes
2020-11-06 09:15:51** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) EXPANSION OF THE EXISTING MAINTENANCE BUILDING TO
 INCORPORATE TWO (2) RESTROOMS REQUIRES A MINOR
 AMENDMENT TO THE RIVERWALK RESIDENTIAL PLANNED
 DEVELOPMENT (RPD). PLEASE CONTACT PLANNING AND ZONING
 STAFF FOR ADDITIONAL INFORMATION ON THE APPLICATION
 PROCESS. PLEASE NOTE THAT THE MINOR PLANNED DEVELOPMENT
 (PD) PROCESS IS A SEPARATE PROCESS FROM THE BUILDING
 PERMIT PROCESS AND MUST BE APPROVED BY THE PLANNING AND
 ZONING DIVISION PRIOR TO ZONING SIGN-OFF FOR THE
 BUILDING PERMIT.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: RIVERWALK RPD
  