Plan Review Details - Permit 20101332
Plan Review Stops For Permit 20101332
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-06-11 Cont ID  
Sent By shill Date 2021-06-11 Time 21:02 Rev Time 0.00
Received By shill Date 2021-06-11 Time 21:02 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-05-17 Cont ID  
Sent By jwitmer Date 2021-05-17 Time 12:27 Rev Time 0.00
Received By jwitmer Date 2021-05-17 Time 11:16 Sent To  
Notes
2021-05-17 12:27:31TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-03-02 Cont ID  
Sent By jwitmer Date 2021-03-02 Time 14:25 Rev Time 0.00
Received By jwitmer Date 2021-03-02 Time 13:41 Sent To  
Notes
2021-03-02 13:53:47TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-06-22 Cont ID  
Sent By jwitmer Date 2021-06-22 Time 13:15 Rev Time 0.00
Received By jwitmer Date 2021-06-22 Time 12:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-11 Cont ID  
Sent By shill Date 2021-06-11 Time 21:06 Rev Time 0.00
Received By shill Date 2021-06-11 Time 21:06 Sent To  
Notes
2021-06-11 21:09:35COMMENTS FROM PREVIOUS LIST WERE NOT ADDRESSED. SEE
 BELOW. TO RECAP:
 CONTRACTORS NEED TO INCLUDE PRINTED NAME AND SIGNATURE
 ON EACH PAGE, LICENSE NUMBER
 FBC 109, VALUE TOO LOW, PROVIDE A COPY OF THE CONTRACT
 AND A COST BREAKDOWN
 SHOW SQUARE FOOT AREAS OF TILE TO BE INSTALLED. ON EACH
 PLAN INDICATE THE FLOORING TYPE THAT WILL BE INSTALLED.
 SCOPE IS NOT CLEAR, VALUE NOT CLEAR.
 [email protected], 561-805-6724
  
  
 THESE ARE COMMENTS FROM PREVIOUS REVIEW WHICH ARE STILL
 NOT ADDRESSED
  
 WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101332
 ADD: 1801 N. FLAGLER DR. # 501
 CONT: COMPLETE CONSTRUCTION & DEVELOPMENT
 TEL: 561-687-8878
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MAY17TH/2021
 ACTION: DENIED
  
 1) 2ND REQUEST. THE ONLY PLANS SUBMITTED THIS TIME WITH
 THE QUALIFIER AND LICENSE NUMBER ON THE PLANS WAS
 ELECTRICAL, THERE WERE NO PLANS SUBMITTED WITH THE
 BUILDING CONTRACTOR QUALIFIER INFORMATION, NAME,
 PRINTED, SIGNATURE AND LICENSE NUMBER.
 1ST ROUND OF COMMENTS. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2 &3) 2ND REQUEST. PROVIDE AN ITEMIZED SHEET SHOWING
 THE SQUARE FOOTAGE OF TILE FOR ON THE FLOORS AND WALLS
 FOR ALL AREAS WHERE WORK IS TO OCCUR. THE PERMIT
 APPLICATION FROM COMPLETE CONSTRUCTION & DEVELOPMENT,
 LEFT THE DESCRIPTION OF WORK BLANK. THE DOLLAR AMOUNT
 IS ALSO BLANK. THE SCOPE OF WORK CANNOT BE DETERMINED
 WITH THE PERMIT APPLICATION AND SUBMITTED PLANS.
  
 THE DOLLAR VALUE FOR THIS PERMIT CURRENTLY CANNOT
 SUBSTANTIATE WORK TO BE ACCOMPLISHED AT THIS TIME.
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4) COMPLIED.
 W. P. B. BUILDING DEPARTMENT HAS
 ALL (3) REQUIRED TEST ON FILE AT CITY HALL
 ON (F) DRIVE FLOOR UNDERLAYMENTS FOR:
  
 WHISPER MAT CS /TILE OR MARBLE
 IIC = 50 DB / 6 INCH SLAB P. T. / NO DROPPED CEILING /
 ASTM E-492
 STC = 55 DB / 6 INCH SLAB P. T./ NO DROPPED / CEILING
 ASTM E-90
 FLAME= 0 ASTM-E84
 SMOKE= 35 ASTM E-84
 J. WITMER BUILD PLAN REVIEW
  
 5) COMPLIED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-17 Cont ID  
Sent By jwitmer Date 2021-05-17 Time 12:16 Rev Time 0.00
Received By jwitmer Date 2021-05-17 Time 11:16 Sent To  
Notes
2021-05-17 12:16:11WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101332
 ADD: 1801 N. FLAGLER DR. # 501
 CONT: COMPLETE CONSTRUCTION & DEVELOPMENT
 TEL: 561-687-8878
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MAY17TH/2021
 ACTION: DENIED
  
 1) 2ND REQUEST. THE ONLY PLANS SUBMITTED THIS TIME WITH
 THE QUALIFIER AND LICENSE NUMBER ON THE PLANS WAS
 ELECTRICAL, THERE WERE NO PLANS SUBMITTED WITH THE
 BUILDING CONTRACTOR QUALIFIER INFORMATION, NAME,
 PRINTED, SIGNATURE AND LICENSE NUMBER.
 1ST ROUND OF COMMENTS. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2 &3) 2ND REQUEST. PROVIDE AN ITEMIZED SHEET SHOWING
 THE SQUARE FOOTAGE OF TILE FOR ON THE FLOORS AND WALLS
 FOR ALL AREAS WHERE WORK IS TO OCCUR. THE PERMIT
 APPLICATION FROM COMPLETE CONSTRUCTION & DEVELOPMENT,
 LEFT THE DESCRIPTION OF WORK BLANK. THE DOLLAR AMOUNT
 IS ALSO BLANK. THE SCOPE OF WORK CANNOT BE DETERMINED
 WITH THE PERMIT APPLICATION AND SUBMITTED PLANS.
  
 THE DOLLAR VALUE FOR THIS PERMIT CURRENTLY CANNOT
 SUBSTANTIATE WORK TO BE ACCOMPLISHED AT THIS TIME.
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4) COMPLIED.
 W. P. B. BUILDING DEPARTMENT HAS
 ALL (3) REQUIRED TEST ON FILE AT CITY HALL
 ON (F) DRIVE FLOOR UNDERLAYMENTS FOR:
  
 WHISPER MAT CS /TILE OR MARBLE
 IIC = 50 DB / 6 INCH SLAB P. T. / NO DROPPED CEILING /
 ASTM E-492
 STC = 55 DB / 6 INCH SLAB P. T./ NO DROPPED / CEILING
 ASTM E-90
 FLAME= 0 ASTM-E84
 SMOKE= 35 ASTM E-84
 J. WITMER BUILD PLAN REVIEW
  
 5) COMPLIED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-02 Cont ID  
Sent By jwitmer Date 2021-03-02 Time 14:25 Rev Time 0.00
Received By jwitmer Date 2021-03-02 Time 13:41 Sent To  
Notes
2021-03-02 14:17:27WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101332
 ADD: 1801 N. FLAGLER DR. # 501
 CONT: COMPLETE CONSTRUCTION & DEVELOPMENT
 TEL: 561-687-8878
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 02/2021
 ACTION: DENIED
  
 1) THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE
 SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE
 AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR
 NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED
 IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) THE PERMIT APPLICATION FROM COMPLETE CONSTRUCTION &
 DEVELOPMENT, LEFT THE DESCRIPTION OF WORK BLANK. THE
 DOLLAR AMOUNT IS ALSO BLANK. THE SCOPE OF WORK CAN NOT
 BE DETERMINED WITH THE PERMIT APPLICATION AND SUBMITTED
 PLANS.
 107.2.1.3. QUALITY OF PLANS. BUILDING PLANS SHALL BE
 DRAWN TO A 1/8TH INCH SCALE ON SUBSTANTIAL. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT
 POLICY OTHER STANDARDS FOR THE PLANS AND SPECIFICATIONS
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA
 STATUTES.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 3) THE DOLLAR VALUE FOR THIS PERMIT CURRENTLY CANNOT
 SUBSTANTIATE WORK TO BE ACCOMPLISHED AT THIS TIME.
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4) THE ORIGINAL PERMIT APPLICATION INDICATES THE
 FLOORING IS TO BE REPLACED. PLEASE PROVIDE THE TYPE OF
 FLOORING AND SQ. FEET AREA. FLOOR INSULATION & FLOOR
 FINISH.
 (FBC-B 2017) FOR TILE, STONE, MARBLE, VINYL AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 4B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2017 FBC-B.
  
 5) THE SUBMITTED PLANS ARE SILENT AS IF THE TILE IN THE
 SHOWER OR BATHTUB WALLS ARE GOING TO BE REPLACED. 5A)
 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 5B) 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-09 Cont ID  
Sent By equinone Date 2021-06-09 Time 07:55 Rev Time 0.00
Received By equinone Date 2021-06-09 Time 07:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-21 Cont ID  
Sent By equinone Date 2021-05-21 Time 09:13 Rev Time 0.00
Received By equinone Date 2021-05-21 Time 09:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-05 Cont ID  
Sent By equinone Date 2021-03-05 Time 15:48 Rev Time 0.00
Received By equinone Date 2021-03-05 Time 15:48 Sent To  
Notes
2021-03-05 15:53:17CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) ELECTRICAL DRAWINGS MUST HAVE THE NAME, LICENSE
 NUMBER, AND SIGNATURE OF THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DREW THE SET OF PLANS. PLEASE PRINT YOUR
 NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE
 YOU ARE LICENSED IN AND PLANS DRAWN.
 2) PLEASE ADD NOTE INDICATING THAT ELECTRICAL WORK MUST
 COMPLY WITH NEC 2017 AND FBC RE 2020, 7TH EDITION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-11 Cont ID  
Sent By shill Date 2021-06-11 Time 21:09 Rev Time 0.00
Received By shill Date 2021-06-08 Time 12:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-21 Cont ID  
Sent By equinone Date 2021-05-21 Time 09:13 Rev Time 0.00
Received By equinone Date 2021-05-13 Time 09:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-03-17 Time   Rev Time 0.00
Received By ccarvaja Date 2021-02-11 Time 09:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-03-02 Cont ID  
Sent By jwitmer Date 2021-03-02 Time 14:25 Rev Time 0.00
Received By jwitmer Date 2021-03-02 Time 13:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-03-09 Cont ID  
Sent By medwards Date 2021-03-09 Time 14:32 Rev Time 0.00
Received By medwards Date 2021-03-09 Time 14:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-06-11 Cont ID  
Sent By ccole Date 2021-06-11 Time 12:00 Rev Time 0.00
Received By ccole Date 2021-06-11 Time 10:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-05-20 Cont ID  
Sent By ccole Date 2021-05-20 Time 12:12 Rev Time 0.00
Received By ccole Date 2021-05-20 Time 11:44 Sent To  
Notes
2021-05-20 12:12:442ND REVIEW FBC-2020 PLUMBING
 PERMIT- 20101332
 5/21/2021
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
 1) THE PLUMBING CONTRACTOR BOBBY KAJAK SHALL PROVIDE
 HIS PRINTED NAME OR COMPANY TITLE BLOCK, SIGNATURE AND
 LICENSE NUMBER ON ALL PLUMBING PLANS HE HAS PREPARED-
 SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H)
 & 471.025.
 2) PLEASE SHOW THE LOCATION OF THE EXISTING TOILET IN
 THE MASTER BATH PLAN- SECTION 107.2.1 WPB.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-17 Cont ID  
Sent By ccole Date 2021-03-17 Time 12:44 Rev Time 0.00
Received By ccole Date 2021-03-17 Time 10:46 Sent To  
Notes
2021-03-17 12:45:351ST REVIEW FBC-2020 PLUMBING
 PERMIT- 20101332
 3/17/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE CLEAR, LEGIBLE PLUMBING PLANS DRAWN
 TO A MINIMUM 1/8 IN. SCALE. THE PLANS SHALL BE DRAWN BY
 EITHER A FL. LICENSED ARCHITECT, ENGINEER OR PLUMBING
 CONTRACTOR- SEE SECTIONS 107.2.1 & 107.2.1.3 WPB, AND
 FL. STATUTES 471.025 & 481.221, AND SECTIONS
 61G1-16.005 & 61G15-23.005 FAC.
  
 2) THE CURRENT HALL BATH PLAN INDICATES A 4 IN. LONG
 BATHTUB BEING REPLACED IN THE HALL BATH WHICH WOULD
 MORE LIKELY BE A 5 FT. TUB BASED ON STANDARD SIZES-
 SECTION 407.1 FBC P. PLEASE INDICATE THE NEW TUB AND
 SHOWER VALVE SHALL BE A BALANCED-PRESSURE, THERMOSTATIC
 OR COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVE
 THAT CONFORMS TO THE REQUIREMENTS OF ASSE 1016/ASME
 A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1-
 SECTION 412.3 FBC P.
 3) PLEASE SHOW THE LOCATION OF THE EXISTING TOILET IN
 THE MASTER BATH PLAN- SECTION 107.2.1 WPB.
  
 4) FAIR HOUSING ACCESSIBILITY GUIDELINES: BECAUSE THE
 BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT AND
 THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN DWELLING
 UNITS, THE PROPOSED ALTERATIONS SHALL ALSO BE IN
 COMPLIANCE WITH THE FAIR HOUSING ACT. THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES ARE INCLUDED IN THE FLORIDA
 ACCESSIBILITY CODE- 2017 SIXTH EDITION. REFER TO
 REQUIRMENT 7 USUABLE KITCHENS AND BATHROOMS AND PAGE
 7.33 IN THE FAIR HOUSING ACT DESIGN MANUAL. THE
 DESIGNER OF RECORD SHALL INDICATE ON THE REVISED PLANS
 WHICH BATHROOM SPECIFICATION- TYPE A OR TYPE B WAS USED
 IN THE ORIGINAL DESIGN. THE DESIGNER OF RECORD FOR THE
 PROJECT IS ADVISED TO DO A RECORDS REQUEST OF THE
 ORIGINAL APPROVED PLANS TO MAKE THAT DETERMINATION.
 RECORDS REQUESTS CAN BE ACCESSED ON THE CITY OF WEST
 PALM BEACH WEBSITE UNDER DEVELOPMENT SERVICES. THE
 ORIGINAL DESIGN INTENT NEEDS TO BE KNOWN IN ORDER TO
 RELOCATE THE TUB AND SHOWER VALVE AND FAUCET TO THE
 OPPOSITE SIDE TO MEET COMPLIANCE WITH THE REQUIRED
 CLEAR FLOOR SPACE APPROACH TO THE BATHTUB AND ACCESS TO
 THE CONTROLS. PLEASE SEE THE FOLLWING PAGES FROM THE
 FAIR HOUSING DESIGN ACT MANUAL- PAGES 7.33, 7.34, 7.35,
 7.36, 7.37, 7.53- 7.55. CONCERNING THE NEW DOUBLE BOWL
 VANITY PLEASE SEE PAGES 7.47- 7.52
 PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE
 GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND
 DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE
 A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE
 ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET
 THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO
 REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF
 SO REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN,
 PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A
 COPY OF THE FAIR HOUSING AFFIDAVIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-06-11 Cont ID  
Sent By shill Date 2021-06-11 Time 21:09 Rev Time 0.00
Received By shill Date 2021-06-11 Time 21:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-17 Cont ID  
Sent By jwitmer Date 2021-05-17 Time 12:17 Rev Time 0.00
Received By jwitmer Date 2021-05-17 Time 11:16 Sent To  
Notes
2021-05-17 12:17:372ND REVIEW
 DATE: MON. MAY17TH/2021
 ACTION: DENIED
  
 1) 2ND REQUEST. THE ONLY PLANS SUBMITTED THIS TIME WITH
 THE QUALIFIER AND LICENSE NUMBER ON THE PLANS WAS
 ELECTRICAL, THERE WERE NO PLANS SUBMITTED WITH THE
 BUILDING CONTRACTOR QUALIFIER INFORMATION, NAME,
 PRINTED, SIGNATURE AND LICENSE NUMBER.
 1ST ROUND OF COMMENTS. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-02 Cont ID  
Sent By jwitmer Date 2021-03-02 Time 14:25 Rev Time 0.00
Received By jwitmer Date 2021-03-02 Time 14:17 Sent To  
Notes
2021-03-02 14:18:481) THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE
 SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE
 AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR
 NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED
 IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  