Plan Review Details - Permit 20101298
| Plan Review Stops For Permit 20101298 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
5 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-05-11 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-05-11 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
4 |
Status |
F |
Date |
2021-05-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-05-11 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-05-11 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2021-05-11 14:30:07 | TO WHOM IT MAY CONCERN, | | | YOUR PERMIT IS READY FOR ISSUANCE WITH THE EXCEPTION OF | | | THE REQUIRED ASBESTOS LETTER: | | | COMMERCIAL ASBESTOS | | | | | | TO THE BUILDING CONTRACTOR: | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING: THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected] OR TO [email protected]. THE INFORMATION | | | SHOULD BE IN PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. | | | PLEASE INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE | | | SUBJECT LINE. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
F |
Date |
2021-02-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-02-07 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-02-07 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2021-02-07 13:44:49 | COMMERCIAL ASBESTOS | | | | | | TO THE BUILDING CONTRACTOR: | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING: THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-01-06 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-01-06 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2021-01-06 11:02:18 | COMMERCIAL ASBESTOS | | | | | | TO THE BUILDING CONTRACTOR: | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING: THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2020-11-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-11-19 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-11-19 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2020-11-19 09:53:47 | COMMERCIAL ASBESTOS | | | | | | TO THE BUILDING CONTRACTOR: | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2021-05-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-05-11 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-05-11 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-02-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-02-07 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-02-07 |
Time |
12:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-01-06 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-01-06 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2021-01-06 11:48:03 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20101298 | | | ADD: 701 BELVEDERE RD. | | | CONT: TORNADO ROOFING AND CONTRACTING, INC. | | | TEL: 954-968-8155 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: WED. JAN. 06TH/2021 | | | ACTION: DENIED | | | | | | 1) SHEET T-1 THE COVERSHEET/ CODE RESEARCH: | | | 1A) COMPLIED. | | | 1B) SEMI-COMPLIED. FOR THE 2ND REVIEW THE CONSTRUCTION | | | TYPE INDICATES AS IIIA PROTECTED , NON-SPRINKLERED. | | | TABLE 601 REQUIRES ALL STRUCTURAL ELEMENTS ARE TO BE | | | ONE HOUR PROTECTED WITH THE EXCEPTION OF THE EXTERIOR | | | BEARING WALLS. PLEASE PROVIDE HOW ALL OF THE STRUCTURAL | | | ELEMENTS ARE 1 HOUR PROTECTED AND THE EXTERIOR BEARING | | | WALLS HAVE A 2 HOUR FIRE RATING. NOTE A III-B | | | CONSTRUCTION UNPROTECTED ONLY HAS TO SHOW A 1 HR. FIRE | | | RATING ON THE EXTERIOR BEARING WALLS. THIS BUILDING | | | QUALIFIES AS A V-B CONSTRUCTION ALLOWING 9,000 SQ. FT. | | | FOR A MERCANTILE OCCUPANCY NON-SPRINKLERED. | | | | | | 1ST ROUND OF COMMENTS. CONSTRUCTION TYPE STATES IIIA | | | UNPROTECTED: FULLY SPRINKLERED. PLEASE REFER TO THE | | | 2017 FBC-B TABLE 601. IN ALL 5 BUILDING CATEGORY TYPES | | | THE TYPE (A) BUILDING HAS AT LEAST A 1-HOUR PROTECTION | | | SO THE BUILDING IS PROTECTED. THE PLANS ALSO STATE THIS | | | BUILDING IS FIRE SPRINKLERED BUT NO FIRE SPRINKLER PLAN | | | WAS INCLUDED IN THE SET OF DOCUMENTS? 107.2.1.2. | | | ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 1C) COMPLIED. | | | 2) COMPLIED. | | | 3) COMPLIED. | | | | | | 4A) SHEET M-3 SHOW A ROOF TOP CONDENSING UNIT ON A | | | STAND. THIS SAME DETAIL INDICATES A NOA 18-0828.09. | | | PLEASE SUBMIT THIS PRODUCT APPROVAL. 1609.6.4.4.1 | | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 | | | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR | | | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(G) PRE-ENGINEERED A/C STANDS/ CURBS/ EXHAUST FANS | | | | | | 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE | | | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP | | | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD | | | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC. | | | | | | 4C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL | | | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO | | | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND | | | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE, BUILDING.FBC-B-1609.6.4.4.1 COMPONENTS | | | AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR | | | CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES | | | COMPONENTS AND ATTACHMENTS. | | | | | | 4D) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP | | | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, | | | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL | | | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. | | | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS. | | | | | | 4E) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE | | | REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE | | | FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) | | | OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, | | | THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, | | | WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, | | | ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE | | | STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL | | | IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED | | | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. | | | | | | 5) SEMI- COMPLIED. WIND DESIGN IS GIVEN BUT NOT THE | | | PRESSURES TO BE EXERTED ON THE ROOF TOP EQUIPMENT AND | | | FOR THEIR SQUARE FOOT AREA PER SIDE, WORST CASE | | | SCENARIO. SEE COMMENT 4E. | | | | | | 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED | | | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR | | | THE DESIGN OF THE STRUCTURE, PSF. | | | | | | 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & | | | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE | | | BUILDING... ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED | | | CONVERSION VULT TO VASD. NOTE THE MIAMI-DADE NOA | | | 18-0719.07 FOR MECHANICAL UNIT TIE DOWN FOR GRADE AND | | | ROOFTOP APPLICATIONS FOR AN EXPLANATION OF THE EXPOSURE | | | CATEGORIES THAT ACCOMPANY THE VULT WIND SPEEDS USED IN | | | THIS DOCUMENT, SEE SECTION 26.7 OF ASCE 7-10. PLEASE | | | PROVIDE THIS INFORMATION. MOST PRODUCT APPROVALS ARE IN | | | VASD NOT IN VULT, IF THE PRESSURES SHOWN ARE IN VULT | | | WHEN REFERRED TO IN VASD THEY MAY NOT BE ADEQUATE. | | | | | | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 | | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-11-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-11-19 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-11-19 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2020-11-19 09:58:50 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20101298 | | | ADD: 701 BELVEDERE RD. | | | CONT: TORNADO ROOFING AND CONTRACTING, INC. | | | TEL: 954-968-8155 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: THURS. NOV. 19TH/2020 | | | ACTION: DENIED | | | | | | 1) SHEET T-1 THE COVERSHEET/ CODE RESEARCH: | | | 1A) THE PLANS STATE THE GOVERNING CODES ARE THE 2010 | | | EDITION OF THE FLORIDA BUILDING CODE AND EXISTING | | | BUILDING CODE (CHAPTER 3401.1). PLEASE NOTE THE 6TH | | | EDITION (2017) OF THE FLORIDA BUILDING CODE WENT INTO | | | EFFECT ON DEC. 31,2017. PLEASE UPDATE THE CODE EDITION | | | AND YEAR. | | | | | | 1B) CONSTRUCTION TYPE STATES IIIA UNPROTECTED: FULLY | | | SPRINKLERED. PLEASE REFER TO THE 2017 FBC-B TABLE 601. | | | IN ALL 5 BUILDING CATEGORY TYPES THE TYPE (A) BUILDING | | | HAS AT LEAST A 1-HOUR PROTECTION SO THE BUILDING IS | | | PROTECTED. THE PLANS ALSO STATE THIS BUILDING IS FIRE | | | SPRINKLERED BUT NO FIRE SPRINKLER PLAN WAS INCLUDED IN | | | THE SET OF DOCUMENTS? 107.2.1.2. ADDITIONAL INFORMATION | | | IS REQUIRED. | | | | | | 1C) THE DESIGNER OF RECORD INDICATES UNDER THE EXISTING | | | BUILDING CODE THIS BUILDING IS A LEVEL III ALTERATION. | | | PLEASE REVIEW THE DEFINITION FOR LEVEL III ALTERATIONS. | | | 505.1 OF THE EXIST. BLDG. CODE. SCOPE. LEVEL 3 | | | ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS 50 PER | | | CENT OF THE BUILDING AREA. 2017 EXIST. BUILDING CODE | | | 907.4.2. SUBSTANTIAL STRUCTURAL ALTERATIONS IS WHERE 30 | | | PERCENT OF THE TOTAL FLOOR AND ROOF AREA OF THE | | | BUILDING HAS BEEN OR PROPOSED TO BE INVOLVED IN | | | STRUCTURAL ALTERATIONS WITHIN A 5 YEAR PERIOD. THIS IS | | | A LEVEL II ALTERATION. | | | | | | 2) SHEET A-3 DETAIL 9 SHOWS BUILT-IN BASE MILLWORK AT A | | | HEIGHT OF 3-0 FEET FROM FINISH FLOOR TO THE TOP OF THE | | | COUNTER. PLEASE SHOW COMPLIANCE WITH THE 2017 | | | FBC-ACCESSIBILITY CODE SECTIONS: | | | 902.1 .WORK SURFACES SHALL COMPLY WITH 902.2 AND 902.3. | | | ADVISORY 902.1 GENERAL. EXAMPLES OF WORK SURFACES | | | INCLUDE WRITING SURFACES, STUDY CARRELS, STUDENT | | | LABORATORY STATIONS, BABY CHANGING AND OTHER TABLES OR | | | FIXTURES FOR PERSONAL GROOMING, COUPON COUNTERS, AND | | | WHERE COVERED BY THE ADA SCOPING PROVISIONS, EMPLOYEE | | | WORKSTATIONS. | | | CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK | | | WRITING SURFACES. WHERE PROVIDED, CHECK WRITING | | | SURFACES SHALL COMPLY WITH 902.3. 902.3HEIGHT. | | | THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM) | | | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. | | | | | | SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION. | | | UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE | | | SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL | | | APPROACH TO AN ELEMENT. | | | | | | 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND | | | SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. | | | THE ACCESSIBLE PORTION OF THE COUNTERTOP SHALL EXTEND | | | THE SAME DEPTH AS THE SALES OR SERVICE COUNTERTOP. | | | | | | 3) SHEETS D-1 AND A-2 SHOW THE REMOVAL OF ONE EXTERIOR | | | DOOR AND CLOSING UP THE OPENING, BUT THERE ARE NO | | | DETAILS FOR THE BLOCKING UP OF THE OPENING AND TIE INS | | | REQUIRED FOR THE BLOCKWORK. 107.2.1.2. ADDITIONAL | | | INFORMATION IS REQUIRED. 2017 FBC-B 2103.4 METAL | | | REINFORCEMENT AND ACCESSORIES. | | | | | | 4A) SHEET M-3 SHOW A ROOF TOP CONDENSING UNIT ON A | | | STAND. THIS SAME DETAIL INDICATES A NOA 18-0828.09. | | | PLEASE SUBMIT THIS PRODUCT APPROVAL. 1609.6.4.4.1 | | | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY | | | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 | | | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR | | | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(G) PRE-ENGINEERED A/C STANDS/ CURBS/ EXHAUST FANS | | | | | | 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE | | | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP | | | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD | | | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC. | | | | | | 4C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL | | | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO | | | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND | | | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE, BUILDING.FBC-B-1609.6.4.4.1 COMPONENTS | | | AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR | | | CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES | | | COMPONENTS AND ATTACHMENTS. | | | | | | 4D) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP | | | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, | | | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL | | | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. | | | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL | | | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY | | | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT | | | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY | | | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. | | | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE | | | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES | | | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND | | | LOADS. | | | | | | 4E) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE | | | REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE | | | FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) | | | OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, | | | THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, | | | WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, | | | ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE | | | STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL | | | IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED | | | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. | | | | | | 5) NO WIND DESIGN CRITERIA WERE FOUND IN EITHER THE | | | ARCHITECTURAL NOR MECHANICAL SHEETS FOR THE NEW ROOF | | | TOP EQUIPMENT, | | | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE | | | STRUCTURE: | | | | | | 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), | | | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS | | | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. | | | | | | 5.2. RISK CATEGORY. | | | | | | 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE | | | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. | | | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. | | | | | | 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. | | | | | | 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED | | | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR | | | THE DESIGN OF THE STRUCTURE, PSF. | | | | | | 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & | | | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE | | | BUILDING... ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED | | | CONVERSION VULT TO VASD. | | | | | | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 | | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-01-15 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-01-15 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-01-15 |
Time |
15:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-12-10 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2020-12-10 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2020-12-10 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2020-12-10 09:52:49 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | REVIEW STATUS: FAILED. | | | | | | 1) IT SEEMS THAT ONLY HALF OF THE PANEL SCHEDULE IS | | | SHOWN ON DRAWINGS. FBC 107 | | | 2) ALL RECEPTACLES IN FOOD PREPARATION AREAS MUST BE | | | GFCI PROTECTED NEC 210.8(B) | | | 3) PLEASE SHOW CIRCUITS FOR AHU 1 AND AHU 2 ON POWER | | | LAYOUT AND PANEL SCHEDULE FBC 107 | | | 4) EXISTING GROUNDING ELECTRODE CONDUCTOR SHOWN IS SIZE | | | #2 CU. PLEASE SPECIFY TYPE OF GROUNDING ELECTRODE | | | SYSTEM USED TO DETERMINE COMPLIANCE WITH NEC 250-66 | | | 5) GFCI, WP RECEPTACLES REQUIRED FOR ALL AC, CU, AHU | | | UNITS AS PER NEC 210-63 | | | 6) PLEASE SUBMIT LOAD CALCULATION FOR EXISTING PANEL A | | | FBC 107 | | | | | | END OF COMMENTS. | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | ENRIQUE QUINONEZ | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-12-30 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-12-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-12-30 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2020-11-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-11-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-11-17 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2020-11-17 16:41:40 | FIRE PROVISO: | | | | | | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | | | ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | | SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER | | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | | | THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2021-05-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-05-10 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-05-10 |
Time |
09:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2021-02-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-02-24 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-02-24 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2021-02-24 11:16:30 | 2ND REVIEW FBC-2017 FUEL GAS | | | PERMIT- 20101298 | | | 2/242021 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST | | | REVIEW LISTED BELOW WERE NOIT ADDRESSED- PLEASE COMPLY. | | | | | | 1) SHEETS P3 & A2: THE EQUIPMENT LIST ON A2 SHOWS GAS | | | STOVE, DOUBLE FRYER AND FLAT GRILL. P3 SHOWS A COOKTOP, | | | FRYER AND GRIDDLE. PLEASE SUBMIT MANUFACTURER?S | | | SPECIFICATIONS FOR THE APPLIANCES SHOWING GAS BTUH | | | LOADS AND INPUT PRESSURES- SECTION 305.1 FBC FG. | | | | | | 2) P3: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR | | | THE COOKING APPLIANCES AND PROVIDE CALCULATIONS- | | | SECTION 304.1 FBC FG. | | | | | | 3) P3: SHOW THE LOCATION OF THE AUTOMATIC GAS SHUTOFF | | | VALVE WHICH IS REQUIRED TO BE CONNECTED TO THE HOOD | | | FIRE SUPPRESSION SYSTEM- SECTION 10.4.1 NFPA 96. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-01-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-01-15 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-01-15 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2021-01-15 11:51:23 | 1ST REVIEW FBC-2017 FUEL GAS | | | PERMIT- 20101298 | | | 1/15/2021 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P3 & A2: THE EQUIPMENT LIST ON A2 SHOWS GAS | | | STOVE, DOUBLE FRYER AND FLAT GRILL. P3 SHOWS A COOKTOP, | | | FRYER AND GRIDDLE. PLEASE SUBMIT MANUFACTURER?S | | | SPECIFICATIONS FOR THE APPLIANCES SHOWING GAS BTUH | | | LOADS AND INPUT PRESSURES- SECTION 305.1 FBC FG. | | | | | | 2) P3: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR | | | THE COOKING APPLIANCES AND PROVIDE CALCULATIONS- | | | SECTION 304.1 FBC FG. | | | | | | 3) P3: SHOW THE LOCATION OF THE AUTOMATIC GAS SHUTOFF | | | VALVE WHICH IS REQUIRED TO BE CONNECTED TO THE HOOD | | | FIRE SUPPRESSION SYSTEM- SECTION 10.4.1 NFPA 96. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-05-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-05-11 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-04-21 |
Time |
09:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-02-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
ccarvaja |
Date |
2021-02-04 |
Time |
06:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-01-15 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-01-15 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2020-12-29 |
Time |
15:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-12-10 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2020-12-10 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2020-11-10 |
Time |
13:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2021-05-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-05-11 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-05-11 |
Time |
14:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-11-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-11-19 |
Time |
10:00 |
Rev Time |
|
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-11-19 10:00:05 | IMPACT FEES - DIGITAL SUBMITTALS: | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 | | | N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2021-05-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-10 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-10 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2021-05-10 12:55:23 | THE HOOD AND GREASE DUCT MUST BE PERMITTED SEPARATELY. | | | NO REVIEW HAS BEEN DONE ON THIS SYSTEM. NO | | | REFRIGERATION HAS BEEN REVIEWED ON THIS PROJECT. A | | | SEPARATE PERMIT AND REVIEW SHALL BE DONE OF | | | REFRIGERATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2021-02-23 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-23 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-23 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2021-02-23 12:58:05 | THE HOOD AND GREASE DUCT MUST BE PERMITTED SEPARATELY. | | | NO REVIEW HAS BEEN DONE ON THIS SYSTEM. NO | | | REFRIGERATION HAS BEEN REVIEWED ON THIS PROJECT. A | | | SEPARATE PERMIT AND REVIEW SHALL BE DONE OF | | | REFRIGERATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2021-01-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-01-12 |
Time |
06:37 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-01-12 |
Time |
06:35 |
Sent To |
|
|
| Notes |
| 2021-01-12 06:37:17 | PLEASE ADDRESS TO NOTES 3 AND 4 BELOW FROM THE FIRST | | | REVIEW. | | | | | | 3) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC C403.2.1 | | | | | | 4) PLEASE PROVIDE SPECIFICATIONS FOR THE AHU?S FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-12-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-05 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-05 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2020-12-05 09:55:25 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT -20101298 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE HOOD SHALL BE PERMITTED AND REVIEWED SEPARATELY. | | | | | | 2) ALL REFRIGERATION WORK SHALL BE PERMITTED AND | | | REVIEWED SEPARATELY. | | | | | | 3) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC C403.2.1 | | | | | | 4) PLEASE PROVIDE SPECIFICATIONS FOR THE AHU?S FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2021-05-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-05-10 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-05-10 |
Time |
09:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2021-02-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-02-24 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-02-24 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2021-02-24 11:13:12 | 3RD REVIEW FBC-2017 PLUMBING | | | PERMIT- 20101298 | | | 2/23/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | REMAINING FAILED COMMENTS FROM THE 1ST AND 2ND REVIEW | | | ARE LISTED BELOW. PLEASE NOTE THE REQUESTED RESPONSE | | | NARRATIVE FROM THE DESIGN PROFESSIONALS WHICH HELPS | | | EXPEDITE THE REVIEW PROCESS WAS NOT SUBMITTED. | | | | | | 1) FAILED. SHEET P1: PROVIDE PLUMBING FIXTURE | | | CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDE NUMBER OF FIXTURES. PLEASE NOTE THAT DRINKING | | | FOUNTAINS ARE REQUIRED FIXTURES FOR MERCANTILE | | | OCCUPANCIES. THE EXCEPTION ALLOWED FOR RESTAURANTS | | | SERVING DRINKING WATER TO CUSTOMERS UNDER SECTION 410.4 | | | DOES NOT APPLY. THE DRINKING FOUNTAINS SHALL BE | | | ACCESSIBLE IN COMPLIANCE WITH SECTIONS 211.2, & 602.1- | | | 602.6 FBC ACC. THE ARCHITECT OF RECORD INDICATES AN | | | OCCUPANT LOAD OF 33 ON SHEET A2 WHICH CONTRADICTS HIS | | | LOAD OF 15 SHOWN IN THE FIXTURE CALCULATIONS. PLEASE | | | PROVIDE THE REQUIRED DRINKING FOUNTAINS- SEE SECTION | | | 410.2 FBC P. | | | | | | 2) FAILED. P1: SHOW THE LOCATIONS OF THE DRINKING | | | FOUNTAINS AND REVISE THE PLUMBING PIPING PLANS AND | | | ISOMETRIC DRAWINGS ACCORDINGLY- SECTION 107.3.5.3 WPB. | | | SEE FAILED COMMENT #1 ABOVE. | | | | | | 3) FAILED. PROVIDE DRINKING FOUNTAIN INSTALLATION | | | DETAILS SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND | | | 602 FBC ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND | | | TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. | | | INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH | | | SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION | | | PATH. SEE FAILED COMMENT #1 ABOVE. | | | | | | 5) FAILED. P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE | | | OF THE PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. | | | PLEASE PROVIDE CLEAR AND COMPLETE SANITARY AND WATER | | | RISERS- SECTIONS 107.2.1 & 107.3.5.3 WPB. PLEASE NOTE | | | THAT THE CHIEF PLUMBING INSPECTOR TIMOTHY LARGE IS NOW | | | REQUIRING ALL MOP SINKS IN RESTAURANTS, OR OTHER | | | FACILITIES WITH COOKING APPLIANCES, TO DRAIN INTO A | | | GREASE INTERCEPTOR. THE HAND SINK SHALL DRAIN INTO THE | | | SANITARY AND NOT INTO THE GREASE INTERCEPTOR. PLEASE | | | DISREGARD PREVIOUS COMMENT AND CORRECT THE PLUMBING | | | PLANS. IF YOU HAVE QUESTIONS PLEASE CONTACT MR. LARGE | | | AT [email protected], 561-805-6692. | | | | | | 10) FAILED. P1 & P2: PLEASE PROVIDE A WATER RISER AND A | | | WATER DISTRIBUTION LAYOUT PLAN. CONNECTION TO THE SODA | | | FILTERING SYSTEM NOT SHOWN- SEE SCHEMATIC ON P-2. | | | | | | 10B) FAILED. SHOW THE SOURCE OF THE HOT WATER TO THE | | | NEW AND EXISTING FIXTURES AND THE TEMPERATURE OF THE | | | WATER- SECTION 607.1. PLEASE LABEL THE WATER HEATER AS | | | NEW OR EXISTING ON THE PLANS. | | | FOR NEW WATER HEATER INSTALLATIONS: PROVIDE AN | | | EQUIPMENT SCHEDULE ON THE PLAN INDICATING MAKE, MODEL, | | | GALLON SIZE, AND EFFICIENCY RATING. PLEASE NOTE THAT | | | MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUAL | | | SHALL BE ONSITE AT TIME OF INSPECTION. PROVIDE PLUMBING | | | PIPING DETAILS- COLD WATER FEED, SHUTOFF VALVE, CHECK | | | VALVE, THERMAL EXPANSION TANK, RECIRCULATION PUMP, | | | RELIEF VALVE, RELIEF VALVE DISCHARGE PIPING, DRAIN PAN, | | | DRAIN PAN LINE, HW PIPE INSULATION- SEE SECTIONS 502 & | | | 607 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2021-01-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-01-15 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-01-15 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2021-01-15 11:55:50 | 2ND REVIEW FBC-2017 PLUMBING | | | PERMIT- 20101298 | | | 1/15/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE | | | MARKED AS PASSED OR FAILED. NOTES HAVE BEEN ADDED TO | | | FAILED COMMENTS. PLEASE NOTE THE REQUESTED RESPONSE | | | NARRATIVE FROM THE DESIGN PROFESSIONALS WHICH HELPS | | | EXPEDITE THE REVIEW PROCESS WAS NOT SUBMITTED. IT | | | APPEARS THAT CORRECTED PLUMBING PLANS BASED ON 1ST | | | REVIEW COMMENTS WERE NOT PROVIDED. | | | | | | 1) FAILED. SHEET P1: PROVIDE PLUMBING FIXTURE | | | CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDE NUMBER OF FIXTURES. PLEASE NOTE THAT DRINKING | | | FOUNTAINS ARE REQUIRED FIXTURES FOR MERCANTILE | | | OCCUPANCIES. THE EXCEPTION ALLOWED FOR RESTAURANTS | | | SERVING DRINKING WATER TO CUSTOMERS UNDER SECTION 410.4 | | | DOES NOT APPLY. THE DRINKING FOUNTAINS SHALL BE | | | ACCESSIBLE IN COMPLIANCE WITH SECTIONS 211.2, & 602.1- | | | 602.6 FBC ACC. | | | | | | 2) FAILED. P1: SHOW THE LOCATIONS OF THE DRINKING | | | FOUNTAINS AND REVISE THE PLUMBING PIPING PLANS AND | | | ISOMETRIC DRAWINGS ACCORDINGLY- SECTION 107.3.5.3 WPB. | | | | | | 3) FAILED. PROVIDE DRINKING FOUNTAIN INSTALLATION | | | DETAILS SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND | | | 602 FBC ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND | | | TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. | | | INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH | | | SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION | | | PATH. | | | | | | 4) PASSED. GAS ISOMETRIC SUBMITTED WILL BE REVIEWED | | | UNDER THIS PERMIT- A GAS SUB-PERMIT WILL BE REQUIRED. | | | GREASE INTERCEPTOR INFORMATION PROVIDED WILL BE | | | REVIEWED, HOWEVER A SEPARATE PRIMARY PERMIT IS REQUIRED | | | FOR INSTALLATION. PLEASE NOTE THAT SUB-PERMITS | | | SUBMITTED WITH MAIN PERMITS ARE ?NO-FEE?. A FEE WILL BE | | | CHARGED FOR SUB-PERMITS APPLIED FOR AFTER MAIN PERMIT | | | ISSUANCE. FINAL APPROVAL OF THE GAS PLANS HOWEVER WILL | | | NOT REQUIRE SUBMITTAL OF THE APPLICATION. P1: PLEASE | | | NOTE THAT SEPARATE PERMITS AND PLAN SUBMITTALS ARE | | | REQUIRED FOR THE GAS PIPING AND GREASE INTERCEPTOR | | | INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB. A COMPLETE | | | REVIEW OF THESE SYSTEMS HAS NOT BEEN PERFORMED AT THIS | | | TIME. | | | | | | 5) FAILED. P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE | | | OF THE PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. | | | PLEASE PROVIDE CLEAR AND COMPLETE SANITARY AND WATER | | | RISERS- SECTIONS 107.2.1 & 107.3.5.3 WPB. THE CORRECTED | | | RISER SHALL IDENTIFY THE FIXTURES AND SHOW THE TYPE OF | | | DRAIN CONNECTIONS- DIRECT OR INDIRECT, AND ALSO SHOW | | | POINTS OF CONNECTIONS TO THE EXISTING SANITARY AND VENT | | | SYSTEMS. A MINIMUM OF ONE VENT FOR THE BUILDING DRAIN | | | SHALL EXTEND TO THE OUTDOORS- SECTION 904.1 FBC P. | | | | | | 6) FAILED. P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC | | | P THE MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT | | | INTO THE GREASE WASTE LINE. PLEASE REVISE THE PLANS, | | | SCHEDULE, AND CALCULATIONS ACCORDINGLY. | | | | | | 7) FAILED. P1: PLEASE PLACE A NOTE TO REQUIRE A COVER | | | FOR THE MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER | | | AND OTHER FLUIDS AND WASTES FROM DRAINING INTO THE CITY | | | SANITARY SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES. | | | | | | 8) FAILED. A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN | | | THE DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA | | | DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND | | | PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P. | | | PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE | | | RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR- | | | SECTION 1003.3.1 FBC P. | | | | | | 9) FAILED. D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT | | | PROVIDE A MEANS FOR THE DRAIN LINES FROM THE HAND SINK | | | AND FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE | | | WASTE AND SANITARY DRAIN LINES. PLEASE PROVIDE THE SLAB | | | CUTS AND SLAB REPAIR DETAILS- SECTION 107.2.1 WPB. | | | PLEASE REVIEW THE PLUMBING PLANS AND REVISE D-1 TO SHOW | | | THE SLAB CUTS RELATIVE TO THE UNDERSLAB DRAIN LINES. | | | | | | 10) P1 & P2: FAILED 10A-F. PLEASE PROVIDE A WATER RISER | | | AND A WATER DISTRIBUTION LAYOUT PLAN: | | | | | | A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER | | | DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3 | | | FBC P. | | | | | | B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND | | | EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER- | | | SECTION 607.1. | | | | | | C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND | | | EQUIPMENT- SECTION 606.2. | | | | | | D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS- | | | SECTION 604.9. | | | | | | E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS | | | TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE | | | AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1 | | | FBC P. | | | | | | F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE | | | LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2. | | | | | | 11) FAILED. P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR | | | DRAINS AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN | | | THE ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P. | | | | | | 12) FAILED. P1 & P2: PROVIDE A COMPLETE PLUMBING | | | FIXTURE SCHEDULE THAT INCLUDES THE MOP SINK, | | | 3-COMPARTMENT SINK, HAND SINK, DRINKING FOUNTAIN, | | | FAUCETS, FLOOR DRAINS, FLOOR SINKS- SECTION 107.2.1 | | | WPB. | | | | | | 13) FAILED. PROVIDE A PLUMBING DEVICE SCHEDULE | | | INCLUDING THE WATER HAMMER ARRESTORS, MIXING VALVE, | | | BACKFLOW PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1 | | | WPB. | | | | | | 14) PASSED. PROVIDE A PLUMBING SUB-PERMIT APPLICATION- | | | SECTION 105.1 WPB. PLEASE NOTE THAT SUB-PERMITS | | | SUBMITTED WITH MAIN PERMITS ARE "NO-FEE". A FEE WILL BE | | | CHARGED FOR SUB-PERMITS APPLIED FOR AFTER MAIN PERMIT | | | ISSUANCE. FINAL APPROVAL OF THE PLUMBING PLANS HOWEVER | | | WILL NOT REQUIRE SUBMITTAL OF THE APPLICATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-12-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-12-09 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-12-09 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2020-12-09 11:56:42 | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT- 20101298 | | | 12/9/2020 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN | | | ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE | | | THAT INDICATES THE REQUIRED AND PROVIDE NUMBER OF | | | FIXTURES. PLEASE NOTE THAT DRINKING FOUNTAINS ARE | | | REQUIRED FIXTURES FOR MERCANTILE OCCUPANCIES. THE | | | EXCEPTION ALLOWED FOR RESTAURANTS SERVING DRINKING | | | WATER TO CUSTOMERS UNDER SECTION 410.4 DOES NOT APPLY. | | | THE DRINKING FOUNTAINS SHALL BE ACCESSIBLE IN | | | COMPLIANCE WITH SECTIONS 211.2, & 602.1- 602.6 FBC ACC. | | | | | | 2) P1: SHOW THE LOCATIONS OF THE DRINKING FOUNTAINS AND | | | REVISE THE PLUMBING PIPING PLANS AND ISOMETRIC DRAWINGS | | | ACCORDINGLY- SECTION 107.3.5.3 WPB. | | | | | | 3) PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS | | | SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND 602 FBC | | | ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND TOE | | | CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. | | | INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH | | | SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION | | | PATH. | | | | | | 4) P1: PLEASE NOTE THAT SEPARATE PERMITS AND PLAN | | | SUBMITTALS ARE REQUIRED FOR THE GAS PIPING AND GREASE | | | INTERCEPTOR INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB. | | | A COMPLETE REVIEW OF THESE SYSTEMS HAS NOT BEEN | | | PERFORMED AT THIS TIME. | | | | | | 5) P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE OF THE | | | PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. PLEASE | | | PROVIDE CLEAR AND COMPLETE SANITARY AND WATER RISERS- | | | SECTIONS 107.2.1 & 107.3.5.3 WPB. | | | | | | 6) P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE | | | MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT INTO THE | | | GREASE WASTE LINE. PLEASE REVISE THE PLANS, SCHEDULE, | | | AND CALCULATIONS ACCORDINGLY. | | | | | | 7) P1: PLEASE PLACE A NOTE TO REQUIRE A COVER FOR THE | | | MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER AND OTHER | | | FLUIDS AND WASTES FROM DRAINING INTO THE CITY SANITARY | | | SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES. | | | | | | 8) A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN THE | | | DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA | | | DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND | | | PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P. | | | PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE | | | RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR- | | | SECTION 1003.3.1 FBC P. | | | | | | 9) D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT PROVIDE | | | A MEANS FOR THE DRAIN LINES FROM THE HAND SINK AND | | | FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE | | | WASTE AND SANITARY DRAIN LINES. PLEASE PROVIDE THE SLAB | | | CUTS AND SLAB REPAIR DETAILS- SECTION 107.2.1 WPB. | | | | | | 10) P1 & P2: PLEASE PROVIDE A WATER RISER AND A WATER | | | DISTRIBUTION LAYOUT PLAN: | | | | | | A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER | | | DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3 | | | FBC P. | | | | | | B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND | | | EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER- | | | SECTION 607.1. | | | | | | C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND | | | EQUIPMENT- SECTION 606.2. | | | | | | D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS- | | | SECTION 604.9. | | | | | | E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS | | | TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE | | | AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1 | | | FBC P. | | | | | | F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE | | | LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2. | | | | | | 11) P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR DRAINS | | | AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN THE | | | ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P. | | | | | | 12) P1 & P2: PROVIDE A COMPLETE PLUMBING FIXTURE | | | SCHEDULE THAT INCLUDES THE MOP SINK, 3-COMPARTMENT | | | SINK, HAND SINK, DRINKING FOUNTAIN, FAUCETS, FLOOR | | | DRAINS, FLOOR SINKS, DOME DRAIN- SECTION 107.2.1 WPB. | | | | | | 13) PROVIDE A PLUMBING DEVICE SCHEDULE INCLUDING THE | | | WATER HAMMER ARRESTORS, MIXING VALVE, BACKFLOW | | | PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1 WPB. | | | | | | 14) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION | | | 105.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | 2020-12-09 11:56:20 | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT- 20101298 | | | 12/9/2020 | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | PLAN REVIEW RESULTS: DENIED. | | | 1) SHEET P1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN | | | ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE | | | THAT INDICATES THE REQUIRED AND PROVIDE NUMBER OF | | | FIXTURES. PLEASE NOTE THAT DRINKING FOUNTAINS ARE | | | REQUIRED FIXTURES FOR MERCANTILE OCCUPANCIES. THE | | | EXCEPTION ALLOWED FOR RESTAURANTS SERVING DRINKING | | | WATER TO CUSTOMERS UNDER SECTION 410.4 DOES NOT APPLY. | | | THE DRINKING FOUNTAINS SHALL BE ACCESSIBLE IN | | | COMPLIANCE WITH SECTIONS 211.2, & 602.1- 602.6 FBC ACC. | | | 2) P1: SHOW THE LOCATIONS OF THE DRINKING FOUNTAINS AND | | | REVISE THE PLUMBING PIPING PLANS AND ISOMETRIC DRAWINGS | | | ACCORDINGLY- SECTION 107.3.5.3 WPB. | | | 3) PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS | | | SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND 602 FBC | | | ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND TOE | | | CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. | | | INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH | | | SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION | | | PATH. | | | 4) P1: PLEASE NOTE THAT SEPARATE PERMITS AND PLAN | | | SUBMITTALS ARE REQUIRED FOR THE GAS PIPING AND GREASE | | | INTERCEPTOR INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB. | | | A COMPLETE REVIEW OF THESE SYSTEMS HAS NOT BEEN | | | PERFORMED AT THIS TIME. | | | 5) P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE OF THE | | | PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. PLEASE | | | PROVIDE CLEAR AND COMPLETE SANITARY AND WATER RISERS- | | | SECTIONS 107.2.1 & 107.3.5.3 WPB. | | | 6) P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE | | | MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT INTO THE | | | GREASE WASTE LINE. PLEASE REVISE THE PLANS, SCHEDULE, | | | AND CALCULATIONS ACCORDINGLY. | | | 7) P1: PLEASE PLACE A NOTE TO REQUIRE A COVER FOR THE | | | MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER AND OTHER | | | FLUIDS AND WASTES FROM DRAINING INTO THE CITY SANITARY | | | SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES. | | | 8) A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN THE | | | DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA | | | DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND | | | PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P. | | | PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE | | | RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR- | | | SECTION 1003.3.1 FBC P. | | | 9) D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT PROVIDE | | | A MEANS FOR THE DRAIN LINES FROM THE HAND SINK AND | | | FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE | | | WASTE AND SANITARY DRAIN LINES- SECTION 107.2.1 WPB. | | | 10) P1 & P2: PLEASE PROVIDE A WATER RISER AND A WATER | | | DISTRIBUTION LAYOUT PLAN: | | | A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER | | | DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3 | | | FBC P. | | | B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND | | | EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER- | | | SECTION 607.1. | | | C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND | | | EQUIPMENT- SECTION 606.2. | | | D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS- | | | SECTION 604.9. | | | E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS | | | TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE | | | AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1 | | | FBC P. | | | F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE | | | LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2. | | | 11) P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR DRAINS | | | AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN THE | | | ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P. | | | 12) P1 & P2: PROVIDE A COMPLETE PLUMBING FIXTURE | | | SCHEDULE THAT INCLUDES THE MOP SINK, 3-COMPARTMENT | | | SINK, HAND SINK, DRINKING FOUNTAIN, FAUCETS, FLOOR | | | DRAINS, FLOOR SINKS, DOME DRAIN- SECTION 107.2.1 WPB. | | | 13) PROVIDE A PLUMBING DEVICE SCHEDULE INCLUDING THE | | | WATER HAMMER ARRESTORS, MIXING VALVE, BACKFLOW | | | PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1 WPB. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-05-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-05-11 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-05-11 |
Time |
14:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-02-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-02-24 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-02-24 |
Time |
11:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-01-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-01-15 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-01-15 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2021-01-15 12:13:52 | 2ND SIGNATURE REVIEW | | | 1/15/21 | | | | | | 1) NEW SHEETS T1, A1, A3, E1, M1, M2, M3 DO NOT BEAR | | | THE DIGITAL SIGNATURE AND SEAL OF THE ARCHITECT OF | | | RECORD AS REQUIRED BY FL. STATUTE 481.221 AND SECTION | | | 61G1 16.005 FLORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-12-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-05 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-05 |
Time |
09:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-12-31 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-12-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-12-31 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-12-31 09:18:41 | ZONING APPROVED WITH THE FOLLOWING PROVISO: | | | | | | 1.) SCOPE OF WORK IS FOR INTERIOR REMODEL ONLY. ANY | | | WORK DONE TO THE EXTERIOR/SITE WILL REQUIRE SEPARATE | | | BUILDING PERMIT(S). | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-11-18 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-11-18 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2020-11-18 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-11-18 12:18:51 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PROVIDE A SIGNED AND SEALED SURVEY OF THE PROPERTY. | | | | | | 2.) THERE SEEMS TO BE EXTERIOR SITE IMPROVEMENTS SHOWN | | | IN THE PLANS. PLEASE CLARIFY. A SITE PLAN SHOWING THE | | | SETBACK DISTANCE FROM ANY NEW STRUCTURE/IMPROVEMENT | | | WILL BE REQUIRED IF EXTERIOR SITE IMPROVEMENTS ARE | | | MADE. | | | | | | | | | NOTES: | | | | | | * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * DO NOT HESITATE TO CONTACT LINDA LOUIE @ (561) | | | 822-1458 IF THERE ARE ANY QUESTIONS. | | | | | | * ZONE: NC | | | |
|
|
|