Plan Review Details - Permit 20101298
Plan Review Stops For Permit 20101298
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 5 Status P Date   Cont ID  
Sent By   Date 2021-05-11 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2021-05-11 Time 15:58 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status F Date 2021-05-11 Cont ID  
Sent By jwitmer Date 2021-05-11 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2021-05-11 Time 14:02 Sent To  
Notes
2021-05-11 14:30:07TO WHOM IT MAY CONCERN,
 YOUR PERMIT IS READY FOR ISSUANCE WITH THE EXCEPTION OF
 THE REQUIRED ASBESTOS LETTER:
 COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] OR TO [email protected]. THE INFORMATION
 SHOULD BE IN PDF FORMAT AS AN ATTACHMENT TO THE EMAIL.
 PLEASE INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE
 SUBJECT LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2021-02-07 Cont ID  
Sent By jwitmer Date 2021-02-07 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2021-02-07 Time 12:58 Sent To  
Notes
2021-02-07 13:44:49COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-01-06 Cont ID  
Sent By jwitmer Date 2021-01-06 Time 11:05 Rev Time 0.00
Received By jwitmer Date 2021-01-06 Time 11:00 Sent To  
Notes
2021-01-06 11:02:18COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By jwitmer Date 2020-11-19 Time 10:01 Rev Time 0.00
Received By jwitmer Date 2020-11-19 Time 07:57 Sent To  
Notes
2020-11-19 09:53:47COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-05-11 Cont ID  
Sent By jwitmer Date 2021-05-11 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2021-05-11 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-02-07 Cont ID  
Sent By jwitmer Date 2021-02-07 Time 13:45 Rev Time 0.00
Received By jwitmer Date 2021-02-07 Time 12:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-06 Cont ID  
Sent By jwitmer Date 2021-01-06 Time 11:48 Rev Time 0.00
Received By jwitmer Date 2021-01-06 Time 11:00 Sent To  
Notes
2021-01-06 11:48:03WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101298
 ADD: 701 BELVEDERE RD.
 CONT: TORNADO ROOFING AND CONTRACTING, INC.
 TEL: 954-968-8155
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JAN. 06TH/2021
 ACTION: DENIED
  
 1) SHEET T-1 THE COVERSHEET/ CODE RESEARCH:
 1A) COMPLIED.
 1B) SEMI-COMPLIED. FOR THE 2ND REVIEW THE CONSTRUCTION
 TYPE INDICATES AS IIIA PROTECTED , NON-SPRINKLERED.
 TABLE 601 REQUIRES ALL STRUCTURAL ELEMENTS ARE TO BE
 ONE HOUR PROTECTED WITH THE EXCEPTION OF THE EXTERIOR
 BEARING WALLS. PLEASE PROVIDE HOW ALL OF THE STRUCTURAL
 ELEMENTS ARE 1 HOUR PROTECTED AND THE EXTERIOR BEARING
 WALLS HAVE A 2 HOUR FIRE RATING. NOTE A III-B
 CONSTRUCTION UNPROTECTED ONLY HAS TO SHOW A 1 HR. FIRE
 RATING ON THE EXTERIOR BEARING WALLS. THIS BUILDING
 QUALIFIES AS A V-B CONSTRUCTION ALLOWING 9,000 SQ. FT.
 FOR A MERCANTILE OCCUPANCY NON-SPRINKLERED.
  
 1ST ROUND OF COMMENTS. CONSTRUCTION TYPE STATES IIIA
 UNPROTECTED: FULLY SPRINKLERED. PLEASE REFER TO THE
 2017 FBC-B TABLE 601. IN ALL 5 BUILDING CATEGORY TYPES
 THE TYPE (A) BUILDING HAS AT LEAST A 1-HOUR PROTECTION
 SO THE BUILDING IS PROTECTED. THE PLANS ALSO STATE THIS
 BUILDING IS FIRE SPRINKLERED BUT NO FIRE SPRINKLER PLAN
 WAS INCLUDED IN THE SET OF DOCUMENTS? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) COMPLIED.
 2) COMPLIED.
 3) COMPLIED.
  
 4A) SHEET M-3 SHOW A ROOF TOP CONDENSING UNIT ON A
 STAND. THIS SAME DETAIL INDICATES A NOA 18-0828.09.
 PLEASE SUBMIT THIS PRODUCT APPROVAL. 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS/ CURBS/ EXHAUST FANS
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 4C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.FBC-B-1609.6.4.4.1 COMPONENTS
 AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR
 CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES
 COMPONENTS AND ATTACHMENTS.
  
 4D) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 4E) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 5) SEMI- COMPLIED. WIND DESIGN IS GIVEN BUT NOT THE
 PRESSURES TO BE EXERTED ON THE ROOF TOP EQUIPMENT AND
 FOR THEIR SQUARE FOOT AREA PER SIDE, WORST CASE
 SCENARIO. SEE COMMENT 4E.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING... ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD. NOTE THE MIAMI-DADE NOA
 18-0719.07 FOR MECHANICAL UNIT TIE DOWN FOR GRADE AND
 ROOFTOP APPLICATIONS FOR AN EXPLANATION OF THE EXPOSURE
 CATEGORIES THAT ACCOMPANY THE VULT WIND SPEEDS USED IN
 THIS DOCUMENT, SEE SECTION 26.7 OF ASCE 7-10. PLEASE
 PROVIDE THIS INFORMATION. MOST PRODUCT APPROVALS ARE IN
 VASD NOT IN VULT, IF THE PRESSURES SHOWN ARE IN VULT
 WHEN REFERRED TO IN VASD THEY MAY NOT BE ADEQUATE.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By jwitmer Date 2020-11-19 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2020-11-19 Time 07:58 Sent To  
Notes
2020-11-19 09:58:50WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20101298
 ADD: 701 BELVEDERE RD.
 CONT: TORNADO ROOFING AND CONTRACTING, INC.
 TEL: 954-968-8155
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 19TH/2020
 ACTION: DENIED
  
 1) SHEET T-1 THE COVERSHEET/ CODE RESEARCH:
 1A) THE PLANS STATE THE GOVERNING CODES ARE THE 2010
 EDITION OF THE FLORIDA BUILDING CODE AND EXISTING
 BUILDING CODE (CHAPTER 3401.1). PLEASE NOTE THE 6TH
 EDITION (2017) OF THE FLORIDA BUILDING CODE WENT INTO
 EFFECT ON DEC. 31,2017. PLEASE UPDATE THE CODE EDITION
 AND YEAR.
  
 1B) CONSTRUCTION TYPE STATES IIIA UNPROTECTED: FULLY
 SPRINKLERED. PLEASE REFER TO THE 2017 FBC-B TABLE 601.
 IN ALL 5 BUILDING CATEGORY TYPES THE TYPE (A) BUILDING
 HAS AT LEAST A 1-HOUR PROTECTION SO THE BUILDING IS
 PROTECTED. THE PLANS ALSO STATE THIS BUILDING IS FIRE
 SPRINKLERED BUT NO FIRE SPRINKLER PLAN WAS INCLUDED IN
 THE SET OF DOCUMENTS? 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 1C) THE DESIGNER OF RECORD INDICATES UNDER THE EXISTING
 BUILDING CODE THIS BUILDING IS A LEVEL III ALTERATION.
 PLEASE REVIEW THE DEFINITION FOR LEVEL III ALTERATIONS.
 505.1 OF THE EXIST. BLDG. CODE. SCOPE. LEVEL 3
 ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS 50 PER
 CENT OF THE BUILDING AREA. 2017 EXIST. BUILDING CODE
 907.4.2. SUBSTANTIAL STRUCTURAL ALTERATIONS IS WHERE 30
 PERCENT OF THE TOTAL FLOOR AND ROOF AREA OF THE
 BUILDING HAS BEEN OR PROPOSED TO BE INVOLVED IN
 STRUCTURAL ALTERATIONS WITHIN A 5 YEAR PERIOD. THIS IS
 A LEVEL II ALTERATION.
  
 2) SHEET A-3 DETAIL 9 SHOWS BUILT-IN BASE MILLWORK AT A
 HEIGHT OF 3-0 FEET FROM FINISH FLOOR TO THE TOP OF THE
 COUNTER. PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTIONS:
 902.1 .WORK SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 ADVISORY 902.1 GENERAL. EXAMPLES OF WORK SURFACES
 INCLUDE WRITING SURFACES, STUDY CARRELS, STUDENT
 LABORATORY STATIONS, BABY CHANGING AND OTHER TABLES OR
 FIXTURES FOR PERSONAL GROOMING, COUPON COUNTERS, AND
 WHERE COVERED BY THE ADA SCOPING PROVISIONS, EMPLOYEE
 WORKSTATIONS.
 CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK
 WRITING SURFACES. WHERE PROVIDED, CHECK WRITING
 SURFACES SHALL COMPLY WITH 902.3. 902.3HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION.
 UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE
 SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL
 APPROACH TO AN ELEMENT.
  
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTERTOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTERTOP.
  
 3) SHEETS D-1 AND A-2 SHOW THE REMOVAL OF ONE EXTERIOR
 DOOR AND CLOSING UP THE OPENING, BUT THERE ARE NO
 DETAILS FOR THE BLOCKING UP OF THE OPENING AND TIE INS
 REQUIRED FOR THE BLOCKWORK. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED. 2017 FBC-B 2103.4 METAL
 REINFORCEMENT AND ACCESSORIES.
  
 4A) SHEET M-3 SHOW A ROOF TOP CONDENSING UNIT ON A
 STAND. THIS SAME DETAIL INDICATES A NOA 18-0828.09.
 PLEASE SUBMIT THIS PRODUCT APPROVAL. 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS/ CURBS/ EXHAUST FANS
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 4C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.FBC-B-1609.6.4.4.1 COMPONENTS
 AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR
 CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES
 COMPONENTS AND ATTACHMENTS.
  
 4D) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 4E) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 5) NO WIND DESIGN CRITERIA WERE FOUND IN EITHER THE
 ARCHITECTURAL NOR MECHANICAL SHEETS FOR THE NEW ROOF
 TOP EQUIPMENT,
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 5.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING... ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-01-15 Cont ID  
Sent By equinone Date 2021-01-15 Time 15:17 Rev Time 0.00
Received By equinone Date 2021-01-15 Time 15:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-10 Cont ID  
Sent By equinone Date 2020-12-10 Time 09:28 Rev Time 0.00
Received By equinone Date 2020-12-10 Time 09:28 Sent To  
Notes
2020-12-10 09:52:49CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) IT SEEMS THAT ONLY HALF OF THE PANEL SCHEDULE IS
 SHOWN ON DRAWINGS. FBC 107
 2) ALL RECEPTACLES IN FOOD PREPARATION AREAS MUST BE
 GFCI PROTECTED NEC 210.8(B)
 3) PLEASE SHOW CIRCUITS FOR AHU 1 AND AHU 2 ON POWER
 LAYOUT AND PANEL SCHEDULE FBC 107
 4) EXISTING GROUNDING ELECTRODE CONDUCTOR SHOWN IS SIZE
 #2 CU. PLEASE SPECIFY TYPE OF GROUNDING ELECTRODE
 SYSTEM USED TO DETERMINE COMPLIANCE WITH NEC 250-66
 5) GFCI, WP RECEPTACLES REQUIRED FOR ALL AC, CU, AHU
 UNITS AS PER NEC 210-63
 6) PLEASE SUBMIT LOAD CALCULATION FOR EXISTING PANEL A
 FBC 107
  
 END OF COMMENTS.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-12-30 Cont ID  
Sent By pleduc Date 2020-12-30 Time   Rev Time 0.00
Received By pleduc Date 2020-12-30 Time 09:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-11-17 Cont ID  
Sent By pleduc Date 2020-11-17 Time   Rev Time 0.00
Received By pleduc Date 2020-11-17 Time 16:41 Sent To  
Notes
2020-11-17 16:41:40FIRE PROVISO:
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-05-10 Cont ID  
Sent By ccole Date 2021-05-10 Time 13:12 Rev Time 0.00
Received By ccole Date 2021-05-10 Time 09:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-02-24 Cont ID  
Sent By ccole Date 2021-02-24 Time 11:15 Rev Time 0.00
Received By ccole Date 2021-02-24 Time 07:35 Sent To  
Notes
2021-02-24 11:16:302ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 20101298
 2/242021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW LISTED BELOW WERE NOIT ADDRESSED- PLEASE COMPLY.
  
 1) SHEETS P3 & A2: THE EQUIPMENT LIST ON A2 SHOWS GAS
 STOVE, DOUBLE FRYER AND FLAT GRILL. P3 SHOWS A COOKTOP,
 FRYER AND GRIDDLE. PLEASE SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE APPLIANCES SHOWING GAS BTUH
 LOADS AND INPUT PRESSURES- SECTION 305.1 FBC FG.
  
 2) P3: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR
 THE COOKING APPLIANCES AND PROVIDE CALCULATIONS-
 SECTION 304.1 FBC FG.
  
 3) P3: SHOW THE LOCATION OF THE AUTOMATIC GAS SHUTOFF
 VALVE WHICH IS REQUIRED TO BE CONNECTED TO THE HOOD
 FIRE SUPPRESSION SYSTEM- SECTION 10.4.1 NFPA 96.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-01-15 Cont ID  
Sent By ccole Date 2021-01-15 Time 11:49 Rev Time 0.00
Received By ccole Date 2021-01-15 Time 08:11 Sent To  
Notes
2021-01-15 11:51:231ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20101298
 1/15/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P3 & A2: THE EQUIPMENT LIST ON A2 SHOWS GAS
 STOVE, DOUBLE FRYER AND FLAT GRILL. P3 SHOWS A COOKTOP,
 FRYER AND GRIDDLE. PLEASE SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE APPLIANCES SHOWING GAS BTUH
 LOADS AND INPUT PRESSURES- SECTION 305.1 FBC FG.
  
 2) P3: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR
 THE COOKING APPLIANCES AND PROVIDE CALCULATIONS-
 SECTION 304.1 FBC FG.
  
 3) P3: SHOW THE LOCATION OF THE AUTOMATIC GAS SHUTOFF
 VALVE WHICH IS REQUIRED TO BE CONNECTED TO THE HOOD
 FIRE SUPPRESSION SYSTEM- SECTION 10.4.1 NFPA 96.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-11 Cont ID  
Sent By jwitmer Date 2021-05-11 Time 14:43 Rev Time 0.00
Received By jwitmer Date 2021-04-21 Time 09:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-02-24 Time   Rev Time 0.00
Received By ccarvaja Date 2021-02-04 Time 06:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-15 Cont ID  
Sent By equinone Date 2021-01-15 Time 15:19 Rev Time 0.00
Received By equinone Date 2020-12-29 Time 15:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-10 Cont ID  
Sent By equinone Date 2020-12-10 Time 09:53 Rev Time 0.00
Received By equinone Date 2020-11-10 Time 13:56 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2021-05-11 Cont ID  
Sent By jwitmer Date 2021-05-11 Time 14:13 Rev Time 0.00
Received By jwitmer Date 2021-05-11 Time 14:02 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By jwitmer Date 2020-11-19 Time 10:00 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-11-19 10:00:05IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-05-10 Cont ID  
Sent By medwards Date 2021-05-10 Time 12:55 Rev Time 0.00
Received By medwards Date 2021-05-10 Time 12:55 Sent To  
Notes
2021-05-10 12:55:23THE HOOD AND GREASE DUCT MUST BE PERMITTED SEPARATELY.
 NO REVIEW HAS BEEN DONE ON THIS SYSTEM. NO
 REFRIGERATION HAS BEEN REVIEWED ON THIS PROJECT. A
 SEPARATE PERMIT AND REVIEW SHALL BE DONE OF
 REFRIGERATION.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-02-23 Cont ID  
Sent By medwards Date 2021-02-23 Time 12:58 Rev Time 0.00
Received By medwards Date 2021-02-23 Time 12:40 Sent To  
Notes
2021-02-23 12:58:05THE HOOD AND GREASE DUCT MUST BE PERMITTED SEPARATELY.
 NO REVIEW HAS BEEN DONE ON THIS SYSTEM. NO
 REFRIGERATION HAS BEEN REVIEWED ON THIS PROJECT. A
 SEPARATE PERMIT AND REVIEW SHALL BE DONE OF
 REFRIGERATION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-01-12 Cont ID  
Sent By medwards Date 2021-01-12 Time 06:37 Rev Time 0.00
Received By medwards Date 2021-01-12 Time 06:35 Sent To  
Notes
2021-01-12 06:37:17PLEASE ADDRESS TO NOTES 3 AND 4 BELOW FROM THE FIRST
 REVIEW.
  
 3) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 4) PLEASE PROVIDE SPECIFICATIONS FOR THE AHU?S FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-05 Cont ID  
Sent By medwards Date 2020-12-05 Time 09:55 Rev Time 0.00
Received By medwards Date 2020-12-05 Time 09:15 Sent To  
Notes
2020-12-05 09:55:251ST REVIEW FBC-2017 MECHANICAL
 PERMIT -20101298
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE HOOD SHALL BE PERMITTED AND REVIEWED SEPARATELY.
  
 2) ALL REFRIGERATION WORK SHALL BE PERMITTED AND
 REVIEWED SEPARATELY.
  
 3) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 4) PLEASE PROVIDE SPECIFICATIONS FOR THE AHU?S FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-05-11 Cont ID  
Sent By ccole Date 2021-05-10 Time 07:05 Rev Time 0.00
Received By ccole Date 2021-05-10 Time 09:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-02-24 Cont ID  
Sent By ccole Date 2021-02-24 Time 11:12 Rev Time 0.00
Received By ccole Date 2021-02-24 Time 07:35 Sent To  
Notes
2021-02-24 11:13:123RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20101298
 2/23/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 REMAINING FAILED COMMENTS FROM THE 1ST AND 2ND REVIEW
 ARE LISTED BELOW. PLEASE NOTE THE REQUESTED RESPONSE
 NARRATIVE FROM THE DESIGN PROFESSIONALS WHICH HELPS
 EXPEDITE THE REVIEW PROCESS WAS NOT SUBMITTED.
  
 1) FAILED. SHEET P1: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDE NUMBER OF FIXTURES. PLEASE NOTE THAT DRINKING
 FOUNTAINS ARE REQUIRED FIXTURES FOR MERCANTILE
 OCCUPANCIES. THE EXCEPTION ALLOWED FOR RESTAURANTS
 SERVING DRINKING WATER TO CUSTOMERS UNDER SECTION 410.4
 DOES NOT APPLY. THE DRINKING FOUNTAINS SHALL BE
 ACCESSIBLE IN COMPLIANCE WITH SECTIONS 211.2, & 602.1-
 602.6 FBC ACC. THE ARCHITECT OF RECORD INDICATES AN
 OCCUPANT LOAD OF 33 ON SHEET A2 WHICH CONTRADICTS HIS
 LOAD OF 15 SHOWN IN THE FIXTURE CALCULATIONS. PLEASE
 PROVIDE THE REQUIRED DRINKING FOUNTAINS- SEE SECTION
 410.2 FBC P.
  
 2) FAILED. P1: SHOW THE LOCATIONS OF THE DRINKING
 FOUNTAINS AND REVISE THE PLUMBING PIPING PLANS AND
 ISOMETRIC DRAWINGS ACCORDINGLY- SECTION 107.3.5.3 WPB.
 SEE FAILED COMMENT #1 ABOVE.
  
 3) FAILED. PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND
 602 FBC ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND
 TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION
 PATH. SEE FAILED COMMENT #1 ABOVE.
  
 5) FAILED. P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE
 OF THE PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE.
 PLEASE PROVIDE CLEAR AND COMPLETE SANITARY AND WATER
 RISERS- SECTIONS 107.2.1 & 107.3.5.3 WPB. PLEASE NOTE
 THAT THE CHIEF PLUMBING INSPECTOR TIMOTHY LARGE IS NOW
 REQUIRING ALL MOP SINKS IN RESTAURANTS, OR OTHER
 FACILITIES WITH COOKING APPLIANCES, TO DRAIN INTO A
 GREASE INTERCEPTOR. THE HAND SINK SHALL DRAIN INTO THE
 SANITARY AND NOT INTO THE GREASE INTERCEPTOR. PLEASE
 DISREGARD PREVIOUS COMMENT AND CORRECT THE PLUMBING
 PLANS. IF YOU HAVE QUESTIONS PLEASE CONTACT MR. LARGE
 AT [email protected], 561-805-6692.
  
 10) FAILED. P1 & P2: PLEASE PROVIDE A WATER RISER AND A
 WATER DISTRIBUTION LAYOUT PLAN. CONNECTION TO THE SODA
 FILTERING SYSTEM NOT SHOWN- SEE SCHEMATIC ON P-2.
  
 10B) FAILED. SHOW THE SOURCE OF THE HOT WATER TO THE
 NEW AND EXISTING FIXTURES AND THE TEMPERATURE OF THE
 WATER- SECTION 607.1. PLEASE LABEL THE WATER HEATER AS
 NEW OR EXISTING ON THE PLANS.
 FOR NEW WATER HEATER INSTALLATIONS: PROVIDE AN
 EQUIPMENT SCHEDULE ON THE PLAN INDICATING MAKE, MODEL,
 GALLON SIZE, AND EFFICIENCY RATING. PLEASE NOTE THAT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUAL
 SHALL BE ONSITE AT TIME OF INSPECTION. PROVIDE PLUMBING
 PIPING DETAILS- COLD WATER FEED, SHUTOFF VALVE, CHECK
 VALVE, THERMAL EXPANSION TANK, RECIRCULATION PUMP,
 RELIEF VALVE, RELIEF VALVE DISCHARGE PIPING, DRAIN PAN,
 DRAIN PAN LINE, HW PIPE INSULATION- SEE SECTIONS 502 &
 607 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-01-15 Cont ID  
Sent By ccole Date 2021-01-15 Time 11:55 Rev Time 0.00
Received By ccole Date 2021-01-15 Time 07:21 Sent To  
Notes
2021-01-15 11:55:502ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20101298
 1/15/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE
 MARKED AS PASSED OR FAILED. NOTES HAVE BEEN ADDED TO
 FAILED COMMENTS. PLEASE NOTE THE REQUESTED RESPONSE
 NARRATIVE FROM THE DESIGN PROFESSIONALS WHICH HELPS
 EXPEDITE THE REVIEW PROCESS WAS NOT SUBMITTED. IT
 APPEARS THAT CORRECTED PLUMBING PLANS BASED ON 1ST
 REVIEW COMMENTS WERE NOT PROVIDED.
  
 1) FAILED. SHEET P1: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDE NUMBER OF FIXTURES. PLEASE NOTE THAT DRINKING
 FOUNTAINS ARE REQUIRED FIXTURES FOR MERCANTILE
 OCCUPANCIES. THE EXCEPTION ALLOWED FOR RESTAURANTS
 SERVING DRINKING WATER TO CUSTOMERS UNDER SECTION 410.4
 DOES NOT APPLY. THE DRINKING FOUNTAINS SHALL BE
 ACCESSIBLE IN COMPLIANCE WITH SECTIONS 211.2, & 602.1-
 602.6 FBC ACC.
  
 2) FAILED. P1: SHOW THE LOCATIONS OF THE DRINKING
 FOUNTAINS AND REVISE THE PLUMBING PIPING PLANS AND
 ISOMETRIC DRAWINGS ACCORDINGLY- SECTION 107.3.5.3 WPB.
  
 3) FAILED. PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND
 602 FBC ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND
 TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION
 PATH.
  
 4) PASSED. GAS ISOMETRIC SUBMITTED WILL BE REVIEWED
 UNDER THIS PERMIT- A GAS SUB-PERMIT WILL BE REQUIRED.
 GREASE INTERCEPTOR INFORMATION PROVIDED WILL BE
 REVIEWED, HOWEVER A SEPARATE PRIMARY PERMIT IS REQUIRED
 FOR INSTALLATION. PLEASE NOTE THAT SUB-PERMITS
 SUBMITTED WITH MAIN PERMITS ARE ?NO-FEE?. A FEE WILL BE
 CHARGED FOR SUB-PERMITS APPLIED FOR AFTER MAIN PERMIT
 ISSUANCE. FINAL APPROVAL OF THE GAS PLANS HOWEVER WILL
 NOT REQUIRE SUBMITTAL OF THE APPLICATION. P1: PLEASE
 NOTE THAT SEPARATE PERMITS AND PLAN SUBMITTALS ARE
 REQUIRED FOR THE GAS PIPING AND GREASE INTERCEPTOR
 INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB. A COMPLETE
 REVIEW OF THESE SYSTEMS HAS NOT BEEN PERFORMED AT THIS
 TIME.
  
 5) FAILED. P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE
 OF THE PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE.
 PLEASE PROVIDE CLEAR AND COMPLETE SANITARY AND WATER
 RISERS- SECTIONS 107.2.1 & 107.3.5.3 WPB. THE CORRECTED
 RISER SHALL IDENTIFY THE FIXTURES AND SHOW THE TYPE OF
 DRAIN CONNECTIONS- DIRECT OR INDIRECT, AND ALSO SHOW
 POINTS OF CONNECTIONS TO THE EXISTING SANITARY AND VENT
 SYSTEMS. A MINIMUM OF ONE VENT FOR THE BUILDING DRAIN
 SHALL EXTEND TO THE OUTDOORS- SECTION 904.1 FBC P.
  
 6) FAILED. P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC
 P THE MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT
 INTO THE GREASE WASTE LINE. PLEASE REVISE THE PLANS,
 SCHEDULE, AND CALCULATIONS ACCORDINGLY.
  
 7) FAILED. P1: PLEASE PLACE A NOTE TO REQUIRE A COVER
 FOR THE MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER
 AND OTHER FLUIDS AND WASTES FROM DRAINING INTO THE CITY
 SANITARY SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES.
  
 8) FAILED. A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN
 THE DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA
 DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND
 PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P.
 PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE
 RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR-
 SECTION 1003.3.1 FBC P.
  
 9) FAILED. D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT
 PROVIDE A MEANS FOR THE DRAIN LINES FROM THE HAND SINK
 AND FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE
 WASTE AND SANITARY DRAIN LINES. PLEASE PROVIDE THE SLAB
 CUTS AND SLAB REPAIR DETAILS- SECTION 107.2.1 WPB.
 PLEASE REVIEW THE PLUMBING PLANS AND REVISE D-1 TO SHOW
 THE SLAB CUTS RELATIVE TO THE UNDERSLAB DRAIN LINES.
  
 10) P1 & P2: FAILED 10A-F. PLEASE PROVIDE A WATER RISER
 AND A WATER DISTRIBUTION LAYOUT PLAN:
  
 A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER
 DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3
 FBC P.
  
 B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND
 EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER-
 SECTION 607.1.
  
 C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND
 EQUIPMENT- SECTION 606.2.
  
 D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS-
 SECTION 604.9.
  
 E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS
 TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE
 AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1
 FBC P.
  
 F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE
 LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2.
  
 11) FAILED. P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR
 DRAINS AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN
 THE ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P.
  
 12) FAILED. P1 & P2: PROVIDE A COMPLETE PLUMBING
 FIXTURE SCHEDULE THAT INCLUDES THE MOP SINK,
 3-COMPARTMENT SINK, HAND SINK, DRINKING FOUNTAIN,
 FAUCETS, FLOOR DRAINS, FLOOR SINKS- SECTION 107.2.1
 WPB.
  
 13) FAILED. PROVIDE A PLUMBING DEVICE SCHEDULE
 INCLUDING THE WATER HAMMER ARRESTORS, MIXING VALVE,
 BACKFLOW PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1
 WPB.
  
 14) PASSED. PROVIDE A PLUMBING SUB-PERMIT APPLICATION-
 SECTION 105.1 WPB. PLEASE NOTE THAT SUB-PERMITS
 SUBMITTED WITH MAIN PERMITS ARE "NO-FEE". A FEE WILL BE
 CHARGED FOR SUB-PERMITS APPLIED FOR AFTER MAIN PERMIT
 ISSUANCE. FINAL APPROVAL OF THE PLUMBING PLANS HOWEVER
 WILL NOT REQUIRE SUBMITTAL OF THE APPLICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-09 Cont ID  
Sent By ccole Date 2020-12-09 Time 11:55 Rev Time 0.00
Received By ccole Date 2020-12-09 Time 08:27 Sent To  
Notes
2020-12-09 11:56:421ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20101298
 12/9/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDE NUMBER OF
 FIXTURES. PLEASE NOTE THAT DRINKING FOUNTAINS ARE
 REQUIRED FIXTURES FOR MERCANTILE OCCUPANCIES. THE
 EXCEPTION ALLOWED FOR RESTAURANTS SERVING DRINKING
 WATER TO CUSTOMERS UNDER SECTION 410.4 DOES NOT APPLY.
 THE DRINKING FOUNTAINS SHALL BE ACCESSIBLE IN
 COMPLIANCE WITH SECTIONS 211.2, & 602.1- 602.6 FBC ACC.
  
 2) P1: SHOW THE LOCATIONS OF THE DRINKING FOUNTAINS AND
 REVISE THE PLUMBING PIPING PLANS AND ISOMETRIC DRAWINGS
 ACCORDINGLY- SECTION 107.3.5.3 WPB.
  
 3) PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS
 SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND 602 FBC
 ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION
 PATH.
  
 4) P1: PLEASE NOTE THAT SEPARATE PERMITS AND PLAN
 SUBMITTALS ARE REQUIRED FOR THE GAS PIPING AND GREASE
 INTERCEPTOR INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB.
 A COMPLETE REVIEW OF THESE SYSTEMS HAS NOT BEEN
 PERFORMED AT THIS TIME.
  
 5) P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE OF THE
 PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. PLEASE
 PROVIDE CLEAR AND COMPLETE SANITARY AND WATER RISERS-
 SECTIONS 107.2.1 & 107.3.5.3 WPB.
  
 6) P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE
 MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT INTO THE
 GREASE WASTE LINE. PLEASE REVISE THE PLANS, SCHEDULE,
 AND CALCULATIONS ACCORDINGLY.
  
 7) P1: PLEASE PLACE A NOTE TO REQUIRE A COVER FOR THE
 MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER AND OTHER
 FLUIDS AND WASTES FROM DRAINING INTO THE CITY SANITARY
 SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES.
  
 8) A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN THE
 DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA
 DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND
 PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P.
 PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE
 RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR-
 SECTION 1003.3.1 FBC P.
  
 9) D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT PROVIDE
 A MEANS FOR THE DRAIN LINES FROM THE HAND SINK AND
 FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE
 WASTE AND SANITARY DRAIN LINES. PLEASE PROVIDE THE SLAB
 CUTS AND SLAB REPAIR DETAILS- SECTION 107.2.1 WPB.
  
 10) P1 & P2: PLEASE PROVIDE A WATER RISER AND A WATER
 DISTRIBUTION LAYOUT PLAN:
  
 A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER
 DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3
 FBC P.
  
 B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND
 EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER-
 SECTION 607.1.
  
 C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND
 EQUIPMENT- SECTION 606.2.
  
 D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS-
 SECTION 604.9.
  
 E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS
 TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE
 AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1
 FBC P.
  
 F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE
 LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2.
  
 11) P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR DRAINS
 AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN THE
 ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P.
  
 12) P1 & P2: PROVIDE A COMPLETE PLUMBING FIXTURE
 SCHEDULE THAT INCLUDES THE MOP SINK, 3-COMPARTMENT
 SINK, HAND SINK, DRINKING FOUNTAIN, FAUCETS, FLOOR
 DRAINS, FLOOR SINKS, DOME DRAIN- SECTION 107.2.1 WPB.
  
 13) PROVIDE A PLUMBING DEVICE SCHEDULE INCLUDING THE
 WATER HAMMER ARRESTORS, MIXING VALVE, BACKFLOW
 PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1 WPB.
  
 14) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2020-12-09 11:56:201ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20101298
 12/9/2020
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
 1) SHEET P1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDE NUMBER OF
 FIXTURES. PLEASE NOTE THAT DRINKING FOUNTAINS ARE
 REQUIRED FIXTURES FOR MERCANTILE OCCUPANCIES. THE
 EXCEPTION ALLOWED FOR RESTAURANTS SERVING DRINKING
 WATER TO CUSTOMERS UNDER SECTION 410.4 DOES NOT APPLY.
 THE DRINKING FOUNTAINS SHALL BE ACCESSIBLE IN
 COMPLIANCE WITH SECTIONS 211.2, & 602.1- 602.6 FBC ACC.
 2) P1: SHOW THE LOCATIONS OF THE DRINKING FOUNTAINS AND
 REVISE THE PLUMBING PIPING PLANS AND ISOMETRIC DRAWINGS
 ACCORDINGLY- SECTION 107.3.5.3 WPB.
 3) PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS
 SHOWING COMPLIANCE WITH SECTIONS 306, 307, AND 602 FBC
 ACC INCLUDING ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 INDICATE HOW THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2- PROTRUDING OBJECTS INTO THE CIRCULATION
 PATH.
 4) P1: PLEASE NOTE THAT SEPARATE PERMITS AND PLAN
 SUBMITTALS ARE REQUIRED FOR THE GAS PIPING AND GREASE
 INTERCEPTOR INSTALLATIONS- SECTION 105.1 & 107.2.1 WPB.
 A COMPLETE REVIEW OF THESE SYSTEMS HAS NOT BEEN
 PERFORMED AT THIS TIME.
 5) P1: THE ISOMETRIC DRAWINGS AT THE LEFT SIDE OF THE
 PLAN SHEET APPEAR TO BE CUT OFF AND INCOMPLETE. PLEASE
 PROVIDE CLEAR AND COMPLETE SANITARY AND WATER RISERS-
 SECTIONS 107.2.1 & 107.3.5.3 WPB.
 6) P1: IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE
 MOP SINK SHALL DRAIN INTO THE SANITARY AND NOT INTO THE
 GREASE WASTE LINE. PLEASE REVISE THE PLANS, SCHEDULE,
 AND CALCULATIONS ACCORDINGLY.
 7) P1: PLEASE PLACE A NOTE TO REQUIRE A COVER FOR THE
 MOP SINK WHEN NOT IN USE TO PREVENT RAINWATER AND OTHER
 FLUIDS AND WASTES FROM DRAINING INTO THE CITY SANITARY
 SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES.
 8) A2, P1, & P2: FLOOR SINKS ARE SPECIFIED IN THE
 DETAILS TO RECEIVE INDIRECT DRAINAGE FROM THE SODA
 DISPENSER AND ICE MACHINE. PLEASE ADD THE RECEPTORS AND
 PLUMBING PIPING TO THE DRAWINGS- SECTION 802.1 FBC P.
 PLEASE NOTE THAT CLEAR WATER WASTES FROM THESE
 RECEPTORS SHALL NOT DRAIN INTO THE GREASE INTERCEPTOR-
 SECTION 1003.3.1 FBC P.
 9) D-1: IT APPEARS THE SLAB CUT SHOWN WILL NOT PROVIDE
 A MEANS FOR THE DRAIN LINES FROM THE HAND SINK AND
 FLOOR SINKS IN THE KITCHEN TO CONNECT TO THE GREASE
 WASTE AND SANITARY DRAIN LINES- SECTION 107.2.1 WPB.
 10) P1 & P2: PLEASE PROVIDE A WATER RISER AND A WATER
 DISTRIBUTION LAYOUT PLAN:
 A) SHOW THE POINTS OF CONNECTIONS TO THE EXISTING WATER
 DISTRIBUTION LINES OR MAIN SERVICE LINE- SECTION 604.3
 FBC P.
 B) SHOW THE SOURCE OF THE HOT WATER TO THE NEW AND
 EXISTING FIXTURES AND THE TEMPERATURE OF THE WATER-
 SECTION 607.1.
 C) SHOW LOCATIONS OF SHUT OFF VALVES TO FIXTURES AND
 EQUIPMENT- SECTION 606.2.
 D) SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS-
 SECTION 604.9.
 E) SHOW THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS
 TO THE ICE MAKER, WATER FILTER, SODA DISPENSER, COFFEE
 AND CAPPUCCINO MACHINES- SECTION 608.3 AND TABLE 608.1
 FBC P.
 F) SHOW HOW TEMPERED WATER IS BEING PROVIDED TO THE
 LAVATORY IN THE RESTROOM- SECTIONS 416.5 & 607.1.2.
 11) P1 & P2: PROVIDE TRAP PRIMERS FOR THE FLOOR DRAINS
 AND FLOOR SINKS AND SHOW LOCATIONS AND PIPING IN THE
 ISOMETRIC DRAWING- SECTION 1002.4.1 FBC P.
 12) P1 & P2: PROVIDE A COMPLETE PLUMBING FIXTURE
 SCHEDULE THAT INCLUDES THE MOP SINK, 3-COMPARTMENT
 SINK, HAND SINK, DRINKING FOUNTAIN, FAUCETS, FLOOR
 DRAINS, FLOOR SINKS, DOME DRAIN- SECTION 107.2.1 WPB.
 13) PROVIDE A PLUMBING DEVICE SCHEDULE INCLUDING THE
 WATER HAMMER ARRESTORS, MIXING VALVE, BACKFLOW
 PREVENTERS, AND TRAP PRIMERS- SECTION 107.2.1 WPB.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-05-11 Cont ID  
Sent By jwitmer Date 2021-05-11 Time 14:31 Rev Time 0.00
Received By jwitmer Date 2021-05-11 Time 14:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-02-24 Cont ID  
Sent By ccole Date 2021-02-24 Time 11:20 Rev Time 0.00
Received By ccole Date 2021-02-24 Time 11:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-01-15 Cont ID  
Sent By ccole Date 2021-01-15 Time 12:04 Rev Time 0.00
Received By ccole Date 2021-01-15 Time 11:58 Sent To  
Notes
2021-01-15 12:13:522ND SIGNATURE REVIEW
 1/15/21
  
 1) NEW SHEETS T1, A1, A3, E1, M1, M2, M3 DO NOT BEAR
 THE DIGITAL SIGNATURE AND SEAL OF THE ARCHITECT OF
 RECORD AS REQUIRED BY FL. STATUTE 481.221 AND SECTION
 61G1 16.005 FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-05 Cont ID  
Sent By medwards Date 2020-12-05 Time 09:59 Rev Time 0.00
Received By medwards Date 2020-12-05 Time 09:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-12-31 Cont ID  
Sent By llouie Date 2020-12-31 Time   Rev Time 0.00
Received By llouie Date 2020-12-31 Time   Sent To  
Notes
2020-12-31 09:18:41ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) SCOPE OF WORK IS FOR INTERIOR REMODEL ONLY. ANY
 WORK DONE TO THE EXTERIOR/SITE WILL REQUIRE SEPARATE
 BUILDING PERMIT(S).
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-11-18 Cont ID  
Sent By llouie Date 2020-11-18 Time   Rev Time  
Received By llouie Date 2020-11-18 Time   Sent To  
Notes
2020-11-18 12:18:51** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE A SIGNED AND SEALED SURVEY OF THE PROPERTY.
  
 2.) THERE SEEMS TO BE EXTERIOR SITE IMPROVEMENTS SHOWN
 IN THE PLANS. PLEASE CLARIFY. A SITE PLAN SHOWING THE
 SETBACK DISTANCE FROM ANY NEW STRUCTURE/IMPROVEMENT
 WILL BE REQUIRED IF EXTERIOR SITE IMPROVEMENTS ARE
 MADE.
  
  
 NOTES:
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * DO NOT HESITATE TO CONTACT LINDA LOUIE @ (561)
 822-1458 IF THERE ARE ANY QUESTIONS.
  
 * ZONE: NC
  