| 2020-11-23 09:40:10 | PLAN REVIEW / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NEC 2014 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1.STATE TYPE OF FLOORING TO BE INSTALLED |
| | |
| | 2. STATE SQUARE FOOTAGE OF FLOORING TO BE INSTALLED. |
| | |
| | 3. PROVIDE THE REQUIRED ASTM TEST REPORT FOR THE |
| | UNDERLAYMENT TO BE USED. |
| | |
| | NOTE: ASTM TEST REPORTS ARE REQUIRED - MANUFACTURER |
| | SPEC SHEETS ARE NOT ACCEPTABLE DUE TO DISCREPANCIES |
| | BETWEEN SPEC SHEETS/BROCHURES AND TEST REPORTS FOR SOME |
| | MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER |
| | SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | NOTE: ONCE TYPE OF FLOORING HAS BEEN IDENTIFIED AND |
| | UNDERLAYMENT HAS BEEN SELECTED, WE MAY BE ABLE TO |
| | ASSIST WITH THE REQUIRED ASTM TEST REPORTS FROM OUR |
| | LIBRARY OF FLOORING UNDERLAYMENTS. |
| | |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED FOR ALL FLOORING |
| | SUBMITTALS PER FBC CHPT. 12 AND CHPT. 6: |
| | |
| | 1. TOTAL SQUARE FOOTAGE OF NEW FLOORING. |
| | 2. TYPE OF PROPOSED FLOORING |
| | (TILE/MARBLE/LAMINATE/WOOD/OTHER). |
| | 3. STATED VALUE OF WORK. |
| | 4. EXISTING SITE CONDITIONS: |
| | A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN |
| | CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL) |
| | 6. PROPOSED UNDERLAYMENT. |
| | 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON |
| | EXISTING SITE CONDITIONS. |
| | 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S, |
| | E-84, E-90 & E-492. |
| | 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04 |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09 |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE |
| | AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT |
| | INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 |
| | IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 492. |
| | |
| | FBC 603.1 FLAME SPREAD |
| | FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 |
| | FBC 804.4.1 TEST REQUIREMENT. |
| | IN ALL OCCUPANCIES, INTERIOR FLOOR COVERING MATERIALS |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE DOC FF-1 |
| | ?PILL TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D2859 |
| | |
| | |