Plan Review Details - Permit 20101249
| Plan Review Stops For Permit 20101249 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-10-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-10-28 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-10-28 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2020-10-28 11:24:32 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
P |
Date |
2020-11-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-11-17 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-11-17 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-11-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-11-17 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-11-17 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-10-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-10-28 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-10-28 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2020-10-28 11:25:22 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT A COPY OF THE CONTRACT WITH THE SCOPE OF WORK | | | SPECIFIED. FBC 109.3 BUILDING PERMIT VALUATION. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 2) THE DRYWALL THAT IS BEING REPLACED ON THE CORRIDOR | | | WALLS, TENANT SEPARATION WALLS AND CEILINGS ARE PART OF | | | FIRE RATED ASSEMBLIES. PROVIDE SIGNED AND SEALED | | | DRAWINGS AND DETAILS FROM A FLORIDA LICENSED DESIGN | | | PROFESSIONAL. PROVIDE WALL AND CEILING SECTIONS WITH | | | THE LISTING DETAILS FOR THE FIRE RATED ASSEMBLY. FBC | | | 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. ALL | | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-11-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-11-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-11-16 |
Time |
16:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2020-11-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-11-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-11-04 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2020-11-04 13:11:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE EXISTING FIRE RATED WALLS THAT ARE BEING | | | REPLACED, HOWEVER, THERE ARE NO INDICATIONS OF A LISTED | | | RATED WALL CALL-OUT TO ENSURE PROPER CONSTRUCTION. | | | | | | PER NFPA 1 CH 8 | | | | | | 8.3.1.3 WALLS USED AS FIRE BARRIERS SHALL COMPLY WITH | | | CHAPTER 7 OF | | | NFPA 221, STANDARD FOR HIGH CHALLENGE FIRE WALLS, FIRE | | | WALLS, AND | | | FIRE BARRIER WALLS. THE NFPA 221 LIMITATION ON | | | PERCENTAGE WIDTH OF | | | OPENINGS SHALL NOT APPLY. | | | | | | 8.3.2 WALLS. | | | 8.3.2.1 THE FIRE-RESISTIVE MATERIALS, ASSEMBLIES, AND | | | SYSTEMS USED SHALL | | | BE LIMITED TO THOSE PERMITTED IN THIS CODE AND THIS | | | CHAPTER. | | | | | | 8.3.2.2 THE CONSTRUCTION MATERIALS AND DETAILS FOR | | | FIRE-RESISTIVE | | | ASSEMBLIES AND SYSTEMS FOR WALLS DESCRIBED SHALL COMPLY | | | WITH ALL | | | OTHER PROVISIONS OF THIS CODE, EXCEPT AS MODIFIED | | | HEREIN. | | | | | | NFPA 221 | | | | | | 4.3 FIRE RESISTANCE RATINGS | | | 4.3.1 THE FIRE RESISTANCE RATING OF ASSEMBLIES SHALL BE | | | DETERMINED | | | IN ACCORDANCE, ASTM E 119, STANDARD TEST METHODS FOR | | | FIRE | | | TESTS OF BUILDING CONSTRUCTION AND MATERIALS, OR | | | ANSI/UL 263, STANDARD | | | FOR FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS, | | | OR OTHER | | | APPROVED TEST METHODS OR ANALYTICAL METHODS IN | | | ACCORDANCE WITH | | | 4.3.2. | | | | | | PLEASE PROVIDE A DETAILED LISTED FIRE RATED WALL | | | CALL-OUT. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-11-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-11-17 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-11-10 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-11-05 |
|
|
Cont ID |
|
| Sent By |
ccarvaja |
Date |
2020-11-04 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
ccarvaja |
Date |
2020-10-28 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-11-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-11-17 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-11-17 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-10-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-10-28 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-10-28 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2020-10-28 11:27:06 | ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE | | | THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE | | | THE OPTION TO SUBMIT THE PAPER VERSION OF DRAWINGS WITH | | | THE ENGINEER?S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL. | | | AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN | | | SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | | DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | | SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15 | | | | | | | | | |
|
|
|