Plan Review Details - Permit 20101190
Plan Review Stops For Permit 20101190
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-12-29 Cont ID  
Sent By cpuell Date 2020-12-29 Time 09:32 Rev Time 0.00
Received By cpuell Date 2020-12-29 Time 09:32 Sent To  
Notes
2020-12-29 09:32:57GIVEN ADDRESS OF 3795@BROADWAY WHICH REFLECTS THE START
 OF THE PROJECT

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-10-26 Cont ID  
Sent By cpuell Date 2020-10-26 Time 12:16 Rev Time 0.00
Received By cpuell Date 2020-10-26 Time 12:16 Sent To  
Notes
2020-10-26 12:17:28PLEASE EMAIL A SITE PLAN SHOWING THE EXACT LOCATION
 WHERE THE WORK IS BEING DONE TO [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2021-08-24 Cont ID  
Sent By rmcphers Date 2021-08-24 Time 07:43 Rev Time 0.00
Received By rmcphers Date 2021-08-24 Time 07:43 Sent To  
Notes
2021-08-24 07:44:45DRAWINGS DO NOT INCLUDE THE POLE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-03 Cont ID  
Sent By rmcphers Date 2021-06-03 Time 08:30 Rev Time 0.00
Received By rmcphers Date 2021-06-03 Time 08:08 Sent To  
Notes
2021-06-03 08:30:15ANTENNA
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) WIND DESIGN SPEED SHOWN SHOULD BE 170MPH FOR A RISK
 CATEGORY II - SEE FBC WPB SECTION 120
 2) POLE AND ANTENNA DRAWINGS C2, C3, C4, C5 AND C6 ARE
 MISSING FROM THE DRAWINGS FOLDER IN PROJECTDOX SHOWING
 THE POLE FOUNDATION AND ANTENNA MOUNT.
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2021-10-28 Cont ID  
Sent By jleahy Date 2021-10-28 Time 13:08 Rev Time 0.00
Received By jleahy Date 2021-10-28 Time 13:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2021-08-26 Cont ID  
Sent By jleahy Date 2021-08-26 Time 11:41 Rev Time 0.00
Received By jleahy Date 2021-08-26 Time 11:39 Sent To  
Notes
2021-08-26 11:42:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SHOW LOCATION OF PANEL AND METER.
  
 IF INSIDE POLE PLEASE SHOW HOW INSTALLTION CONFORMS
 WITH 110.26 FOR WORKING CLEARANCES.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-05-14 Cont ID  
Sent By jleahy Date 2021-05-14 Time 15:12 Rev Time 0.00
Received By jleahy Date 2021-05-14 Time 15:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-04-05 Cont ID  
Sent By jleahy Date 2021-04-05 Time 11:12 Rev Time 0.00
Received By jleahy Date 2021-04-05 Time 10:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-01-06 Cont ID  
Sent By jleahy Date 2021-01-05 Time 14:33 Rev Time 0.00
Received By jleahy Date 2021-01-05 Time 12:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-12-02 Cont ID  
Sent By jleahy Date 2020-12-02 Time 14:27 Rev Time 0.00
Received By jleahy Date 2020-12-02 Time 14:27 Sent To  
Notes
2020-12-02 14:28:43NEED TO ADJUST VALUE OF WORK TO INCLUDE FEED FROM
 HANDHOLE TO NEW POLE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By jleahy Date 2020-11-02 Time 08:17 Rev Time 0.00
Received By jleahy Date 2020-11-02 Time 08:08 Sent To  
Notes
2020-11-02 08:20:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) FAULT CURRENT CALCULATION REQUIRED PER 110.9, 110.10
 AND LABEL REQUIRED BY 110.24
  
 2) SERVICE FEED BY OTHERS, TO BE INCLUDED WITH THE
 VALUE OF PROJECT.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-10-26 Cont ID  
Sent By shill Date 2021-10-26 Time 13:30 Rev Time 0.00
Received By shill Date 2021-10-26 Time 13:30 Sent To  
Notes
2021-10-26 13:30:56PROVISO: CONTACT ENGINEERING TO DETERMINE IF A RIGHT OF
 WAY PERMIT IS REQUIRED AND OBTAIN A ROW PERMIT IF
 REQUIRED. ISSUED AT APPLICANT'S RISK.
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-10-26 Cont ID  
Sent By shill Date 2021-10-26 Time 13:31 Rev Time 0.00
Received By shill Date 2021-08-10 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-06-24 Cont ID  
Sent By lmarchan Date 2021-06-24 Time 12:24 Rev Time 0.00
Received By lmarchan Date 2021-05-11 Time 08:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-04-15 Cont ID  
Sent By cthroop Date 2021-04-15 Time 10:18 Rev Time 0.00
Received By cthroop Date 2021-03-29 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-11 Cont ID  
Sent By lmarchan Date 2021-01-11 Time 12:07 Rev Time 0.00
Received By lmarchan Date 2020-12-29 Time 08:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-02 Cont ID  
Sent By jleahy Date 2020-12-02 Time 14:29 Rev Time 0.00
Received By jleahy Date 2020-11-24 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-02 Cont ID  
Sent By jleahy Date 2020-11-02 Time 08:20 Rev Time 0.00
Received By jleahy Date 2020-10-26 Time 08:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2021-10-28 Cont ID  
Sent By jleahy Date 2021-10-28 Time 13:12 Rev Time 0.00
Received By jleahy Date 2021-10-28 Time 13:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2021-08-24 Cont ID  
Sent By rmcphers Date 2021-08-24 Time 07:55 Rev Time 0.00
Received By rmcphers Date 2021-08-24 Time 07:47 Sent To  
Notes
2021-08-24 07:55:53SIGNATURE REVIEW
 DRAWINGS LABELED "003 C1-SITE PLAN.PDF.PDF" - "007
 N1-NOTES.PDF " IN PROJECTDOX DO NOT SHOW AS
 ELECTRONICALLY SIGNED IN ADOBE READER - SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2021-06-03 Cont ID  
Sent By rmcphers Date 2021-06-03 Time 08:42 Rev Time 0.00
Received By rmcphers Date 2021-06-03 Time 08:42 Sent To  
Notes
2021-06-03 08:50:12SIGNATURE REVIEW
 DRAWINGS E3 AND N1 DO NOT SHOW AS ELECTRONICALLY SIGNED
 IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC
 PLAN REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-04-15 Cont ID  
Sent By cthroop Date 2021-04-15 Time 10:18 Rev Time 0.00
Received By cthroop Date 2021-04-15 Time 09:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-01-05 Cont ID  
Sent By jleahy Date 2021-01-05 Time 14:33 Rev Time 0.00
Received By jleahy Date 2021-01-05 Time 14:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-02 Cont ID  
Sent By jleahy Date 2020-12-02 Time 14:27 Rev Time 0.00
Received By jleahy Date 2020-12-02 Time 14:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By jleahy Date 2020-11-02 Time 08:15 Rev Time 0.00
Received By jleahy Date 2020-11-02 Time 08:08 Sent To  
Notes
2020-11-02 08:16:34PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED (AND SEALED FOR DESIGN
 PROFESSIONALS) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED OR SIGNED/SEALED
 PAPER SET MAY BE SUPPLIED TO THE BUILDING DEPARTMENT
 WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 5 Status P Date 2021-09-21 Cont ID  
Sent By eschneid Date 2021-09-21 Time 11:44 Rev Time 0.25
Received By eschneid Date 2021-09-20 Time 11:48 Sent To  
Notes
2021-09-21 11:48:36PASSED
  
 1. OBTAIN A RIGHT-OF-WAY USE PERMIT FROM THE CITY'S
 ENGINEERING SERVICES DEPARTMENT PRIOR TO COMMENCING ANY
 WORK WITHIN THE RIGHT-OF-WAY. INCLUDE YOUR APPROVED
 SITE PLAN AND CERTIFIED MAINTENANCE OF TRAFFIC. YOU
 MUST CALL FOR ALL INSPECTIONS REQUIRED AS PART OF THE
 RIGHT-OF-WAY USE PERMIT.
  
 2. MAINTAIN AN ACTIVE CITY OF WEST PALM BEACH WIRELESS
 COMMUNICATIONS SERVICES PROVIDER REGISTRATION. THE
 REGISTRATION MUST BE RENEWED ANNUALLY AND UPDATED
 ANYTIME THAT THERE ARE CHANGES TO THE REGISTRATION.
  
 3. THE INSTALLATION CONTRACTOR MUST CONTACT SUNSHINE
 811 TO VERIFY THE LOCATION OF ALL UTILITIES AND VERIFY
 ALL DEPTHS PRIOR TO CONSTRUCTION. ALL CITY UTILITIES
 MUST BE LOCATED BY SOFT DIG METHODS BEFORE STARTING THE
 WORK.

Review Stop Z ZONING
Rev No 4 Status F Date 2021-06-24 Cont ID  
Sent By eschneid Date 2021-06-24 Time 11:56 Rev Time 0.25
Received By eschneid Date 2021-06-24 Time 08:52 Sent To  
Notes
2021-06-24 11:56:46FAILED
  
 1) THE POWER DRAW IS SHOWN FROM A POLE WITHIN THE 37TH
 STREET RIGHT-OF-WAY. THE SUBMITTED CITY WIRELESS
 COMMUNICATION FACILITY IN THE RIGHT-OF-WAY PERMIT
 REQUIRES ADDITIONAL INFORMATION AND HAS NOT BEEN
 ISSUED, SO THE POWER DRAW IS NOT APPROVED.
  
 2) PROVIDE THE UPDATED UTILITY POWER PLAN WITH
 DIMENSIONS AND THE UPDATED SURVEY SHOWING THE FULL
 EXTENT OF THE UNDERGROUND POWER THAT ARE REQUIRED AS
 PART OF THE WIRELESS COMMUNICATION FACILITY
 APPLICATION.
  
 3) UPLOAD THE MOST CURRENT VERSION OF SHEET C1 SITE
 PLAN THAT WAS SUBMITTED WITH THE WIRELESS COMMUNICATION
 FACILITY APPLICATION.
  
 THE POLE COMPLIES WITH CITY STANDARDS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2021-04-14 Cont ID  
Sent By eschneid Date 2021-04-14 Time 13:41 Rev Time 0.25
Received By eschneid Date 2021-04-14 Time 13:20 Sent To  
Notes
2021-04-14 13:50:03FAILED
  
 1) THE POWER DRAW IS SHOWN FROM A POLE WITHIN THE 37TH
 STREET RIGHT-OF-WAY. STAFF HAS NO RECORD THAT A CITY
 WIRELESS COMMUNICATION FACILITY IN THE RIGHT-OF-WAY
 PERMIT HAS BEEN ISSUED FOR THE BORE WITHIN THE CITY'S
 37TH STREET RIGHT-OF-WAY. PLEASE NOTE THAT THE WIRELESS
 COMMUNICATION FACILITY IN THE RIGHT-OF-WAY APPLICATION
 REQUIRES A SURVEY BY A FLORIDA LICENSED SURVEYOR TO
 VERIFY THAT THE BORE IS NOT ON PRIVATE PROPERTY.
  
 THE POLE COMPLIES WITH CITY STANDARDS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-01-08 Cont ID  
Sent By eschneid Date 2021-01-08 Time 15:04 Rev Time 0.25
Received By eschneid Date 2021-01-08 Time 14:32 Sent To  
Notes
2021-01-08 15:04:56FAILED
  
 1) THE PROPOSED WIRELESS FACILITY (POLE) DOES NOT MEET
 THE CITY OF WEST PALM BEACH CONCEALMENT (STEALTH) OR
 STYLE REQUIREMENTS LISTED IN SECTIONS 78-411(E) AND
 78-411(F) OF THE CITY CODE. PROVIDE A POLE THAT MEETS
 THE CITY CODE REQUIREMENTS. NOTE: VERIZON HAS SHOWN
 POLES ON OTHER APPLICATIONS FOR OTHER LOCATIONS WITHIN
 THE CITY THAT MEET THE CITY CODE REQUIREMENTS.
  
 2) THE POWER DRAW IS SHOWN FROM A POLE WITHIN THE 37TH
 STREET RIGHT-OF-WAY. STAFF HAS NO RECORD THAT A CITY
 WIRELESS COMMUNICATION FACILITY IN THE RIGHT-OF-WAY
 PERMIT HAS BEEN ISSUED FOR THE BORE WITHIN THE CITY'S
 37TH STREET RIGHT-OF-WAY. PLEASE NOTE THAT THE WIRELESS
 COMMUNICATION FACILITY IN THE RIGHT-OF-WAY APPLICATION
 REQUIRES A SURVEY BY A FLORIDA LICENSED SURVEYOR TO
 VERIFY THAT THE BORE IS NOT ON PRIVATE PROPERTY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By eschneid Date 2020-12-01 Time 16:52 Rev Time 0.25
Received By eschneid Date 2020-12-01 Time 16:52 Sent To  
Notes
2020-12-01 17:00:11FAILED
  
 1) PROVIDE A COPY OF THE FDOT APPROVAL FOR THE PROPOSED
 WIRELESS COMMUNICATION FACILITY IN THE RIGHT-OF-WAY.
  
 2) THE PROPOSED WIRELESS FACILITY (POLE) DOES NOT MEET
 THE CITY OF WEST PALM BEACH CONCEALMENT (STEALTH) OR
 STYLE REQUIREMENTS LISTED IN SECTIONS 78-411(E) AND
 78-411(F) OF THE CITY CODE. PROVIDE A POLE THAT MEETS
 THE CITY CODE REQUIREMENTS. NOTE: VERIZON HAS SHOWN
 POLES ON OTHER APPLICATIONS FOR OTHER LOCATIONS WITHIN
 THE CITY THAT MEET THE CITY CODE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy