| 2020-11-06 12:53:32 | RESIDENTIAL (R3) SHUTTERS SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | ORIGINAL COMMENT: |
| | |
| | SHUTTERS INSTALLATION SCHEDULE SUBMITTED: |
| | 1- CONTRACTOR SPECIFIES UNDER THE SUBSTRATE COLUMN THAT |
| | THERE IS A "SOLID CONCRETE TOP BEAM". THERE ARE NOT |
| | SPECIFICATIONS FOR THE SUBSTRATE AT THE BOTTOM OF THE |
| | OPENING. TYPICALLY, THE CONCRETE ANCHOR SCHEDULE IS |
| | USED FOR TOP ANCHORS AND CONCRETE BLOCK ANCHOR SCHEDULE |
| | IS USED FOR BOTTOM ANCHORS UNLESS CONTRACTOR PROVES |
| | THAT THE OPENING SILL IS CONCRETE WITH THE REQUIRED |
| | CONCRETE STRENGTH. |
| | CONTRACTOR IS USING THE SAME CONCRETE ANCHOR SCHEDULE |
| | FOR TOP AND BOTTOM ANCHOR SPACING. REVISE ANCHOR |
| | SPACING AS REQUIRED OR PROVIDE DETAILS OF THE OPENING |
| | SILL CONSTRUCTION INCLUDING THE STRENGTH OF THE |
| | CONCRETE. |
| | |
| | RESPONSE: |
| | COMMENTS WERE NOT ADDRESSED. THE ONLY THING CONTRACTOR |
| | RESUBMIT WAS A PRINTOUT FROM PAPA. THIS WAS NOT |
| | REQUESTED AND DOESN'T ADDRESS THE COMMENTS. PLEASE |
| | REVIEW THE COMMENTS ABOVE AND REVISE THE SHUTTERS |
| | INSTALLATION SCHEDULE ACCORDINGLY AND RESUBMIT. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |