| 2020-11-17 12:41:44 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20101163 |
| | 11/17/20 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) 2ND REQUEST FOR A GAS PIPING RISER DRAWING. PLEASE |
| | NOTE A GAS PLAN AND RISER DRAWING WERE NOT SUBMITTED |
| | UNDER THE RENOVATION PERMIT 19041280. THE PLAN REVIEWER |
| | FOR THE PROJECT NOTED IN HIS COMMENTS THAT GAS WAS TO |
| | BE UNDER A SEPARATE PERMIT. PLEASE SUBMIT A COMPLETE |
| | RISER DRAWING AND APPLIANCE SPECIFICATIONS- SECTIONS |
| | 107.2.1 & 107.3.5.3 WPB. INDICATE HOW MAKEUP AIR WILL |
| | BE PROVIDED TO THE DRYER AND COMBUSTION AIR FOR THE |
| | RANGE- SECTION G2407.1 FBC RES. THE RISER SHALL |
| | INCLUDE: |
| | |
| | A) THE DELIVERY PRESSURE AT THE METER- G2413.1 & |
| | G2413.2 FBC RES. |
| | |
| | B) THE TYPES AND SIZES OF GAS PIPING SECTIONS G2412.3, |
| | G2412.4, & G2413.3 FBC RES. |
| | |
| | C) THE TOTAL LOAD AND THE INDIVIDUAL LOADS OF THE |
| | SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES. |
| | |
| | D) THE TOTAL LENGTH DEVELOPED LENGTH OF THE PIPING FROM |
| | THE METER TO THE MOST REMOTE OUTLET, AND THE INDIVIDUAL |
| | BRANCH AND CUT LENGTHS- SECTIONS G2413.4.1 AND |
| | G2413.4.2 FBC RES. |
| | |
| | E) LOCATIONS OF SHUT OFF VALVES AND PIPE UNIONS- |
| | SECTIONS G2420.5 & G2422.1.4. |
| | |
| | F) LOCATIONS OF NEW AND EXISTING REGULATORS, MAKE AND |
| | MODEL NUMBERS, INLET AND OUTLET PRESSURES- SECTIONS |
| | G2421.1 & G2421.2. SUBMIT MARKED UP OR HIGHLIGHTED |
| | SPECS SHOWING THE SELECTED MODELS, THE MAX INLET AND |
| | OUTLET SIZES AND PRESSURES, SPRING DATA, AND ORIFICE |
| | SIZES. |
| | |
| | 2) PLEASE NOTE THE CONTRACTOR OR QUALIFIER WHO PREPARES |
| | THE GAS RISER DRAWING SHALL PROVIDE HIS/HER SIGNATURE |
| | ON IT- SECTION 107.2.1 WPB, AND FLORIDA STATUTES |
| | 471.003(2)(H) & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |