| 2020-12-09 10:52:41 | PLAN REVIEW / ELECTRICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2014 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE NEW LOAD CALCULATIONS. |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220; FBC RE E3602.2 |
| | |
| | 2. PROVIDE NEW PANEL SCHEDULE. |
| | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | 3. PROVIDE KITCHEN OUTLET SPACING. |
| | E3901.4 COUNTERTOP RECEPTACLES. |
| | IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND |
| | SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR |
| | COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH |
| | SECTIONS E3901.4.1 THROUGH E3901.4.5 (SEE FIGURE |
| | E3901.4). [210.52(C)] |
| | |
| | NOTICE: |
| | TWO 20 AMP SMALL APPLIANCE BRANCH CIRCUTS REQUIRED. |
| | NEC 210.52 (B) (3) ? KITCHEN COUNTER TOP RECEPTACLES |
| | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE |
| | BRANCH CIRCUITS. |
| | |
| | 4. WALL COUNTER TOP SPACING. |
| | E3901.4.1 WALL COUNTERTOP SPACE. |
| | A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE 12 INCHES (305 MM) OR WIDER. |
| | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT |
| | ALONG THE WALL LINE IS MORE THAN 24 INCHES (610 MM), |
| | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| | SPACE. [210.52(C)(1)] |
| | |
| | 5. PROVIDE SMOKE ALARMS |
| | 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A BUILDING. |
| | R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | R314.3 LOCATION. |
| | R314.4 INTERCONNECTION. |
| | |
| | 6. R315.1 CARBON MONOXIDE PROTECTION. |
| | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| | ROOM USED FOR SLEEPING PURPOSES. |
| | FBC-R 315.1 PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 |
| | FEET OF EACH SLEEPING ROOM. |
| | R314.5 COMBINATION ALARMS. |
| | COMBINATION SMOKE AND CARBON MONOXIDE ALARMS SHALL BE |
| | PERMITTED TO BE USED IN LIEU OF SMOKE ALARMS. |
| | |
| | 7. DISHWASHER OUTLET SHALL BE GFCI PROTECTED. |
| | E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT. |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE |
| | PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN |
| | DWELLING UNIT LOCATIONS. [210.8(D)] |
| | |
| | 8. PROVIDE LOCATION OF ALL OUTLETS ON PLAN. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | NOTICE: |
| | GROUND-FAULT AND ARC-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION REQUIRED. |
| | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)] |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |