| Plan Review Stops For Permit 20100993 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-11-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-11-04 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-11-04 |
Time |
16:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-11-02 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-11-02 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2020-11-02 11:03:26 | DEFERRED SUBMITTALS TO BE SUBMITTED AND APPROVED PRIOR | | | TO INSTALLATION | | | | | | 1) GLASS GUARD RAILS | | | | | | 2) IMPACT RATED WINDOWS AND DOORS | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2020-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-10-29 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-10-29 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2020-10-29 15:34:41 | DEFERRED SUBMITTALS TO BE SUBMITTED AND APPROVED PRIOR | | | TO INSTALLATION | | | | | | 1) GLASS GUARD RAILS | | | | | | 2) IMPACT RATED WINDOWS AND DOORS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-11-05 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2020-11-05 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2020-11-05 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2020-11-05 13:16:15 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | PREVIOUS REVIEW COMMENTS: | | | | | | 1) DRAWING E101 MENTIONS TWO DUPLEX RECEPTABLES IN | | | APPLIANCE GARAGE BUT THEY SEEM TO BE INSTALLED AS PART | | | OF THE KITCHEN RECEPTACLES. PLEASE CLARIFY. ARE THESE | | | RECEPTACLES GFCI PROTECTED? | | | | | | SECOND ELECRICAL REVIEW (APPROVED) | | | | | | | | | 1) DRAWING E101 MENTIONS TWO DUPLEX RECEPTABLES IN | | | APPLIANCE GARAGE BUT THEY SEEM TO BE INSTALLED AS PART | | | OF THE KITCHEN RECEPTACLES. PLEASE CLARIFY. ARE THESE | | | RECEPTACLES GFCI PROTECTED? | | | | | | CORRECTED. | | | | | | ENRIQUE QUINONEZ | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | | | | ENRIQUE QUINONEZ | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-10-30 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2020-10-30 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2020-10-30 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2020-10-30 14:07:06 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1) DRAWING E101 MENTIONS TWO DUPLEX RECEPTABLES IN | | | APPLIANCE GARAGE BUT THEY SEEM TO BE INSTALLED AS PART | | | OF THE KITCHEN RECEPTACLES. PLEASE CLARIFY. ARE THESE | | | RECEPTACLES GFCI PROTECTED? | | | | | | ENRIQUE QUINONEZ | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-11-05 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2020-11-05 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2020-11-03 |
Time |
09:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-10-30 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2020-10-30 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2020-10-23 |
Time |
06:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2020-10-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-10-28 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-10-28 |
Time |
08:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-11-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-11-04 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-11-04 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2020-11-04 10:59:12 | 11/04/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-10-27 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-10-27 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2020-10-27 12:59:17 | 10/27/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE PROVIDE A PLUMBING RISER DIAGRAM REQUIRED PER | | | THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) | | | RESIDENTIAL PLUMBING. | | | | | | 2. THE SLAB REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT | | | OF THE SOIL AND THE REQUIRED VAPOR BARRIER OVER | | | WELL-COMPACTED SOIL. A COPY OF THE TERMITE CERTIFICATE | | | SHALL BE ONSITE FOR A FINAL INSPECTION PER THE 2017 | | | FBC-RESIDENTIAL SECTION R 318.1.1. IF SOIL TREATMENT IS | | | USED FOR SUBTERRANEAN TERMITE PREVENTION, THE INITIAL | | | CHEMICAL SOIL TREATMENT INSIDE THE FOUNDATION PERIMETER | | | SHALL BE DONE AFTER ALL EXCAVATION, BACKFILLING AND | | | COMPACTION IS COMPLETE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-11-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-11-04 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-11-04 |
Time |
16:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-11-02 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-11-02 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2020-11-02 11:04:03 | S&S CALCS RECEIVED & UPLOADED | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-10-29 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-10-29 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2020-10-29 15:25:48 | THE STRUCTURAL CALCULATIONS FROM THE ENGINEER ARE | | | REQUIRED TO BE SIGNED AND SEALED. ELECTRONICALLY | | | SUBMITTED DRAWINGS AND DOCUMENTS ARE REQUIRED TO HAVE | | | THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE | | | THE OPTION TO SUBMIT THE PAPER VERSION OF DRAWINGS WITH | | | THE ENGINEER?S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL. | | | AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN | | | SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | | DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | | SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15 |
|
|