| 2020-11-02 12:29:47 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100980 |
| | 11/2/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REVISE THE GAS RISER TO INCLUDE THE 22 KW GAS |
| | GENERATOR WHICH IS CURRENTLY BEING REVIEWED FOR PERMIT |
| | ISSUANCE UNDER APPLICATION #20090018. THE SUBMITTED |
| | SPECS FOR THE GENERATOR INDICATE A FULL LOAD CAPACITY |
| | OF 327,000 BTUH- SECTION G2412.3 & G2412.4 FBC RES. |
| | |
| | 2) SHOW ALL PIPE SIZES INCLUDING THE MAIN PIPE FROM THE |
| | METER TO THE TEE, THE MAIN RUN, AND THE BRANCHES TO THE |
| | APPLIANCES- SECTION G2413.1 FBC RES. |
| | |
| | 3) SHOW THE LOCATIONS OF THE LOW PRESSURE REGULATORS |
| | AND THE OUTPUT PRESSURES AT EACH APPLIANCE- SECTION |
| | G2421.1. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | REGULATORS MARKED UP OR HIGHLIGHTED TO SHOW THE |
| | SELECTED MODEL, INPUT AND OUTPUT PRESSURES AND PIPE |
| | SIZES, AND ORIFICE SIZES. |
| | |
| | 4) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING |
| | WITHIN 1 FT. OF EITHER SIDE THE REGULATORS- SECTION |
| | G2421.2(7). |
| | |
| | 5) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS COMPLETE SIGNATURE ON IT- SECTION |
| | 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) & |
| | 471.025. PLEASE INCLUDE A TITLE BLOCK ON THE DRAWING |
| | THAT INCLUDES CONTRACTOR OR COMPANY NAME AND LICENSE |
| | NUMBER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |