2020-11-20 08:51:30SEE INTE. DEMO PERMIT 20080547. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By jgomez Date 2020-11-20 Time 10:41 Rev Time 0.00
Received By jgomez Date 2020-11-19 Time 17:17 Sent To  
Notes
2020-11-20 10:42:59RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- THE VALUE DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL THE BUILDING, ELECTRICAL AND PLUMBING
 SCOPE OF WORK SHOWN ON SKETCHES AND SUPPORTING
 DOCUMENTS SUBMITTED. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS OR
 PROVIDE COPY OF SIGNED CONTRACTS INCLUDING ALL LABOR,
 MATERIALS, DESIGN PROFESSIONAL FEES, ETC.
  
 2- NEED TO PROVIDE COMPLETE SET OF PLANS SHOWING ALL
 THE SCOPE OF WORK TO BE PERFORMED AND PLANS NEED TO BE
 SIGNED AND SEALED BY AN ARCHITECT AS REQUIRED BY
 CHAPTER 481 FLORIDA STATUTES AND 61G1 FLORIDA
 ADMINISTRATIVE CODE.
 A)BASED ON ALL THE BUILDING, ELECTRICAL AND PLUMBING
 SCOPE OF WORK SHOWN ON SKETCHES AND SUPPORTING
 DOCUMENTS SUBMITTED-AND THE OVERALL VALUE THE WORK IS
 NO EXEMPT FROM ARCHITECT'S LICENSURE. SEC. 481.229
 FLORIDA STATUTE.
 NOTE: PLANS TO SHOW THE EXISTING AND PROPOSED KITCHEN
 LAYOUT, DETAILS AND SPECIFICATIONS FOR THE NEW KITCHEN,
 BATHROOM AND HALL DROPPED CEILINGS, SPRINKLER HEADS
 LOCATION OR RELOCATION, FIRE ALARMS LOCATION, A/C
 CLOSET WALL DETAILS, ETC.
  
 B)THIS IS AN ALTERATION LEVEL 2. SEC. 504 FBC-EXISTING
 BUILDING. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE. SEC. 801.3 FBC-EXISTING
 BUILDING.
  
 3- THE SCOPE OF WORK SPECIFIED ON THE PERMIT
 APPLICATION WAS REVISED. BASED ON THE SCOPE OF WORK
 SUBMITTED THE DESCRIPTION WAS CHANGED TO REPLACE
 KITCHEN CABINETS(NEW LAYOUT)AND VANITIES IN BATHROOM.
 BEDROOM/DINING AND A/C CLOSET ALTERATION. SEC. 107.2.1
 CITY AMENDMENTS. REVISE SCOPE OF WORK IN PERMIT
 APPLICATION.
  
 4- FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-11-30 Cont ID  
Sent By equinone Date 2020-11-30 Time 14:52 Rev Time 0.00
Received By equinone Date 2020-11-30 Time 14:51 Sent To  
Notes
2020-11-30 14:52:28SEE SIGNATURE COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-11-17 Cont ID  
Sent By pleduc Date 2020-11-17 Time   Rev Time 0.00
Received By pleduc Date 2020-11-17 Time 15:47 Sent To  
Notes
2020-11-17 15:48:20FIRE PROVISO:
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-30 Cont ID  
Sent By equinone Date 2020-11-30 Time 14:52 Rev Time 0.00
Received By equinone Date 2020-11-10 Time 14:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By lcrespo Date 2020-11-18 Time 09:14 Rev Time 0.00
Received By lcrespo Date 2020-11-18 Time 09:06 Sent To  
Notes
2020-11-20 10:45:3311/20/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SIGNED AND SEALED DRAWINGS OR
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ARCHITECT TO BE
 USED IN ELECTRONIC PLAN REVIEW - OR - IF YOUR THEY DO
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - PLEASE
 DROP OFF (CITY HALL DROPBOX) THE ORIGINAL SIGNED AND
 SEALED DOCUMENT ALONG WITH A "PLAN REVIEW REQUEST FORM"
 EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT OR
 DRAWINGS. THE PLAN REVIEW REQUEST FORM CAN BE OBTAINED
 BY EMAILING [email protected] AND ASKING FOR THE FORM.
  
 2. PLEASE PROVIDE A SANITARY AND WATER PLUMBING RISER
 DIAGRAM PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 3. PLEASE PROVIDE A DESCRIPTIVE AND MORE UNDERSTANDABLE
 SCOPE OF WORK ON THE PLANS PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. THE OVERALL VALUE IS LOW PER THE WPB AMENDMENTS TO
 THE FBC 109.3 BUILDING PERMITS VALUATIONS. IF IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF THE BUILDING, ALTERATION, STRUCTURE, ELECTRICAL,
 GAS, MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED UNLESS THE APPLICANT CAN SHOW DETAILED, QUANTITY
 ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING
 LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING
 OFFICIAL. FOR PERMITTING PURPOSES, THE VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD, AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. THE FINAL BUILDING PERMIT VALUATION SHALL BE
 SET BY THE BUILDING OFFICIAL.
  
 5. PLEASE SHOW THE MORING KITCHEN ON PLANS WPB
 AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL
 PLUMBING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By jgomez Date 2020-11-20 Time 10:44 Rev Time 0.00
Received By jgomez Date 2020-11-20 Time 10:15 Sent To  
Notes
2020-11-20 10:45:53NOTE: SEE BUILDING REVIEW COMMENTS.
  
 1-- NEED TO PROVIDE COMPLETE SET OF PLANS SHOWING ALL
 THE SCOPE OF WORK TO BE PERFORMED AND PLANS NEED TO BE
 SIGNED AND SEALED BY AN ARCHITECT AS REQUIRED BY
 CHAPTER 481 FLORIDA STATUTES AND 61G1 FLORIDA
 ADMINISTRATIVE CODE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ