Plan Review Details - Permit 20100902
Plan Review Stops For Permit 20100902
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-01-14 Cont ID  
Sent By rmcphers Date 2021-01-14 Time 12:57 Rev Time 0.00
Received By rmcphers Date 2021-01-14 Time 12:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By rmcphers Date 2020-11-25 Time 12:33 Rev Time 0.00
Received By rmcphers Date 2020-11-25 Time 11:05 Sent To  
Notes
2020-11-25 12:33:07NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A SIGNED AND SEALED SURVEY SHOWING
 THE FOLLOWING INFORMATION 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY
 PROPOSED WATER RETAINING SWALES)
 2) PLEASE DESCRIBE THE BUILDING USE. (WHAT IS THE
 BUILDING BEING USED FOR?).
 3) EACH PAGE OF THE DRAWINGS NEED TO BE SIGNED AND
 SEALED BY THE ENGINEER. FBC 107.2
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-01-15 Cont ID  
Sent By equinone Date 2021-01-15 Time 15:30 Rev Time 0.00
Received By equinone Date 2021-01-15 Time 15:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-02 Cont ID  
Sent By equinone Date 2020-12-02 Time 08:37 Rev Time 0.00
Received By equinone Date 2020-12-02 Time 08:37 Sent To  
Notes
2020-12-02 08:39:42CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: FAILED.
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW LOCATION OF NEW SERVICE, PANEL. PROVIDE
 RISER DIAGRAM SHOWING PANEL SIZE, MAIND DISCONNECT,
 SERVICE CONDUCTOR SIZE, AND GROUNDING DETAILS.
 2) DRAWINGS WILL NEED TO BE SIGNED BY CONTRACTOR
 QUALIFIER OR ENGINEER.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-15 Cont ID  
Sent By equinone Date 2021-01-15 Time 15:30 Rev Time 0.00
Received By equinone Date 2021-01-06 Time 10:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-05 Cont ID  
Sent By equinone Date 2021-01-05 Time 09:48 Rev Time 0.00
Received By lmarchan Date 2020-11-13 Time 08:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-11-19 Cont ID  
Sent By medwards Date 2020-11-19 Time 08:15 Rev Time 0.00
Received By medwards Date 2020-11-19 Time 08:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-11-20 Cont ID  
Sent By lcrespo Date 2020-11-20 Time 12:05 Rev Time 0.00
Received By lcrespo Date 2020-11-20 Time 12:05 Sent To  
Notes
2020-11-20 12:05:44NO PLUMBING ON THE SCOPE OF WORK OR ON PLANS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2020-11-25 Cont ID  
Sent By rmcphers Date 2020-11-25 Time 12:38 Rev Time 0.00
Received By rmcphers Date 2020-11-25 Time 12:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-14 Cont ID  
Sent By rmcphers Date 2021-01-14 Time 12:58 Rev Time 0.00
Received By rmcphers Date 2021-01-14 Time 12:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By rmcphers Date 2020-11-25 Time 12:38 Rev Time 0.00
Received By rmcphers Date 2020-11-25 Time 12:38 Sent To  
Notes
2020-11-25 12:39:09SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 2 Status P Date 2021-01-08 Cont ID  
Sent By kalexand Date 2021-01-08 Time 17:28 Rev Time 0.00
Received By kalexand Date 2021-01-08 Time 17:28 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-04 Cont ID  
Sent By kalexand Date 2021-01-04 Time 16:54 Rev Time 0.00
Received By kalexand Date 2021-01-04 Time 16:54 Sent To I
Notes
2021-01-04 17:08:26ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE A CURRENT PROPERTY SURVEY INDICATIONG THE
 FOLLWING:
 -- LOCATION OF WORK
 -- SETBACKS DIMENSIONS OF PROPOSED WORK FROM ALL
 PROPERTY LINES; PURSUANT TO ZLDR SEC. 94-304, THE
 SETBACKS FOR ACCESSORY STRUCTURES ARE AS FOLLOWS:
 --FRONT: 25 FEET
 --SIDE: FIVE FEET MINIMUM
 --REAR: 15 FEET OR 15 FEET FROM THE CENTERLINE OF THE
 ALLEY TO A GARAGE DOOR FACING THE ALLEY, WHICHEVER IS
 GREATER.
  
 2. PROVIDE THE TOTAL HEIGHT OF THE PROPOSED STRUCTURE
 ON THE ELEVATION PLAN. PURSUANT TO THE ZLDR, SECTION
 94-611, HEIGHT SHALL BE MEASURED AS THE VERTICAL
 DISTANCE FROM THE AVERAGE ELEVATION OF THE FINISHED
 GRADE OF THE BUILDING TO THE HIGHEST POINT OF THE TOP
 OF THE STRUCTURE OF A FLAT ROOF, OR TO THE DECK LINE OF
 A MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL BETWEEN
 EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved