Plan Review Details - Permit 20100899
Plan Review Stops For Permit 20100899
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-01-21 Cont ID  
Sent By cpuell Date 2021-01-21 Time 10:43 Rev Time 0.00
Received By cpuell Date 2021-01-21 Time 10:43 Sent To  
Notes
2021-01-21 10:43:54GARAGES HAVE NOT BEEN GIVEN ADDRESSES

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-12-11 Cont ID  
Sent By cpuell Date 2020-12-11 Time 14:38 Rev Time 0.00
Received By cpuell Date 2020-12-11 Time 14:38 Sent To  
Notes
2020-12-11 14:39:34ACCESSORY STRUCTURES NOT BEING GIVEN AN ADDRESS HOWEVER
 HAVE TO WAIT UNTIL NEW OWNER TAKES OVER PROJECT SO THE
 CORRECT PRIMARY ADDRESS IS ASSIGNED. PLEASE EMAIL
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-07-08 Cont ID  
Sent By rmcdouga Date 2021-07-08 Time 10:49 Rev Time 0.00
Received By rmcdouga Date 2021-07-08 Time 10:49 Sent To  
Notes
2021-07-08 10:50:56UNDER CONSTRUCTION AND FINAL ELEVATION CERTIFICATES ARE
 REQUIRED.
 SEE LIST OF DEFERRED SUBMITTALS ON SHEET GA-1A.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-14 Cont ID  
Sent By pvalenti Date 2021-06-14 Time 16:16 Rev Time 0.00
Received By pvalenti Date 2021-06-14 Time 12:59 Sent To  
Notes
2021-06-14 16:24:37****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD BUILDING REVIEW DENIED:
  
 1) OK PER PAGE GA1A.
 2) APPROVED
 3) APPROVED
 4) FAILED, PROVIDE A CLARIFICATION AS THE FOUNDATION
 PLANS INDICATE FOOTINGS AT A DEPTH OF 16" BELOW GRADE
 AND THE GEO TECH REPORT STATES THAT THE FOOTINGS SHOULD
 BOTTOM AT 18" BELOW GRADE.
 5) APPROVED
 6) APPROVED
 7) APPROVED
 8) & 9) THE SUBMITTED PRODUCT APPROVALS NEED TO BE
 REVIEW STAMPED BY DESIGNER OF RECORD. IF THESE PRODUCT
 APPROVALS ARE TO BE DEFERRED, PLEASE PROVIDE A LIST ON
 PLANS (APPROVED BY DESIGNER OF RECORD) OF THOSE
 SUBMITTALS THAT ARE TO BE DEFERRED.
 10) APPROVED
 11) APPROVED
 12) APPROVED
 13) APPROVED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-02-16 Cont ID  
Sent By rmcdouga Date 2021-02-16 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2021-02-16 Time 11:50 Sent To  
Notes
2021-02-16 10:33:18PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 GARAGE ( TYPE 1A ) / DETACHED PRIVATE GARAGE BUILDING
 (8 UNITS)
 TYPE V-B CONSTRUCTION, UNSPRINKLERED
 GROUP U OCCUPANCY
  
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED. I DO NOT SEE THAT THE PROPOSED SLAB
 ELEVATIONS IN NAVD 88 VERTICAL DATUM IS SPECIFIED ON
 THE ARCHITECTURAL PLANS AS REQUESTED. FBC
 AMEND.107.2.1.2 THE PROPOSED FLOOD VENTS IN THE GARAGE
 DOORS DO NOT COMPLY WITH FEMA TECHNICAL BULLETIN 1 FOR
 WET FLOOD PROOFING. AT LEAST 2 FLOOD OPENINGS ARE
 REQUIRED ON DIFFERENT SIDES OF THE ENCLOSURE. THE
 REQUIRED NET OPEN AREA FOR NON-ENGINEERED FLOOD VENTS
 IS 1 SQUARE INCH FOR EACH SQUARE FOOT OF ENCLOSED AREA
 (MEASURED ON THE EXTERIOR OF THE ENCLOSURES WALLS).
 ONLY THE NET FREE AREA EXCLUDING LOUVERS, SCREENS, ETC.
 CAN BE COUNTED. THE SPACES BETWEEN GARAGE DOORS AND
 JAMBS OR WALLS CAN NOT BE COUNTED. ONLY THE NET AREA OF
 THE VENTS THAT AREA BELOW DFE CAN BE COUNTED. VENTS IN
 FIRE RATED WALLS ARE REQUIRED TO HAVE A FIRE RATING AS
 REQUIRED FOR THE WALL. SEE FEMA TB 1 FOR GUIDANCE. YOU
 ALSO HAVE THE OPTION TO ELEVATE THE GARAGES TO THE DFE
 OR TO DRY FLOOD PROOF THE DETACHED GARAGES.
 THIS PROJECT IS IN A SPECIAL FLOOD HAZARD AREA, AE. THE
 BFE IS 14' NAVD88 AND THE DFE IS 16' NAVD88. THE FINISH
 FLOOR ELEVATION OF THE GARAGE IS SPECIFIED AS 15'
 NAVD88. THIS IS ONE FOOT BELOW THE REQUIRED DFE AND
 WILL BE REQUIRED TO BE DESIGNED WITH FLOOD VENTS OR BE
 FLOOD PROOFED. PROVIDE A DESIGN THAT COMPLIES WITH THE
 CITY'S FLOOD ORDINANCE. SPECIFY THE PROPOSED ELEVATION
 OF THE GARAGE SLAB, IN NAVD 88 VERTICAL DATUM, ON THE
 ARCHITECTURAL PLANS. FBC 1612
  
 2) RESOLVED. PROVIDE A DETAIL FOR THE REQUIRED ONE HOUR
 FIRE RESISTIVE RATED CEILING ASSEMBLY AND THE LISTING
 INFORMATION. FBC 711
  
 3) RESOLVED. PROVIDE A DETAIL FOR THE LISTED JOINT
 TREATMENT THAT WILL BE USED AT THE INTERSECTION OF THE
 ONE HOUR FIRE RESISTIVE RATED THE INTERIOR WALLS AND
 CEILINGS. FBC 715
  
 4) PARTIALLY RESOLVED. THE DATE ON THE REVISED
 GEOTECHNICAL REPORT IS 1/1/2020 AND THE YEAR SHOULD BE
 2021. SECTION 4.2 ON THE GEOTECHNICAL REPORT STATES
 THAT THE FOOTINGS SHOULD BOTTOM AT LEAST 18" BELOW
 FINAL GRADE. SHOW HOW THIS BUILDING WILL MEET THIS
 REQUIREMENT. FBC 107.2
  
 5) RESOLVED. WALL SECTION 2 ON SHEET GA-1, SHOWS THE
 BOTTOM OF THE FOOTER 8" BELOW GRADE. FBC REQUIRES THE
 BOTTOM OF FOOTINGS TO BE A MINIMUM OF 12" BELOW GRADE.
 FBC 1809.5
  
 6) RESOLVED.ON SHEET GA-1A THE FIRE RATED WALLS, TYPE
 L, BETWEEN THE GARAGE UNITS ARE SPECIFIED AS 8"
 MASONRY. DETAIL S-GA-1A.2 IS FOR A 4" X 4" CONCRETE CAP
 AT THESE LOCATIONS WITH ONLY THE CONCRETE SLAB AND NO
 FOOTING. PLEASE COORDINATE. FBC 107.2
  
 7) RESOLVED. PROVIDE STRUCTURAL DETAILS FOR THE TYPE L
 FIRE RATED MASONRY WALLS BETWEEN THE GARAGES. SPECIFY
 THE FOOTING, WALL AND TIE BEAM REINFORCING. FBC 2101
  
 8) PARTIALLY RESOLVED. A) ROOF TILE: THE PRODUCT
 APPROVAL FOR THE ROOF TILE DOES NOT HAVE THE COVER
 SHEET WITH THE FLORIDA PRODUCT APPROVAL NUMBER THAT
 REFERENCES THE EVALUATION REPORT THAT WAS SUBMITTED.
 HIGHLIGHT OR CIRCLE THE SPECIFIC TYPE AND NUMBER OF
 FASTENERS THAT WILL BE USED TO ATTACH THE ROOF TILES.
 IF AN ADHESIVE WILL BE USED, SUBMIT THE PRODUCT
 APPROVAL FOR IT.
 B) GARAGE DOOR: THE PRODUCT APPROVAL DRAWINGS FOR THE
 OVERHEAD GARAGE DOORS ARE INCOMPLETE. A PORTION OF THE
 UPLOADED DRAWINGS ARE MISSING. PLEASE SUBMIT COMPLETE
 DRAWINGS.
 C) NO PRODUCT APPROVALS WERE SUBMITTED FOR THE OUTSWING
 SIDE HINGED DOORS.
 D) SUBMIT THE PRODUCT APPROVALS WITH A SHOP REVIEW
 STAMP MARKED APPROVED BY THE DESIGNER OF RECORD FOR THE
 PROJECT.
 FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001
 PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA
 NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM
 DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING
 MATERIALS, ROOF VENTS, SWING DOORS AND OVERHEAD GARAGE
 DOORS. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 9) DEFERRED. SUBMIT TRUSS DRAWINGS AND A TRUSS LAYOUT
 PLAN. FBC 2303.4 THESE ITEMS CAN BE DEFERRED IF
 REQUESTED, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND
 APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 10) RESOLVED. ACCESSIBLE CAR AND VAN PARKING SPACES ARE
 REQUIRED TO BE A MINIMUM OF 12' WIDE AND HAVE A MINIMUM
 60" WIDE ACCESS AISLE. SHOW COMPLIANCE WITH FBC
 ACCESSIBILITY 502.2 AND 502.3.1
  
 11) RESOLVED. FBC ACCESSIBILITY 502.4 REQUIRES THE
 ACCESSIBLE PARKING SPACE AND ACCESS AISLE TO HAVE A
 SLOPE NOT STEEPER THAN 1:48. THE SLOPE ON SHEET GA-1A
 IS SPECIFIED AS 1:20.
  
 12) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 13) NEW COMMENT. THE (2) OUTSWING SIDE HINGED DOORS ARE
 NOT LISTED IN THE DOOR SCHEDULE ON SHEET GA-1A. FBC
 107.2.1
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-10 Cont ID  
Sent By rmcdouga Date 2020-11-10 Time 10:06 Rev Time 0.00
Received By rmcdouga Date 2020-11-10 Time 07:34 Sent To  
Notes
2020-11-10 10:06:49PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 GARAGE ( TYPE 1A ) / DETACHED PRIVATE GARAGE BUILDING
 (8 UNITS)
 TYPE V-B CONSTRUCTION, UNSPRINKLERED
 GROUP U OCCUPANCY
  
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PROJECT IS IN A SPECIAL FLOOD HAZARD AREA, AE.
 THE BFE IS 14' NAVD88 AND THE DFE IS 16' NAVD88. THE
 FINISH FLOOR ELEVATION OF THE GARAGE IS SPECIFIED AS
 15' NAVD88. THIS IS ONE FOOT BELOW THE REQUIRED DFE AND
 WILL BE REQUIRED TO BE DESIGNED WITH FLOOD VENTS OR BE
 FLOOD PROOFED. PROVIDE A DESIGN THAT COMPLIES WITH THE
 CITY'S FLOOD ORDINANCE. SPECIFY THE PROPOSED ELEVATION
 OF THE GARAGE SLAB, IN NAVD 88 VERTICAL DATUM, ON THE
 ARCHITECTURAL PLANS. FBC 1612
  
 2) PROVIDE A DETAIL FOR THE REQUIRED ONE HOUR FIRE
 RESISTIVE RATED CEILING ASSEMBLY AND THE LISTING
 INFORMATION. FBC 711
  
 3) PROVIDE A DETAIL FOR THE LISTED JOINT TREATMENT THAT
 WILL BE USED AT THE INTERSECTION OF THE ONE HOUR FIRE
 RESISTIVE RATED THE INTERIOR WALLS AND CEILINGS. FBC
 715
  
 4) SECTION 4.2 ON THE GEOTECHNICAL REPORT STATES THAT
 THE FOOTINGS SHOULD BOTTOM AT LEAST 18" BELOW FINAL
 GRADE. SHOW HOW THIS BUILDING WILL MEET THIS
 REQUIREMENT. FBC 107.2
  
 5) WALL SECTION 2 ON SHEET GA-1, SHOWS THE BOTTOM OF
 THE FOOTER 8" BELOW GRADE. FBC REQUIRES THE BOTTOM OF
 FOOTINGS TO BE A MINIMUM OF 12" BELOW GRADE. FBC 1809.5
  
 6) ON SHEET GA-1A THE FIRE RATED WALLS, TYPE L, BETWEEN
 THE GARAGE UNITS ARE SPECIFIED AS 8" MASONRY. DETAIL
 S-GA-1A.2 IS FOR A 4" X 4" CONCRETE CAP AT THESE
 LOCATIONS WITH ONLY THE CONCRETE SLAB AND NO FOOTING.
 PLEASE COORDINATE. FBC 107.2
  
 7) PROVIDE STRUCTURAL DETAILS FOR THE TYPE L FIRE RATED
 MASONRY WALLS BETWEEN THE GARAGES. SPECIFY THE FOOTING,
 WALL AND TIE BEAM REINFORCING. FBC 2101
  
 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, ROOF VENTS, SWING DOORS AND OVERHEAD
 GARAGE DOORS. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 9) SUBMIT TRUSS DRAWINGS AND A TRUSS LAYOUT PLAN. FBC
 2303.4 THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 10) ACCESSIBLE CAR AND VAN PARKING SPACES ARE REQUIRED
 TO BE A MINIMUM OF 12' WIDE AND HAVE A MINIMUM 60" WIDE
 ACCESS AISLE. SHOW COMPLIANCE WITH FBC ACCESSIBILITY
 502.2 AND 502.3.1
  
 11) FBC ACCESSIBILITY 502.4 REQUIRES THE ACCESSIBLE
 PARKING SPACE AND ACCESS AISLE TO HAVE A SLOPE NOT
 STEEPER THAN 1:48. THE SLOPE ON SHEET GA-1A IS
 SPECIFIED AS 1:20.
  
 12) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-03 Cont ID  
Sent By equinone Date 2021-06-03 Time 10:56 Rev Time 0.00
Received By equinone Date 2021-06-03 Time 10:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-02-08 Cont ID  
Sent By equinone Date 2021-02-08 Time 13:49 Rev Time 0.00
Received By equinone Date 2021-02-08 Time 13:39 Sent To  
Notes
2021-02-08 13:49:27CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 NEW COMMENTS:
  
 1) NEW SHEET GA2 -0.0 INDEX OF DRAWINGS: NEWLY REVISED
 SHEET LISTS THREE ELECTRICAL DRAWINGS (E-1.0, E-1-1,
 AND E-GIA.1). ONLY THE E-GIA.A ELECTRICAL HAS BEEN
 SUBMITTED. PLEASE CLARIFY AND UPLOAD MISSING DRAWINGS
 IF NEEDED.
 2) PLEASE SUBMIT SHORT CIRCUIT CALCULATIONS AND
 AVAILABLE FAULT CURRENTS FOR PANEL G1A. FCB 107
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By equinone Date 2020-11-25 Time 09:47 Rev Time 0.00
Received By equinone Date 2020-11-25 Time 09:26 Sent To  
Notes
2020-11-25 09:48:28CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: FAILED, SEE COMMENTS BELOW.
  
 1) GARAGE POWER RISER SHOWS PANEL G1A BEING FED FROM
 UTILITY TRANSFORMER. PANEL G1A IS DESCRIBED AS MLO
 TYPE. PLEASE PROVIDE SERVICE EQUIPMENT DISCONNECT AND
 OVERCURRENT PROTECTION TO COMPLY WITH NEC 230.
 2) SEE BUILDING COMMENTS REGARDING FLOOD ZONE
 REQUIREMENTS. PLEASE SHOW COMPLIANCE WITH THESE
 REQUIREMENTS.
 2) SCOPE OF WORK IS LIMITED TO DETACHED GARAGE TYPE I
 STRUCTURES. SITE LIGHTING, FIRE ALARM, AND LOW VOLTAGE
 WORK REQUIRES SEPARATE PERMITS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2020-11-05 Cont ID  
Sent By rrossano Date 2020-11-05 Time   Rev Time  
Received By rrossano Date 2020-11-05 Time   Sent To  
Notes
2020-11-05 08:20:55ONSITE UTILITIES ARE PRIVATE. REVIEWING OVERALL
 ENGINEERING SUBMITTAL E20080019.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-07-07 Cont ID  
Sent By pleduc Date 2021-07-07 Time   Rev Time 0.00
Received By pleduc Date 2021-07-07 Time 12:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-05-27 Cont ID  
Sent By pleduc Date 2021-05-27 Time   Rev Time 0.00
Received By pleduc Date 2021-05-27 Time 15:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2021-01-25 Cont ID  
Sent By pleduc Date 2021-01-25 Time   Rev Time 0.00
Received By pleduc Date 2021-01-25 Time 13:17 Sent To  
Notes
2021-01-25 13:17:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) YOUR RESPONSE HAS CITED THE FL BUILDING CODE.
  
 THE PROPOSED IS A PARKING STRUCTURE UNDER THE FLORIDA
 FIRE PREVENTION CODE.
  
 PER NFPA 1, CH 3 DEFINITIONS
  
 3.3.183.23* PARKING STRUCTURE. A BUILDING, STRUCTURE,
 OR PORTION
 THEREOF USED FOR THE PARKING, STORAGE, OR BOTH, OF
 MOTOR VEHICLES.
  
  
 THE PREVIOUS COMMENTS REMAIN.
  
 PLEAE REVIEW AND CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-11-10 Cont ID  
Sent By pleduc Date 2020-11-10 Time   Rev Time 0.00
Received By pleduc Date 2020-11-10 Time 15:43 Sent To  
Notes
2020-11-10 16:02:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) ONLY ONE EXIT IS INDICATED IN SOME OF THE INDIVIDUAL
 UNITS.
  
 PER NFPA 101, CH 42
  
 42.8 SPECIAL PROVISIONS FOR PARKING STRUCTURES.
  
 42.8.1 GENERAL REQUIREMENTS
  
 42.8.1.1 APPLICATION. THE PROVISIONS OF 42.8.1 THROUGH
 42.8.5.4
 SHALL APPLY TO PARKING STRUCTURES OF THE CLOSED OR OPEN
 TYPE, ABOVE
 OR BELOW GRADE PLANE, BUT SHALL NOT APPLY TO ASSISTED
 MECHANICALTYPE
 OR AUTOMATED-TYPE PARKING FACILITIES THAT ARE NOT
 OCCUPIED BY
 CUSTOMERS. THE REQUIREMENTS OF SECTIONS 42.1 THROUGH
 42.7 SHALL
 NOT APPLY.
  
 42.8.2.2.2.3 AN OPENING FOR THE PASSAGE OF AUTOMOBILES
 SHALL BE
 PERMITTED TO SERVE AS AN EXIT FROM A STREET FLOOR,
 PROVIDED THAT NO
 DOOR OR SHUTTER IS INSTALLED THEREIN.
  
 42.8.2.4.1 NOT LESS THAN TWO MEANS OF EGRESS SHALL BE
 PROVIDED
 FROM EVERY FLOOR OR SECTION OF EVERY PARKING STRUCTURE.
  
 PLEASE CORRECT OF JUSTIFY WITH SPECIFIC CODE REFERENCES
 AND NARRATIVE.
  
  
  
 2) THERE IS AN EXHAUST FAN INDICATED; HOWEVER, IT DOES
 NOT APPEAR TO MEET THE REQUIREMENT.
  
 NFPA 88A
  
 6.3 VENTILATION.
 6.3.1* ALL ENCLOSED PARKING STRUCTURES SHALL BE
 VENTILATED BY
 A MECHANICAL SYSTEM CAPABLE OF PROVIDING A MINIMUM OF
 300 L/MIN PER M2 OF FLOOR AREA (1 FT3/MIN PER FT2 OF
 FLOOR
 AREA) DURING HOURS OF NORMAL OPERATION.
  
 6.3.3 MECHANICAL VENTILATING SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE
 WITH NFPA 90A. DUCTWORK SHALL BE CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIAL.
  
 PLEASE REVIEW AND EXPLAIN COMPLIANCE WITH THE CODE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-09 Cont ID  
Sent By jleahy Date 2021-07-09 Time 16:13 Rev Time 0.00
Received By jleahy Date 2021-07-06 Time 08:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-15 Cont ID  
Sent By pvalenti Date 2021-06-15 Time 11:24 Rev Time 0.00
Received By pvalenti Date 2021-05-26 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-16 Cont ID  
Sent By rmcdouga Date 2021-02-16 Time 11:53 Rev Time 0.00
Received By rmcdouga Date 2021-01-20 Time 10:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-11 Cont ID  
Sent By cpuell Date 2020-12-11 Time 14:39 Rev Time 0.00
Received By cpuell Date 2020-10-23 Time 16:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2021-07-14 Cont ID  
Sent By lmarchan Date 2021-07-14 Time 10:11 Rev Time 0.00
Received By lmarchan Date 2021-07-08 Time 08:21 Sent To  
Notes
2021-07-14 10:12:10NO IMPACT FEES DUE - EMAIL UPLOADED
2021-07-08 08:21:267/8/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2021-03-25 Cont ID  
Sent By lmarchan Date 2021-03-25 Time 11:20 Rev Time 0.00
Received By lmarchan Date 2021-03-25 Time 11:19 Sent To  
Notes
2021-03-25 11:20:07STOP ENTERED IN ERROR - IMPACT FEES HAVE NOT BEEN
 ASSESSED YET.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-10 Cont ID  
Sent By rmcdouga Date 2020-11-10 Time 07:41 Rev Time 0.00
Received By rmcdouga Date 2020-11-10 Time 07:34 Sent To  
Notes
2020-11-10 07:42:49PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-06-14 Cont ID  
Sent By medwards Date 2021-06-14 Time 06:50 Rev Time 0.00
Received By medwards Date 2021-06-14 Time 06:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-02-04 Cont ID  
Sent By medwards Date 2021-02-04 Time 08:41 Rev Time 0.00
Received By medwards Date 2021-02-04 Time 08:41 Sent To  
Notes
2021-02-04 08:43:30THE CFM'S OF THE SPECIFIED EXHAUST FAN IS 194 CFM, EACH
 GARAGE MUST HAVE MINIMUM EXHAUST REQUIRED. FBC M TABLE
 403.3.1.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-09 Cont ID  
Sent By medwards Date 2020-11-09 Time 11:45 Rev Time 0.00
Received By medwards Date 2020-11-09 Time 11:44 Sent To  
Notes
2020-11-09 11:45:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100899
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE VENTILATION CALCULATIONS FOR EACH
 GARAGE AND PROVIDE THE CORRECT SIZE EXHAUST FAN FOR
 EACH. FBC M TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2021-07-08 Cont ID  
Sent By rmcdouga Date 2021-07-08 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2021-07-08 Time 10:45 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2021-06-15 Cont ID  
Sent By pvalenti Date 2021-06-15 Time 08:23 Rev Time 0.00
Received By pvalenti Date 2021-06-14 Time 13:00 Sent To  
Notes
2021-06-15 08:27:44****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 NFIP REVIEW DENIED:
  
 1) FBC B 107.2.1,PROVIDE MORE INFORMATION IN THE
 COMMENT SECTION "D" OF THE ELEVATION CERTIFICATE.
 PLEASE ADD NOTES ABOUT THE REQUIRED SMART VENTS MODEL
 NUMBERS FOR EXTERIOR WALLS(NON-RATED WALLS) AND FOR
 INTERIOR(RATED WALLS).
 2) FBC B 107.2.1, PLEASE CLARIFY INFORMATION ON SHEET
 GAIA-OSP AS TO DFE OF 16.0' DUE TO THE CITY'S REQUIRED
 2.0' FREEBOARD FROM CITY ORDENANCE 4729.17. THE NOTES
 ON SHEET GAIA-OSP ARE NOT CLEAR.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2021-02-16 Cont ID  
Sent By rmcdouga Date 2021-02-16 Time 11:52 Rev Time 0.00
Received By rmcdouga Date 2021-02-16 Time 11:52 Sent To  
Notes
2021-02-16 11:52:50THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA,
 AE. THE BFE IS 14' NAVD88. THE CITY OF WEST PALM
 BEACH'S FLOOD ORDINANCE ADDS A TWO FOOT FREE BOARD TO
 THE BFE WHICH MAKES THE DFE 16'. AS OF OCTOBER 5TH,
 2017, THE CITY HAS ADOPTED NEW FLOOD INSURANCE RATE
 MAPS WHICH USE NAVD 88 AS THE VERTICAL DATUM. THE CITY
 ALSO ADOPTED A 2' FREEBOARD WHICH REQUIRES THE FINISH
 FLOOR AND EQUIPMENT TO BE A MINIMUM OF TWO FEET ABOVE
 THE BFE. ACCORDING TO THE FLOOD INSURANCE RATE MAP
 WHICH WAS ADOPTED ON OCTOBER 5, 2017 AND IS APPLICABLE
 TO THIS PROJECT, THE STRUCTURE IS IN AN AE FLOOD ZONE
 WHICH IS A SPECIAL FLOOD HAZARD AREA. THE CITY OF WEST
 PALM BEACH HAS ADOPTED A FLOOD ORDINANCE THAT REQUIRES
 A TWO (2) FOOT FREE BOARD. SPECIFY ALL ELEVATIONS IN
 NAVD 88. THREE ELEVATION CERTIFICATES ARE REQUIRED TO
 BE SUBMITTED. 1) A PRE-CONSTRUCTION ELEVATION
 CERTIFICATE BASED ON THE CONSTRUCTION PLANS IS REQUIRED
 BEFORE THE PERMIT IS ISSUED. 2) A BUILDING UNDER
 CONSTRUCTION ELEVATION CERTIFICATE WHEN FIRST FLOOR
 SLABS ARE POURED. 3) A FINISHED CONSTRUCTION ELEVATION
 WHEN THE JOB IS COMPLETE INCLUDING LANDSCAPING. THE
 FINAL ELEVATION CERTIFICATE IS REQUIRED TO BE SUBMITTED
 AND APPROVED BEFORE THE C.O. WILL BE ISSUED. SEE
 BUILDING COMMENTS FOR ADDITIONAL COMMENTS.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2020-11-10 Cont ID  
Sent By rmcdouga Date 2020-11-10 Time 09:25 Rev Time 0.00
Received By rmcdouga Date 2020-11-10 Time 09:25 Sent To  
Notes
2020-11-10 09:25:58THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA,
 AE. THE BFE IS 14' NAVD88. THE CITY OF WEST PALM
 BEACH'S FLOOD ORDINANCE ADDS A TWO FOOT FREE BOARD TO
 THE BFE WHICH MAKES THE DFE 16'. AS OF OCTOBER 5TH,
 2017, THE CITY HAS ADOPTED NEW FLOOD INSURANCE RATE
 MAPS WHICH USE NAVD 88 AS THE VERTICAL DATUM. THE CITY
 ALSO ADOPTED A 2' FREEBOARD WHICH REQUIRES THE FINISH
 FLOOR AND EQUIPMENT TO BE A MINIMUM OF TWO FEET ABOVE
 THE BFE. ACCORDING TO THE FLOOD INSURANCE RATE MAP
 WHICH WAS ADOPTED ON OCTOBER 5, 2017 AND IS APPLICABLE
 TO THIS PROJECT, THE STRUCTURE IS IN AN AE FLOOD ZONE
 WHICH IS A SPECIAL FLOOD HAZARD AREA. THE CITY OF WEST
 PALM BEACH HAS ADOPTED A FLOOD ORDINANCE THAT REQUIRES
 A TWO (2) FOOT FREE BOARD. SPECIFY ALL ELEVATIONS IN
 NAVD 88. THREE ELEVATION CERTIFICATES ARE REQUIRED TO
 BE SUBMITTED. 1) A PRE-CONSTRUCTION ELEVATION
 CERTIFICATE BASED ON THE CONSTRUCTION PLANS IS REQUIRED
 BEFORE THE PERMIT IS ISSUED. 2) A BUILDING UNDER
 CONSTRUCTION ELEVATION CERTIFICATE WHEN FIRST FLOOR
 SLABS ARE POURED. 3) A FINISHED CONSTRUCTION ELEVATION
 WHEN THE JOB IS COMPLETE INCLUDING LANDSCAPING. THE
 FINAL ELEVATION CERTIFICATE IS REQUIRED TO BE SUBMITTED
 AND APPROVED BEFORE THE C.O. WILL BE ISSUED. SEE
 BUILDING COMMENTS FOR ADDITIONAL COMMENTS.
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-12-01 Cont ID  
Sent By lcrespo Date 2020-12-01 Time 15:46 Rev Time 0.00
Received By lcrespo Date 2020-11-04 Time 11:08 Sent To  
Notes
2020-12-01 15:46:44NO PLUMBING IN DETACHED GARAGES PER THE SCORE OF WORK.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status N Date 2021-07-08 Cont ID  
Sent By rmcdouga Date 2021-07-08 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2021-07-08 Time 10:45 Sent To  
Notes
2021-07-08 10:47:24ROOFING PRODUCT APPROVALS HAVE BEEN DEFERRED.
 CONTRACTOR IS TO SUBMIT THE ROOFING PRODUCT APPROVALS
 FOR REVIEW THAT HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2021-06-15 Cont ID  
Sent By pvalenti Date 2021-06-15 Time 11:22 Rev Time 0.00
Received By pvalenti Date 2021-06-14 Time 12:59 Sent To  
Notes
2021-06-15 11:23:45****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ROOFING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE ROOFING
 SYSTEM/UNDERLAYMENT PRODUCT APPROVALS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-02-16 Cont ID  
Sent By rmcdouga Date 2021-02-16 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2021-02-16 Time 11:50 Sent To  
Notes
2021-02-16 11:51:25ROOFING PRODUCT APPROVALS ARE NOT COMPLETE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-11-10 Cont ID  
Sent By rmcdouga Date 2020-11-10 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2020-11-10 Time 07:34 Sent To  
Notes
2020-11-10 07:41:30NO PRODUCT APPROVALS WERE SUBMITTED FOR THE CEMENT TILE
 ROOF OR ROOF VENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-07-08 Cont ID  
Sent By rmcdouga Date 2021-07-08 Time 12:49 Rev Time 0.00
Received By rmcdouga Date 2021-07-08 Time 12:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-14 Cont ID  
Sent By medwards Date 2021-06-14 Time 06:53 Rev Time 0.00
Received By medwards Date 2021-06-14 Time 06:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-02-04 Cont ID  
Sent By medwards Date 2021-02-04 Time 09:41 Rev Time 0.00
Received By medwards Date 2021-02-04 Time 09:41 Sent To  
Notes
2021-02-04 09:43:13THE SIGNATURE AND SEAL ON THE SOIL REPORT APPEARS TO BE
 A COPY OF THE ORIGINAL. PLEASE EITHER PROVIDE A DIGITAL
 ORIGINAL SIGNED AND SEALED COPY OR YOU CAN BRING AN
 ORIGINAL SIGNED AND SEALED PAPER REPORT TO OUR OFFICE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-09 Cont ID  
Sent By medwards Date 2020-11-09 Time 12:25 Rev Time 0.00
Received By medwards Date 2020-11-09 Time 12:21 Sent To  
Notes
2020-11-09 12:25:04SHEETS LISTED BELOW MUST BE DIGITALLY SIGNED AND SEALED
 BY THE DESIGNER: STRUTURAL CALCULATIONS, SOILS REPORT,
 COVER SHEET, SURVEY, C-107, C-171, C-172,
 C-173,OVERALLL SITE PLAN.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-06-14 Cont ID  
Sent By jroach Date 2021-06-14 Time 09:30 Rev Time 0.00
Received By jroach Date 2021-06-14 Time 09:28 Sent To  
Notes
2021-06-14 09:30:53ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 06.14.2021
 PERMIT NO.: 20100899
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE SCOPE OF THIS PERMIT REVIEW IS LIMITED TO GARAGE
 TYPE 1A ONLY. SEPARATE PERMITS REQUIRED FOR ALL OTHER
 BUILDINGS, SURROUNDING SITE WORK, FENCING, LANDSCAPING,
 IRRIGATION, ETC.
  
 2. THE BROADSTONE LAKESIDE RESIDENTIAL PLANNED
 DEVELOPMENT SHALL BE SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS AS OUTLINED IN RESOLUTION NO. 106-20, AND AS
 MAY BE AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY
 RESOLUTION NO. 106-20, AS AMENDED, SHALL BE ADDRESSED
 WITHIN THE APPROPRIATE SPECIFIED TIMEFRAMES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-02-05 Cont ID  
Sent By jroach Date 2021-02-05 Time 11:39 Rev Time 0.00
Received By jroach Date 2021-02-05 Time 11:39 Sent To  
Notes
2021-02-05 11:39:35ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 02.05.2021
 PERMIT NO.: 20100899
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ SATISFIED ] - ALL LANDSCAPE PLANS, ETC. SHALL BE
 REMOVED FROM THE BUILDING PERMIT SUBMITTAL AND
 SUBMITTED AS PART OF SEPARATE PERMIT APPLICATIONS. THE
 ONLY PLANS THAT SHOULD BE SUBMITTED WITH THIS PERMIT
 APPLICATION ARE THOSE THAT ARE NECESSARY FOR THE REVIEW
 AND ISSUANCE OF THIS PERMIT. ALL PLANS ASSOCIATED WITH
 SEPARATE PERMITS SHOULD BE REMOVED FROM THE SUBMITTAL.
  
 2. [ NOT SATISFIED ] - AS MODIFICATIONS HAVE BEEN MADE
 SINCE ADOPTION OF THE DEVELOPMENT ORDER (RESOLUTION NO.
 106-20), A MINOR AMENDMENT SHALL BE SUBMITTED TO AND
 APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT ?
 PLANNING DIVISION. THIS IS WITH THE ASSUMPTION AND
 FUTURE CONFIRMATION THAT NONE OF THE CHANGES TRIGGER
 THE THRESHOLD FOR A MAJOR AMENDMENT, AS SPECIFIED IN
 THE CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 3. [ SATISFIED ] - PURSUANT TO RESOLUTION NO. 106-20,
 PRIOR TO THE ISSUANCE OF ANY BUILDING PERMIT:
  
 3.1. [ SATISFIED ] - THE DEVELOPER SHALL PAY TO THE
 CITY OF WEST PALM BEACH A CONTRIBUTION IN THE AMOUNT OF
 $30,000 TOWARD TO COST OF A SAFETY STUDY FOR VILLAGE
 BOULEVARD.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-11 Cont ID  
Sent By jroach Date 2020-12-11 Time 13:15 Rev Time 0.00
Received By jroach Date 2020-12-11 Time 13:15 Sent To  
Notes
2020-12-11 13:15:49ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 12.11.2020
 PERMIT NO.: 20100899
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ALL LANDSCAPE PLANS, ETC. SHALL BE REMOVED FROM THE
 BUILDING PERMIT SUBMITTAL AND SUBMITTED AS PART OF
 SEPARATE PERMIT APPLICATIONS. THE ONLY PLANS THAT
 SHOULD BE SUBMITTED WITH THIS PERMIT APPLICATION ARE
 THOSE THAT ARE NECESSARY FOR THE REVIEW AND ISSUANCE OF
 THIS PERMIT. ALL PLANS ASSOCIATED WITH SEPARATE PERMITS
 SHOULD BE REMOVED FROM THE SUBMITTAL.
  
 2. AS MODIFICATIONS HAVE BEEN MADE SINCE ADOPTION OF
 THE DEVELOPMENT ORDER (RESOLUTION NO. 106-20), A MINOR
 AMENDMENT SHALL BE SUBMITTED TO AND APPROVED BY THE
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION.
 THIS IS WITH THE ASSUMPTION AND FUTURE CONFIRMATION
 THAT NONE OF THE CHANGES TRIGGER THE THRESHOLD FOR A
 MAJOR AMENDMENT, AS SPECIFIED IN THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 3. PURSUANT TO RESOLUTION NO. 106-20, PRIOR TO THE
 ISSUANCE OF ANY BUILDING PERMIT:
  
 3.1. THE DEVELOPER SHALL PAY TO THE CITY OF WEST PALM
 BEACH A CONTRIBUTION IN THE AMOUNT OF $30,000 TOWARD TO
 COST OF A SAFETY STUDY FOR VILLAGE BOULEVARD.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved